Consumer units. designed for modern living THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Consumer units designed for modern living THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DESIGN is all around us Modern i...
45 downloads 1 Views 1MB Size
Consumer units designed for modern living

THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

DESIGN is all around us Modern interiors revolve around minimalist, sophisticated interior design themes consisting of clean lines, neutral tones and maximised use of space. Designed to blend in with the modern environment, Legrand’s new consumer units are perfectly placed to stand the test of time.

CONSUMER UNITS... DESIGN OF THE TIMES Legrand’s insulated and metal consumer units are manufactured to white RAL 9003, creating a stylish, understated inish which blends in perfectly with modern interiors.

MEETING THE DEMANDS OF MODERN LIVING There is an increasing demand for additional electrical circuits due to the popularity of smart home solutions, and a growing requirement for dedicated circuits for items such as hard wired smoke detectors, photovoltaic panels and electric vehicle charging points. Legrand’s consumer units are available with up to 22 ways, including a custom build option which offers complete choice and lexibility.

Discreet semi-flush mounting option available

Increasing popularity of home automation and control

Growth in requirement for dedicated circuits

The demands of modern living have led to the requirement for an increased number of electrical circuits WWW.LEGRAND.CO.UK

3

design is more than skin deep Rigid base with multiple cut-outs

Removable pan assembly

Removable terminal holders with screws in backed-off position

Cut-to-length busbar for lexible on-site coniguration Rail positioned for maximum cabling space

4

With an array of design innovations making them easy to install, Legrand’s consumer units save valuable time and money during installation... allowing you to relect on the generous wiring space and the all-round extra protection.

White RAL 9003 case with high ire retardancy. Self extinguishing at 750°C

Insulated shield

Hinged door conceals protection devices and labelling

Legrand consumer units are itted as standard with 80 A RCDs

Guide to choosing the right consumer unit coniguration under the 17th Edition Dual RCD split load with dedicated main switch ways Select MCBs and RCBOs to complete installation

EASY ACCESS Features include a removable pan assembly, earth terminal holder that simply clips into place, and multiple cut-outs to the unit’s back, bottom, top and sides.

ON-SITE CONFIGURATION

Dual RCD split load Select MCBs to complete installation

Main switch incomer Select RCBOs to complete installation

For lexible on-site coniguration, simply cut busbar to the required length.

RCD incomer Select MCBs to complete installation

PROTECTION OPTIONS Legrand has everything you need to complete your installation: isolating switches, RCDs, NEW RX3 MCBs and RCBOs. Custom build Maximum lexibility

WWW.LEGRAND.CO.UK

5

NEW

consumer units insulated and metal

Insulated consumer units Conform to BS EN 60439-3. IP 30. RAL 9003. White colour. Plain door opens downwards Supplied with neutral and earth terminals completely assembled. Supplied with 5 module spare blank plate Factory fitted link leads for both neutral and live connections. Configurable outgoing ways Self-extinguishing at 750 °C. UL 94 V2 material for improved flame retardancy. Robust thermoplastic construction. 4 fixing holes

Dimensions p. 11

Total outgoing ways 2

4

6

8

10

12

14

16

18

20

22

High integrity dual RCD split load with 2 unprotected ways 100 A main switch and 2 x 80 A 30 mA RCD









6075 70





6075 71







Dual RCD split load 100 A main switch and 2 x 80 A 30 mA RCD









6075 57





6075 58







Dual RCD split load semi flush 100 A main switch and 2 x 80 A 30 mA RCD









8204 10





8204 09







Main switch incomer 63 A main switch

6075 63





















Main switch incomer 100 A main switch





6075 59



6075 60



6075 66





6075 67



RCD incomer 80 A 30 mA RCD





6075 64



6075 65













Custom build



6075 68



6075 61



6075 62











Metal consumer units Conform to BS EN 60439-3. IP 30. RAL 9003. White colour. Plain door opens downwards Supplied with neutral and earth terminals completely assembled. Supplied with 5 module spare blank plate Factory fitted link leads for both neutral and live connections. Configurable outgoing ways Pre-galvanised steel for strength and rigidity. Epoxy/polyester powder coated base and lid

