Building Management System

Building Automation System using LonWorks® technology Apice’s nodes based on LonWorks technology for the global automation of rooms (as Offices, Hotel Rooms and Others Residential Areas) are able to manage the following applications: 

Load activation Lighting; Socket; Heating system.



Security Fire alarm (smoke sensors management); Windows and door status; Bathroom alarm.



Temperature regulation Temperature probe; Setpoint regulation; Fancoil output.



Access control Mag or proximity card reader, Electric lock output.



Other utility Busy room/do not disturb information.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

LonWorks®Apice Building Management Terminals AC6400 General purpose I/O node; 6 insulated inputs, 4 power relay outputs. AC6400 is a general purpose I/O device equipped with 4 power relay outputs which can directly control 1 KW of resistive load at 220 VAC or 750 VA of reactive load (i.e. fluorescent lamps). It is used for lighting management and, in general, for room control (offices, common areas, etc…).

AC6400 APPLICATION EXAMPLES Example of Management office and common areas.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

The above example illustrates a simple, effective and economical solution for building automation. In each office a motion detector enables energy consumption. The lights can be turned on either automatically, depending on the level of daylight, either manually through a switch. A button removes manually the occupancy status. This status would have been revoked automatically after a certain programmable period of inactivity of the sensor. In the absence of people, the outputs are off, resulting in significant energy savings.

EXAMPLE FOR HOTEL AUTOMATION Solution 1: Room management: enabling load, monitoring of power and bathroom alarm. Everything is monitored by PC.

Inserting a card in the card holder inside the room the output, which enables lights, sockets and the heating of the room, is activated. When the card is removed from the pocket, lights and loads remain activated for a programmable time. The bathroom SOS is supervised 24h/24h. When it is activated, an audible alarm is generated, the room of origin is indicated and the event is recorded in the historical archive, as well as its time of examination and termination.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Solution 2: Room management with the enabling of the loads, the monitoring of presence of a guest or of the cleaning staff and the ‘cleaned up’ state of the room. Everything is monitored by PC. This solution doesn’t provide the bathroom alarm.

The guest card or the card of the cleaning staff will activate the output that enables the lights and loads of room. The supervisor will report in a different way the presence of one or other users. When the card is removed from the pocket, lights and loads remain activated for a programmable time. After the passage of the cleaning staff, on the supervisor the room will be reported as ‘cleaned up’ room and this state will last until the next day.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Solution 3: Room management with the enabling of the loads, the monitoring of power, the bathroom alarm, the monitoring of presence of a guest or of the cleaning staff and the ‘cleaned up’ state of the room. Everything is monitored by PC.

AC6400 module is used to manage two rooms. The intelligent card holder identifies whether the user is the guest or the cleaning staff. In the first case the output that enables loads and lights and the output that enables the heating system will be activated, while in the second case, the heating system will not be activated. When the card is removed from the pocket, lights and loads remain activated for a programmable time. After the passage of the cleaning staff, on the supervisor the room will be reported as ‘cleaned up’ room and this state will last until the next day. If the room is not assigned, it remains in the state of ‘cleaned up’ room for a configurable number of days. The bathroom SOS is supervised 24h/24h. When it is activated, an audible alarm is generated, the room of origin is indicated and the event is recorded in the historical archive, as well as its time of examination and termination. APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Solution 4: Room management with the enabling of the loads, the heating system, the monitoring of presence of a guest or of the cleaning staff and the ‘cleaned up’ state of the room and the bathroom alarm. Check of the door state and the window state for security and automation.

This solution maintains the functionality of solution 3. If the window is open and the customer is not in the room, an intrusion alarm will be activated and if the customer is in the room the heating system will be excluded in order to save energy. The door contact is used to activate the output of the lighting and loads at the time of opening the door.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Lon Series Modular system in LonWorks Technology LONM The series LON is composed of a master device "LONM" and one or more slave devices named "LONS". LONM is a CPU in LONWORKS technology for the control of actuators and sensors modular sensors. The combination of a LONM and one or more LONS is an excellent versatile and expandable solution for building automation systems. Each LONM allows the management of up to 8 terminals LONS. The modules of the LON Series (LONM and LONS) provide a connector labeled HBUS for easy connection between them. Connections LON series

