INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
APPLICATION OF FUZZY BASED THREE-PHASE INVERTER IN DISTRIBUTED GENERATION BY IMPLEMENTING UNIFIED CONTROL STRATEGY MUKKU MURALI1, DR. K VENKATESWARLU2 1 2
PG Scholar, Malineni, Lakshmaiah Engineering College, Andhra Pradesh, India
Assistant professor, Malineni, Lakshmaiah Engineering College, Andhra Pradesh, India
Abstract-By eliminating need of separate
generation system using the renewable energies is on
controllers or critical islanding detection, this paper
a falling trend and is expected to fall further as
proposes a fuzzy based three-phase inverter in
demand and production.
distributed generation which can be implemented for
DG delivers power to the utility and local critical
both islanded and grid-tied operations. In the
loads in grid-connected mode. Upon outage of any
proposed strategy the three-phase inverter is
generator connected to the utility the islanding is
regulated as just current source by inner inductor
formed. Under these situations, DG must be tripped
current loop in grid-tied and for islanding mode a
and must stop to energize according to IEEE standard
voltage loop in the synchronous reference frame will
929-2000. In order to continue to feed the local
automatically regulates the load voltage. This paper
critical load by disconnecting DG’s and some local
proposes a unified load current feedforward to
load in order to improve the power reliability. Load
maintain the grid current waveforms in grid-tied
voltage is fixed by the DG in the islanded mode and
mode and load voltage waveforms in islanding mode
by the utility in the grid mode operation. So,
to be undistorted even under nonlinear local load.
maintaining the load voltage is important. In order to
The effectiveness of the proposed strategy is
reduce transients in the load DG must take over the
validated by simulation.
load as soon as possible which is challenging
Index Terms— Fuzzy Logic Controller,
operation for the DG.
unified control, islanding, load current, seamless transfer, Distributed generation (DG), three-phase inverter, unified control.
In this paper voltage control mode is nothing but Droop-based control is used widely for the sharing of power among parallel inverters and can be applied to DG to realize power sharing between DG and utility
INTRODUCTION
in grid-tied mode [11-12]. Under this operation, load voltage is guaranteed during transitions of operation
The distributed generation (DG) concept
modes and inverter is regulated as voltage source by
emerged as a way to integrate different power plants,
voltage loop is good only steady-state performance
increasing the DG owner’s reliability, reducing
whereas dynamic performance is poor because
emissions, and providing additional power quality
bandwidth of voltage loop is higher than of the
benefits [4]. The cost of the distribution power
external power loop, realizing droop control. In
IJPRES
218
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
addition to the (phase locked loop) PLL and the
With the occurrence of utility outage the interval
virtual inductance, the inrush grid currents during
during to change it to voltage mode, the load voltage
transition from islanded mode to grid-tied mode
is neither regulated by DG nor fixed by the utility but
always exists it means grid current is not controlled
the length of the time interval is determined by the
directly [13].
islanding detection process. The main issue in this
Better dynamic performance can be achieved by
approach is that quality of load voltage can heavily
hybrid voltage and current mode type control for DG.
reliant on the speed islanding detection method
In which inverter is controlled as current source by
accuracy [7]-[10].second issue is under non-linear
one sets of controller in grid-tied mode, and as a
local load with aforementioned approaches is the
voltage source by other sets of controller in the
quality waveform of the grid current and load
islanded mode. Inrush grid currents are almost
voltage.
eliminated in the output by directly controlling the
The output current of DG is generally desired to be
output current in grid-tied mode. There is no need to
pure in
grid-tied mode
[13].
The harmonic
change the switch of the controller when the
component will fully flow into the utility when
operation mode of DG is changed, with the use of
nonlinear load is fed. The harmonic components of
hybrid voltage and current control mode.
the grid current can be mitigated by harmonics
Fig. 1. Schematic diagram of the DG based on the proposed control strategy.
injected by single-phase DG in [4]. DG will emulate
grid current in the grid-tied mode and on load voltage
a resistance at harmonic frequency is being controlled
in island mode and improving both of them for
by voltage mode control and then the harmonic
unified strategy is rarely used.
current flowing into the utility can be mitigated. In
This paper discusses about unified control strategy
the islanding mode, the nonlinear load may distort.