Dimensions p. 12

6

8

10

12

14

16

18

20

22

Dual RCD split load 100 A main switch and 2 x 80 A 30 mA RCD





6065 57





6065 58







Main switch incomer 100 A main switch

6065 59



6065 60















6065 61



6065 62



6065 50





6065 51

Custom build

6

Total outgoing ways

protection devices MCBs and RCBOs

RX3 residential MCBs - 6 kA

RX3 MCBs - 6 kA Breaking capacity : 6 kA to BS EN 60898-1

Single pole - 230/400 V

RCBOs (combined MCB/RCD)

±

Single pole and neutral - 240 V

±

RCBOs (combined MCB/RCD) Breaking capacity : 10 kA to BS EN 61009-1 RCD type AC conform to BS EN 61009-1 Terminal capacity : rigid conductor 35 mm2 flexible conductor 25 mm2

4022 70

6064 18

Nominal rating (In)

Pack Qty

Number of 17.5 mm modules

B curve

C curve

Number of 17.5 mm modules

30 mA B curve

6A

10

1

4022 70

4023 10

1

6064 16

10 A

10

1

4022 71

4023 11

1

6064 17

16 A

10

1

4022 72

4023 13

1

6064 18

20 A

10

1

4022 73

4023 14

1

6064 19

25 A

10

1

4022 74

4023 15





32 A

10

1

4022 75

4023 16

1

6064 20

40 A

10

1

4022 76

4023 17

1

6064 21

50 A

10

1

4022 77

4023 18

1

6064 28

63 A

10

1

4022 78

4023 19





7

insulated consumer units surface mounting

6075 57

6075 71

6075 63

6075 64

Dimensions p.11 Conform to BS EN 60439-3. IP 30. RAL 9003 - white colour Self-extinguishing at 750 °C - UL 94 V2 material for improved flame retardancy Robust, rigid thermoplastic construction with 4 fixing holes Door opens downwards Supplied with neutral and earth terminals completely assembled Supplied with 5 module spare blank plate (except 4 module unit) MCBs to be ordered separately, (see p. 10) Rigid base with multiple cut-outs Removable terminal holders with screws in backed-off position Insulated shield Cut-to-length busbar Removable pan assembly Pack

Cat. Nos.

Insulated high integrity dual RCD split load with 2 unprotected ways - surface mounting

NEW 1

16 module unit (8 + 2 ways available) 6075 70 With 100 A main switch and 2 x 80 A 30 mA RCD

1

22 module unit (13 + 3 ways available) 6075 71 With 100 A main switch and 2 x 80 A 30 mA RCD

New image VC to supply

RX3 residential MCBs and single module RCBOs

Pack

Cat. Nos.

Accessories for surface mounting units

NEW

16 module unit (10 ways available) 6075 57 With 100 A main switch and 2 x 80 A 30 mA RCD

1

22 module unit (16 ways available) 6075 58 With 100 A main switch and 2 x 80 A 30 mA RCD

Insulated dual RCD split load - semi-flush mounting 1

16 module unit (10 ways available) 8204 10 With 100 A main switch and 2 x 80 A 30 mA RCD

1

22 module unit (16 ways available) 8204 09 With 100 A main switch and 2 x 80 A 30 mA RCD

1 1

3

8

4 module unit 6075 63 With 63 A main switch (2 ways available)

1 1

8 module unit 6075 59 With 100 A main switch (6 ways available) 6075 64 With 80 A 30 mA RCD (6 ways available)

1 1

12 module unit 6075 60 With 100 A main switch (10 ways available) 6075 65 With 80 A 30 mA RCD (10 ways available)

