Bitronics 70 Series Measurement System

Bitronics® 70 Series ® A Substation Automation Solution for Real-Time Monitoring and Event Recording The Bitronics 70 Series Measurement System is a...
Author: Ella Harvey
59 downloads 0 Views 4MB Size
Bitronics® 70 Series

®

A Substation Automation Solution for Real-Time Monitoring and Event Recording The Bitronics 70 Series Measurement System is a substation automation solution designed to satisfy the real-time monitoring and event recording needs of AC network operators.

70 Series

Bitronics

D/3

Orion

Measurement System

The Bitronics 70 Series Measurement System consists of four component types. These components form a real-time monitoring and event recording system for use in high voltage AC substations. The component types are monitoring and recording IEDs, detached displays, firmware, and software.

LAN

M870D

M871

M570DA

M571

ROUTER

M570DA

M571

• PREEMPT CATASTROPHIC EVENTS BY NEVER MISSING A DISTURBANCE • IMPROVE SECURITY OF OPERATION BY DESIGN

70 Series Measurement System Components COMPONENT 1: 70 Series Monitoring and Recording IEDs Each Monitoring and Recording IED has pre-arranged channel inputs for different substation elements - feeder, transformer, single bus, and dual bus. There are two families: • The Bitronics M57x Compact Family design optimizes lower prices for lesser options - options are built-in at time of order. • The Bitronics M87x Modular Family design has a wider operating frequency range and allows many more options to be added at any time. COMPONENT 2: 70 Series Displays The 70 Series displays give a choice for flush or surface switchboard mounting remotely from 70 Series IEDs.

• LOWER INVESTIGATIVE EXPENSE BY QUICK DIAGNOSIS OF THE CAUSE OF A DISTURBANCE

COMPONENT 3: 70 Series Firmware

• USE SUBSTATION LANs TO REDUCE YOUR AUTOMATION INVESTMENT COSTS

• Disturbance Recorders

• SOFTWARE TOOLS TO LOWER LIFE CYCLE COSTS

70 Series Firmware is imbedded in all 70 Series IEDs to support functions typically found in: • SOE Recorders • Trend Recorders • Revenue Meters • Power Quality Monitors • AC Switchboard Meters • SCADA Transducers COMPONENT 4: 70 Series Software 70 Series Software is an integrated set of PC-based programs to facilitate implementation and operation of the 70 Series Measurement System.

Bitronics

D/3

®

Orion

70 Series IED: M87x Modular Family This family consists of the following models: M871 Single Line, Dual Bus IED and M872 Dual Line, Dual Bus IED The Bitronics M87x Modular Family offers a broad range of configurations that allow field hardware upgrades, with these specs for each IED: • 14 Channels, up to 2 full buses • Up to 100A fault current • 56 DI Max & 24 DO Max • 16 transducer inputs • 3 Chassis sizes • 4 Serial Ports • Optional Ethernet Port & Modbus Plus • 8 AO Min by Optional Analog Output Converter • 70 Series Firmware & Software

M871 in Transformer Application

M872 shown in a breaker-and-a-half configuration. This configuration shares the same M872 hardware as in a full dual-feeder application requiring only a configuration change.

M871 with V10, P30A, P11, H11 & S10 (left to right) mounted in C07A5 chassis (8.5” (216mm) W x 5.2” (132mm) H)

Bitronics M87x Modules The Bitronics M87x IED can be configured by selecting the following modules and chassis at time of order. These modules can also be added after purchase up to the capacity of the chassis. • • • • • • • • • • • •

V10 Universal Power Supply P20 Modbus Plus P30A - 8/4 Digital I/O P31 - 16/4 Digital I/O P40 - 8 transducer inputs H11 - Host Processor A10 - Analog Processor P10 - Ethernet RJ45 10/100Mbs P11 - Ethernet P10 + 10Mbs Fiber P12 - Ethernet P10 + 100Mbs Fiber S10, S11, S12 - Signal Input M871 S13, S14, S15 - Signal Input M872

H11 Module with optional Flash memory up to 256MB

70 Series IED: M57x Compact Family This family consists of the following models:

Optional Ethernet

M571 Single Line, Dual Bus IED and M572 Dual Line, Dual Bus IED The Bitronics M57x Compact Family of IEDs offers fixed option configurations for less demanding applications with the following specs for each IED: • • • • • • • •

Up to 100A fault current available on either model Up to 14 Channels and 2 full buses Optional 4 DI & 4 DO Optional IRIG-B BNC input Optional 4 transducer inputs Optional Ethernet Unlimited AO by Analog Output Converter 70 Series Firmware & Software

G

Optional Status In Relay Out

M572 with Options indicated

I 1 (3 ph)

V 1 (3 ph)

I 2 (3 ph)

/// V 2 (1 ph)

M571 for Distributed Generation with sync check measurement support

Improve Security of Operation by Design: • Ensure enterprise-wide retrieval of event files without exposing relay IEDs to security issues. Using separate IEDs for monitoring and recording insures limited access by foreign intruders to the safety and protection systems as well as verifying the protection system operation. • If the relay doesn’t operate, the cause may never be known, so an independent IED is essential. • The common task of setting triggers can be done without the re-commissioning of the relay.