that avoids the aforementioned shortcomings. With a
With the use of multi-loop control method, resonant
given reference in the synchronous frame (SRF) the
controllers, sliding mode control and many control
three-phase inverter is controlled in DG act as a
schemes have been proposed to improve the quality
current source using traditional current loop. A novel
of the load voltage. Existing control strategies, DG
voltage controller is presented to supply reference for
with nonlinear local load will mainly concentrate on
the inner inductor current loop in D-axis and Q-axis
IJPRES 219
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
proportional-plus-integral (PI) compensator and a proportional (P) compensator are employed. The load
DISTRIBUTED GENERATION (DG)
voltage is dominated by the utility and the voltage
AND IT’S APPLICATIONS
compensator in D-axis is saturated, while the output of the voltage compensator in Q-axis is forced to be zero by the PLL. The reference of the inner current loop cannot be regulated by the voltage loop. With the occurrence of grid outage, the load voltage is no more determined by the utility. The voltage controller is automatically activated to regulate the load voltage. Hence proposed control strategy does not need a forced switching between two different sets of controllers. So, there is no need of detecting islanding quickly and accurately is no more critical in approach. For better dynamic performance, the proposed control strategy utilizes the feedback control for both current and voltage compares to voltage control mode. And paper is enhanced by introducing a unified load current feedforward, is implemented by adding the load current into the reference of the inner current loop in order to deal with the issue caused by the nonlinear local load. The benefits of the proposed load current feedforward can be extended into the islanded operation mode, due to the improved quality of the load voltage. This paper is arranged as follows. Section II discusses about Distributed generation (DG) and its applications. Section III describes the proposed unified control strategy for three phase inverter in DG which includes the power stage, the basic idea and control diagram. Section IV discuss about fuzzy logic controller. The parameter design and small signal analysis of the proposed control system are given in Section V. The simulation results for the proposed system are shown in Section VI. Finally, the conclusion and remarks are given in section VII.
IJPRES
Distributed generation (or DG) generally refers to small-scale (typically 1 kW – 50 MW) electric power generators that produce electricity at a site close to customers or that are tied to an electric distribution system [12]. Distributed generators include, but are not limited to synchronous generators, induction generators, reciprocating engines,
microturbines
(combustion turbines that run on high-energy fossil fuels such as oil, propane, natural gas, gasoline or diesel), combustion gas turbines, fuel cells, solar photovoltaic, and wind turbines. There are many reasons a customer may choose to install a distributed generator. DG can be used to generate a customer’s entire electricity supply; for peak shaving (generating a portion of a customer’s electricity onsite to reduce the amount of electricity purchased during peak price periods); for standby or emergency generation (as a backup to Wires Owner's power supply); as a green power source (using renewable technology); or for increased reliability. In some remote locations, DG can be less costly as it eliminates the need for expensive construction of distribution and/or transmission lines. Islanding: Islanding occurs when a DG system is still generating power to the distribution system when the main breaker from the Wires Owner is open. In this case, the DG system would be the sole supplier of electricity to the distribution system. This is a concern for several reasons. i. Safety concern for system maintenance if the Wires Owner's line workers are not aware that the DG system is still running, they may be electrocuted working on the line or other equipment connected to the line.
220
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
ii. Equipment damage to other Wires Owners
after the islanding has been detected by the DG and
customers. If the DG is still generating while the
DG will be transferred to islanded mode from grid-
main breaker from the wire owner is open, the
tied mode. The DG will be resynchronized with the
voltage and the waveform from the DG may fluctuate
utility only after when the utility is restored and the
and may not meet the acceptable standard. Existing
switch
customers who are connected to the distribution line
the grid.
will be turned ON to connect the DG with
are then fed by very poor quality of power from the DG. As a result, their light fixtures, motors and other electric equipment may be damaged or its life may be shortened. If the situation persists unnoticed for an unacceptably long time, a fire hazard may exist. iii. Damage to the DG owner's generator if the DG is still generating while the main breaker from the wires owner is open, the DG equipment may be damaged when the wires owner’s main breaker is closed due to closing out of synchronism.
Fig. 2. Overall block diagram of the proposed unified control strategy.
SYSTEM PROPOSED CONTROL
B. Basic Idea with the proposed control modes (hybrid voltage and
STRATEGY
current mode) the inverter is controlled as a current
A. Power Stage: To operate in both grid-tied and islanded modes this
source to generate reference power +
+
in
paper proposes unified control strategy for three-
grid-tied mode, output power
phase inverter in DG. The DG is equipped with a
the power injected into the grid
three-phase interface inverter with a LC filter. The
demand can be expressed as follows by assuming the
energy from prime mover is converted in electrical
load is represented as a parallel RLC circuit:
energy and then into DC by front end power
=
converter, the DC voltage is regulated represented by
=
connected in the ac side of the inverter. The two and
and the utility
will control the utility protection switch
. Under
and load
3 ∙ 2
3 ∙ 2
∙
1
functions are different. DG will
control the inverter transfer switch
+
------- (1)
as shown in figure. Local grids are directly
switches
should be
− --------- (2)
Where frequency
the amplitude of load voltage and f is is the of
load
voltage.