1

16 module unit 6075 66 With 100 A main switch (14 ways available)

1

22 module unit 6075 67 With 100 A main switch (20 ways available)

Padlock 4063 13 Ø 4 m

Accessories for semi-flush mounting units 1 1

Lockable brackets 8204 71 For 16 module unit 8204 72 For 22 module unit

NEW 3

1

Lockable brackets 8218 57 For 16 module unit 8218 58 For 22 module unit

NEW

Insulated with incomer - surface mounting NEW

Insulated custom build - surface mounting

Allow several configurations when using kits and incomers (isolating switches, RCDs, RCBOs) For kits, (see p. 215) NEW For incomers and outgoing devices, (see p. 10) 1 6075 68 4 modules available 1 6075 61 8 modules available 1 6075 62 12 modules available

Insulated dual RCD split load - surface mounting 1

p. 10

Padlock 4063 13 Ø 4 m

metal consumer units

NEW ay 2013 le M b a il a v A

surface mounting

accessories for insulated and metal consumer units

RX3 residential MCBs and single module RCBOs

p. 10

6065 62

Dimensions p. 12 Conform to BS EN 60439-3. IP 30. RAL 9003 - white colour Pre-galvanised steel for strength and rigidity Door opens downwards Supplied with neutral and earth terminals completely assembled Supplied with 5 module spare blank plate MCBs to be ordered separately, (see p. 10) Pack

1 1

Cat. Nos.

Metal dual RCD split load - surface mounting

16 module unit (10 ways available) 6065 57 With 100 A main switch and 2 x 80 A 30 mA RCD 22 module unit (16 ways available) 6065 58 With 100 A main switch and 2 x 80 A 30 mA RCD

Pack

1 1

Metal custom build - surface mounting

1 1 1 1

6065 6065 6065 6065

61 62 50 51

Epoxy/polyester powder coated base and lid Stand-off feet complete with keyhole fixing Allow several configurations when using kits and incomers (isolating switches, RCDs, RCBOs) For kits, (see opposite) For incomers and outgoing devices, (see p. 10) 8 modules available 12 modules available 16 modules available 22 modules available

Accessories

1

Incomer or dual tariff kit 6075 19 Comprises : 1 flexible neutral (blue) lead 1 rigid neutral link

1

Split load kit 6075 39 Comprises : 1 flexible live (brown) lead 1 flexible neutral (blue) lead 2 rigid neutral links

Metal with incomer - surface mounting Epoxy/polyester powder coated base and lid Stand-off feet complete with keyhole fixing 8 module unit 6065 59 With 100 A main switch (6 ways available) 12 module unit 6065 60 With 100 A main switch (10 ways available)

Cat. Nos.

1

Split load dual tariff kit (for insulated units only) 6075 49 Comprises : 1 flexible live (brown) lead 2 flexible neutral (blue) leads 2 rigid neutral links 1 neutral terminal

NEW 20

Spare blank plate RAL 9003 0016 60 5 modules - white colour

10

Spare blank plate RAL 9010 0016 64 18 module, separable by single or half modules

5

Spare busbar 6075 99 21 prongs

NEW 10 2

Spacing elements 4063 07 0·5 module

Locking device for MCBs and RCDs 4063 03 Locking attachment for Ø 4 mm and Ø 6 mm padlocks

NEW 3

Padlock for MCBs and RCDs 4063 13 Padlock Ø 4 m

1

Spare terminal block 8204 07 13 hole

10

Self-adhesive label holder 0049 96 Width : 16 mm Width available for marking : 12 mm Length 530 mm (24 modules)

0049 96

9

protection and control devices

4022 70

4020 27

6064 18

Pack

RX3 residential MCBs - 6 kA

Cat. Nos.

Pack

4064 55 Cat. Nos.