V 3 (2 ph)

F1

M572 shown in dual feeder application with common 3-Phase voltage plus reference voltages.

F2

®

Orion D/3 Bitronics

70 Series Firmware The 70 Series Firmware, common to all of the Bitronics 70 Series IEDs, allows the IEDs to satisfy a number of different applications. The firmware provides the following functions: • 6 simultaneous recorders • More than 2000 measurements covering 2 full buses on some models • Instantaneous, Demands, Harmonics to 63rd for LineCurrent, Bus Voltage L-N, L-L • Instantaneous, Demands, Real, Reactive, Apparent for Bus Power, total, per Ø • Bus 1 - Bus 2 Voltage Phase Angle and Slip Frequency per Ø • Energy monitoring with accuracy as high as 0.2% • Multiple ports & protocols • DNP3 (Serial or UDP/TCP), Modbus (Serial or TCP), UCA (including GOOSE messaging), FTP, telnet, Modbus Plus and IEC 61850-8-1 • Up to 15 remote displays • Up to 120 triggers, each of which can initiate any or all recorders • Accepts IRIG-B signal for time synchronization • Automatic event notification via ethernet or serial • Fault location (fault type and distance to fault)

Example of Frequency Disturbance

Each Bitronics 70 Series IED records and saves the events and trends based on user configured criteria. This criteria may include conditions associated with all the electrical parameters of the IED. This criteria can also include conditions observed by other IEDs connected on the same Local Area Network (LAN). The following gives example graphics derived from the 6 recorder files. Recorders 1 & 2 - Disturbance Voltage and frequency disturbances • Two independent disturbance recorders • Catch sags and swells in voltage supply • Record frequency deviations • Enough memory to store more than 8000 events

PREEMPT CATASTROPHIC EVENTS BY NEVER MISSING A DISTURBANCE: • Enable utility operation personnel to never miss the varying length of disturbances on an AC network by employing high fidelity multimode recorders with megabytes of non-volatile memory. • This includes disturbances such as faults, voltage sags and swells, frequency deviations and power swings.

Example of Voltage Disturbance

Recorder 3 & 4 - WaveForm Record waveform of all signals on any disturbance • Oscillography recording at 128 samples per cycle (option for 32 or 64, as well as 256 on a reduced number of channels for M871 and M571 only) • Adequate resolution to record any protection scheme miss-operation or nuisance tripping • Enterprise-wide retrieval of event files without exposing relay IEDs to security issues • Record only the channels you want divided among two recorders • Set event triggers without re-commissioning relays • Select from three triggering modes with hysteresis • Linear recording up to 100A symmetrical faults • Enough memory to store more than 1700 events

Oscillography (waveform) captured during a disturbance

Recorder 5 - Trend Forecast load demand and monitor voltage profile • Trend recorder • Record system planning and load profiling data for weeks • Monitor voltage or other parameter performance for weeks • Use trend data to identify system anomalies and to direct more detailed analysis of disturbance and waveform records • Enough memory to store more than 400 days of trend data Recorder 6 - Sequence of Events Record events in the order they happened • Sequence of events recorder • Quickly reconstruct the cause and effect of cascading operations • Time-stamp resolution to 1ms • Enough memory to store 5000 events

Trend any parameter over time. Display in graph and circular chart. Use to pinpoint system anomalies.

944 23-Feb-06 14:25:30.453949 Lower Unit (IP 218) RMS Volts A 1 is below 50 threshold (Manual trigger Hi Amps, Low Volts, Phase A.) 945 946 947 948 949 950 2148 2149 2150 2151 2152 2153 2154 2155 2156

23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06 23-Feb-06

14:25:30.455127 14:25:30.455555 14:25:30.456551 14:25:30.456952 14:25:30.457216 14:25:30.457833 14:25:30.461275 14:25:30.461275 14:25:30.461275 14:25:30.461275 14:25:30.466898 14:25:30.466898 14:25:30.466898 14:25:30.466898 14:25:30.469534

Lower Unit (IP 218) Lower Unit (IP 218) Lower Unit (IP 218) Lower Unit (IP 218) Lower Unit (IP 218) Lower Unit (IP 218) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103) Upper Unit (IP 103)