+ + - -

A+ BGND

12-24 VDC/VAC

POW

RS485

Modulo Slave n

Modulo Slave 1 LON

Service LED

Service pin

LON TP/FT-10

LONM Technical features Power Supply

12-24 VDC/VAC

Consumption

70 mA

Chip

FT-5000

Transceiver Interface

LONWORKS FTT-10 78.1Kb/s 1 LON port (twisted pair), 1 RS485 port, HBUS

Case

Plastic, size: 35x90x60 mm (2 DIN modules)

Temperature

0°C +50°C

Umidity

10 - 95%

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Lon Series Modular system in LonWorks Technology LONS-IO Is a peripheral series interfacing device. Communicate directly with LONM, through the connector HBUS. It is an appliance dedicated to the physical control of sensors and actuators. Each LONS-IO handles 6 digital inputs, expandable up to 8, due to the availability of two universal inputs (analog or digital). It provides 3 analog inputs for a temperature sensor, a light sensor and a 0-10V signal. There are 4 digital relay outputs and 2 analog outputs of power. LONS—IO Technical features Power Supply

12-24 VDC/VAC (da HBUS)

Output voltages

12 VDC, 5VDC

Consumption

400 mA

Interface

HBUS, 1 door RS485

Digital Inputs Universal inputs (analog-digital)

6 2

Analog Inputs

3

Digital Outputs

4 (power relays: 10A 250VAC / 5A 30VDC)

Analog Outputs

2

Case

Plastic, size: 71x90x60 mm (4 DIN modules)

Temperature

0°C +50°C

Umidity

10 - 95%

LONSR-IO Is a peripheral series interfacing device. Communicate directly with LONM, through the connector HBUS. You can connect 2 card readers. Has an RS485 port for interfacing with one or more accessory devices (eg thermostat). Each LONSR-IO handles 4 digital inputs expandable up to 6, due to the availability of two universal inputs (analog or digital). Provides 2 analog inputs for a light sensor and a 0-10V signal. There are 4 digital relay outputs and 2 analog outputs. LONSR—IO Technical features Power Supply

12-24 VDC/VAC (da HBUS)

Output voltages

12 VDC

Consumption

500 mA

Interface Digital Inputs Universal inputs (analog-digital)

HBUS, 1 door RS485, 1 door RS485 HOST 4 2

Analog Inputs

2 (light sensor, 0-10 V)

Digital Outputs

4 (relay 1A 240VAC/30VDC)

Analog Outputs

2

Case

Plastic, size: 71x90x60 mm (4 DIN modules)

Temperature

0°C +50°C

Umidity

10 - 95%

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

AN 802 I/O analog data acquisition node, 8 analog inputs, 2 outputs OC 

I/O node for security sensor or clean contact acquisition, operating with LonWorks technology.



Is equipped with 8 inputs which can be programmed differently: to acquire ON/OFF signals or security signals with one or two balancing resistances.



The two Open Collector outputs permit activation of electrical devices using external interface relays.



Ideal for collecting security sensor status and sending them via network to a supervision system or to other field devices.

APPLICATION EXAMPLES Switches for lighting: Collection of 8 switches or buttons to control lighting or other loads. Sensors for security: Collection of 8 security sensors using two balancing resistors, in order to distinguish the alarm from the sabotage of the sensor or of the line connection. Card holder: Collection of 8 card holders to manage 8 rooms with the discrimination between the guest's presence and that of the cleaning staff. Temperature sensors: Collection of 4 temperature sensors + 4 card holders to manage 4 rooms with the discrimination between the guest's presence and that of the cleaning staff and the temperature maintenance.

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Other Modules



Input/output modules



Sunblind control modules



Climatic stations



Room Control Panels

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com

Software for Supervision SCADA Software for control and monitoring of the entire building (lighting, temperature, access control, etc..). It manages also: 

Fire Alarms system data acquisitions



Acquire and manage video camera information on CCTVs and IP Cameras. IP cameras manageable via Web.



Comfort and Climate (heating, air-conditioning, HVAC).

APICE Srl Via G.B. Vico, 45/B - 50053 Empoli (FI) E-mail: [email protected]; Web: www.apicesrl.com