Breaking capacity : 6 kA to BS EN 60898-1 Single pole - 230/400 V B curve 10 10 10 10 10 10 10 10 10

4022 4022 4022 4022 4022 4022 4022 4022 4022

70 71 72 73 74 75 76 77 78

C curve

4023 4023 4023 4023 4023 4023 4023 4023 4023

10 11 13 14 15 16 17 18 19

Nominal rating (In)

6 10 16 20 25 32 40 50 63

Number of 17·5 mm modules

1 1 1 1 1 1 1 1 1

C

1 1 1 1 1 1 1 1

1 10 10 1 1 1 1 1

B curve

4074 4074 4074 4074 4074 4074 4074 4074

29 30 32 33 35 36 37 38

C curve

4076 4076 4076 4076 4076 4076 4076 4076

66 68 70 71 73 74 75 76

Nominal rating (In)

6 10 16 20 32 40 50 63

A A A A A A A A

1 1 1

4020 4020 4020 4020

25 40 63 80 100 mA 4020 28 25 4020 29 40 4020 30 63

±

1 1 1 1 1 1 1

6064 6064 6064 6064 6064 6064 6064

16 17 18 19 20 21 28

30 mA

6 10 16 20 32 40 50

A A A A A A A

1 1 1 1 1 1 1 1

24 25 26 27

A A A A

2 2 2 2

A A A

2 2 2

Conform to BS EN 60947-3, IEC 60669-1 Usage : AC 22 according to IEC 60947-3 Red handle Double break contacts, padlockable 50 mm2 capacity shielded terminals

NEW 5 5

±

Number of 17·5 mm modules

4064 53 63 A double pole 4064 55 100 A double pole

2 2

± coil

CX3 Contactor with 230 V Conforms to BS EN 61095 Double pole (L + N) 250 V 230 V coil circuit

NEW

±

±

I max.

Type of contact

Number of 17·5 mm modules

2 N/O

1

230 V

1

Number of 17·5 mm modules

4125 44 25 A

For other contactors, see current Industrial and Power Protection catalogue

1 1 1 1 1 1 1

Bell transformers

d

Conform to IEC/EN 61558-2-8 Supplied with label holder Protected against overloads and short circuits Power to 8 V-12 V or 24 V access control devices such as bells and chimes Possibility for supply busbars to run through (Cat. Nos. 4130 90/91) Number Secondary (V)

1 1 1

10

Number of 17·5 mm modules

DX3 Isolating switches

Number of 17·5 mm modules

Breaking capacity : 10 kA to BS EN 61009-1 RCD type AC conform to BS EN 61009-1 Terminal capacity : rigid conductor 35 mm2 flexible conductor 25 mm2 Single pole and neutral - 240 V Nominal rating (In)

±

Nominal rating (In)

30 mA 1 1 1 1

RCBOs (combined MCB/RCD) Single module

B curve

RX3 residual current devices (RCDs)

Type AC

DX3 multi-purpose MCBs - 10 kA

B

NEW

Breaking capacity : 10 kA to BS EN 60947-2 Single pole - 230/400 V

NEW

4130 91

Conform to BS EN 61008-1 Terminal capacity : rigid conductor 35 mm2 flexible conductor 25 mm2 Double pole 230 V

±

A A A A A A A A A

4125 44

NEW 230 V / 8 V 4130 90 8 V

±

Rating (A)

Power (VA)

of 17·5 mm modules

0·5 A

4 VA

2

8 VA

2

24/18 VA

4

230 V / 12 V - 8 V 4130 91 12/8 V 0·66/1 A 230 V / 24 V - 12 V 4130 93 24/12 V 1/1·5 A

±

±

insulated consumer units surface mounting n Insulated - surface mounting dimensions (mm)

n 8 module unit Back box fixing centres and cable entries (mm)

110 2 cut-outs 50 x 50

2 cut-outs 40 x 50

40 20

View from above

50

A

B

6 cut-outs 20 x 25

8 cut-outs 25 x 25

View from sides

Modules

A (mm)