Merged Sequence of Events report from 2 IEDs with cross triggering

Virtual Output 1 has been set to 1 Goose User Status 001 has been turned on Waveform 1 Recorder Active is now 1 (Recorder Active.) Virtual Output 2 has been set to 1 Goose User Status 002 has been turned on Waveform Recorder 1 triggered M871:User Status 001 is now on Virtual Input 1 is now 1 M871:User Status 001 is now on Virtual Input 1 is now 1 (Received GOOSE US1: Incipient condition.) M871:User Status 002 is now on Virtual Input 2 is now 1 M871:User Status 002 is now on Virtual Input 2 is now 1 (Received GOOSE US2: Recorder Active.) Waveform Recorder 1 triggered

LOWER INVESTIGATIVE EXPENSES BY QUICK DIAGNOSIS OF THE CAUSE OF A DISTURBANCE: • Quickly reconstructs the cause/effect of cascading operations with enough fidelity and time resolution to troubleshoot any protection scheme misoperation or nuisance tripping with microsecond accuracy. • Operation costs can be lowered further with services from the NovaTech Services group. • Obtain expert advice from engineers, all with substation experience.

®

Orion D/3 Bitronics

70 Series Displays This family consists of the following models: • Bitronics M870D Remote Display • Bitronics M570DA Remote Display The 70 Series Displays provides a local presentation of any of the measured parameters- the display looks like a Bitronics digital meter but is driven remotely from the IED. Multiple values are displayed continuously & screens are scrollable and all fully configurable. Replaces Switchboard meters. M570DA Remote Display

M870D Detached Display Flush mounted through 4” round hole, separately powered • Remotely connected to either a M57x or M87x IED • Up to 1000 meters distant • Fits 4” round hole • Daisy-chain 15 from one 70 Series IED • Separate power supply

M570DA detached Display Lower cost, flexible surface mount with power from M57x IED • Remotely connected to M57x IED • 50 feet (15 meters) distant • Surface mount • Covers 4-inch round hole • Covers DIN 92mm openings

Front RS-232 passthrough port allows access to M57x IED from PC.

Move up and down through list of screens. If display is scrolling, the first button pressed will stop the scrolling.

Toggle display scroll On and Off.

Scroll through screens to “Home” screen. If display is scrolling, the first button pressed will stop the scrolling.

Features of the Bitronics 70 Series Displays

70 Series Software The 70 Series Software provides Windows® based tools to manage the configuration and the analysis of the multiple data provided by the 70 Series IED. This software consists of utility software and application software. 70 Series Utility Software • Configurator - Complete setup/configuration • BiView II - Instantaneous viewing and manual file retrieval • Retriever (part of BiView II) for automatic retrieving of files • 70 Series Utility Software can be provided at no charge on a utility CD 70 Series Application Software • Wavewin™ Bitronics - A high resolution COMTRADE file viewer • Win DR Manager - supports retrieving and automatically merging and displaying of COMTRADE files

Configurator Trigger Page

Win DR Manager BiView Dual Instantaneous view SOFTWARE TOOLS TO LOWER LIFE CYCLE COSTS: • A complete suite of user friendly software programs can greatly improve the startup costs of an automation system. • Firmware upgrade including remote capability further lower the life cycle costs of these highly advanced IEDs. • Automatic retrieval of event files and pre-defined archiving is essential.

BiView Synchro Data View from 70 Series Software

Bitronics® 70 Series

CT

CT

LAN

Router

VT

USE SUBSTATION LANS TO REDUCE YOUR AUTOMATION INVESTMENT: • Lower your initial investment by employing a LAN-based IED family that permits the initial purchase of just what you need for the current budgeted project but allows for easy expansion in the future. • Reduce investment further by employing switchyard grade IEDs that allow physical distribution into the yards, which provides further wiring cost savings. • Lower integration costs by incorporating this technology into distributed substation automation schemes.

The Engineer’s Choice

Copyright © 2010 NovaTech, LLC. All rights reserved. All brand and product names mentioned in this document are trademarks of their respective owners. NovaTech and Bitronics are registered trademarks of NovaTech, LLC. The information in this literature is subject to change without notice and is not to be construed as a warranty. BR_70Series_102010

Contact: NovaTech, LLC Bitronics Measurement and Recording 261 Brodhead Road Bethlehem, PA 18017

T: 610.997.5100 F: 610.997.5450 E: [email protected] www.novatechweb.com

70 Series

®

WAN

D/3

VT

Bitronics

Typical LAN configuration of a Bitronics 70 Series Measurement System. M871 IED (1), M870D Display (3), M571 (2) and M572 (1) IEDs, M570DA Display (2)

Orion