B (mm)

4

140

225

8

212

225

12

298

225

14/16

370

225

20/22

478

225

114

225

50

2 cut-outs 20 x 25

195 162

6 cut-outs 20 x 25

n 4 module unit Back box fixing centres and cable entries (mm) 1 cut-out 40 x 50

n 12 module unit

40 20 4 cut-outs 20 x 25

Back box fixing centres and cable entries (mm) View from above

2 cut-outs 50 x 50

2 cut-outs 40 x 50

40 20

4 cut-outs 25 x 25 View from sides

50

1 cut-out 50 x 50

50

View from above

View from below

6 cut-outs 20 x 25

2 cut-outs 20 x 18.5

22 cut-outs 25 x 20

114

225

2 cut-outs 20 x 25

View from sides

90

225 180

2 cut-outs 20 x 25

4 cut-outs 20 x 25 268

View from below

2 cut-outs 20 x 25

2 cut-outs 20 x 18.5

View from below

11

insulated consumer units

metal consumer units

surface mounting (continued)

surface mounting

n 14/16 module unit

n Metal - surface mounting dimensions (mm)

Back box fixing centres and cable entries (mm) A 2 cut-outs 50 x 50

113

50

2 cut-outs 40 x 50

B

40 20

View from above

10 cut-outs 20 x 25

View from sides

50

30 cut-outs 25 x 20

225 180

2 cut-outs 20 x 25

340

Modules

A (mm)

B (mm)

8

219

235

12

305

235

16

377

235

22

485

235

200

n 8 module unit

8 cut-outs 20 x 25

Back box fixing centres and cable entries (mm) 4 cut-outs Ø 32

View from below View from above

n 20/22 module unit Back box fixing centres and cable entries (mm) 2 cut-outs 50 x 50

2 cut-outs 40 x 50

1 obround cut-out 100 x 50

12 cut-outs 20 x 25 42 cut-outs 25 x 20

View from sides

225 180

2 cut-outs 20 x 25

View from below

12

View from below

1 cut-out Ø 25

448

2 cut-outs 20 x 22

Ø9

10 cut-outs 20 x 25

3

2 cut-outs 20 x 22

4

Ø5 95

40 20

50

80

View from above

100

metal consumer units surface mounting (continued) n 12 module unit

n 22 module unit

Back box fixing centres and cable entries (mm)

Back box fixing centres and cable entries (mm) 4 cut-outs Ø 25

4 cut-outs Ø 32

View from above

View from above

175

350 120

80

1 obround cut-out 100 x 50

95

95

80

2 obround cut-outs 100 x 50

100

275 View from below View from below 2 cut-outs Ø 20

2 cut-outs Ø 25

8 cut-outs Ø 20

4 cut-outs Ø 32

n 16 module unit Back box fixing centres and cable entries (mm) 4 cut-outs Ø 20

View from above

250 120

95

80

2 obround cut-outs 100 x 50

175

View from below

4 cut-outs Ø 25

4 cut-outs Ø 32

13

Contact details United Kingdom Great King Street North, Birmingham, B19 2LF Customer Services: Tel: +44 (0) 845 605 4333 Fax: +44 (0) 845 605 4334 E-mail: [email protected] Quotations and Technical Support: Tel: +44 (0) 870 608 9020 Fax: +44 (0) 870 608 9021 E-mail: [email protected] Republic of Ireland: Tel: 01 295 9673 Fax: 01 295 4671 E-mail: [email protected]

Head ofice (UK and Ireland): Legrand Electric Limited Great King Street North, Birmingham, B19 2LF Tel: 0870 608 9000 Fax: 0870 608 9004 Website: www.legrand.co.uk

This document is printed on sustainably sourced paper. Please recycle.

The Legrand logo is a registered trademark of the Legrand group of companies.

Consumer unit product guide 04/2013.PDF