Considering
the
normal operation, the DG in the grid-tied mode
fundamental component still equivalent to the
injects power to the utility and both
parallel RLC circuit when the nonlinear local load is
and
switches are ON. When the utility is in fault, the
fed. The load voltage will neither be fixed by the
utility instantly trips the switch
and then the
utility nor regulated by the inverter during the time
Switch will be disconnected
interval the moment of switching the control to the
islanding is formed.
IJPRES
221
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
instant of islanding mode. The load voltage may drift
reference generation module. In order to mitigate the
from the normal range.
couplings due to the inductor, is implemented by the
The inverter will still controlled as current source
PI compensator in both D- and Q-axes and /
and kept it output power almost unchanged during
decoupling
this time interval. The power injected to utility
Decoupling capacitor 1/
decreases to zero rapidly, and then the power
current loop
consumed by the load will be imposed to the output
space vector modulation (SVM) that control the
power of DG. If considered both active power and
switches of the three-phase inverter. Where
reactive power injected into the grid is positive in the
denotes the voltage gain of the inverter which equals
grid-tied mode, then
to half of the dc voltage in this paper.
and
will increase the
of
the
cross
coupling
.
and output of inner
sets the reference for the standard
after the islanding mode. The amplitude and
The widely used SRF PLL in three-phase power
frequency of the load voltage will rise and drop
converter to estimate the utility frequency and phase
according to equations (1) and (2).
is also proposed in the control strategy [15], in order
Comparing to the traditional analysis, the output +
power of inverter
can be regulated to
to hold the frequency of the load within the normal range in the islanded operation a limiter is inserted
match the load demand by changing the current
between the PI compensator
reference before islanding is confirmed. The load
From figure it can be concluded that the inductor
voltages excursions will be mitigated which is
current is regulated to follow the current reference
implemented in this paper. By regulating the three-
and the current phase is synchronized to the
phase inductor current
only the output power of
grid voltage
and integrator.
.
the inverter is controlled in the proposed control strategy, while the magnitude and frequency of the load voltage
are monitored. While islanding is
about to operate, the magnitude and frequency of the load voltage may drift from normal range and then they are controlled automatically and recovered to normal range by regulating the output power of the inverter.
Figure 2 shows the proposed unified overall control
Fig 3 Block diagram of the current reference generation module. If current reference is constant, the inverter is just
block diagram. The sensed values from the block
controlled to be a current source, which is same with
diagram are the utility voltage
, the inductor
the traditional grid-tied inverter. The new thing in
. The three-
this paper is the current reference to guarantee the
phase variables of the three-phase inverter will be
power match between the DG and local load and
represented in dc quantity is controlled in the SRF.
enables to operate in islanded mode. In this module
The main modes of the control diagram are the
even unified load current feedforward to cope with
inductor current loop, the PLL, and the current
nonlinear local load is implemented. Figure 3
C. proposed Control strategy:
current
and the load current
IJPRES 222
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
provides the current reference for the inner current
In [18] the inductor current control shown in Fig 2
loop in both grid-tied and islanding modes. An
was proposed for grid-tied operation of DG. Inspired
unsymmetrical structure is used in D- and Q-axis
from [18] this paper proposes a unified control
where PI compensator in D-axis with an extra limiter
strategy for DG in both grid-tied and islanded modes
and P is employed in Q-axis. Load current
can
is
be represented by the current reference
being added to the final inductor current reference
generation module in figure 3.This module can be
by the load current feedforward. The benefits
summarized in two aspects for this contribution.
from figure 3 are represented by two parts: 1) without
First, PI compensator in D and P compensator Q-axis
critical
transfer
respectively, upon occurrence of islanding voltage
capability; and 2) in both grid-tied and islanded
controller is activated automatically and maintained
operations improving the power quality. In D and Q-
inactive during grid-tied mode. There is no need for
axes the current reference
switching different controllers and load voltage
islanding
detection
seamless
composes of four
parts namely: 1) controller output voltages the reference grid current
; 2)
; 3) the load current
and 4) the current through filter capacitor
.In
quality during transition from grid-tied mode to the islanded
mode
can
be
improved.
Another
contribution of this module is to provide load current feedforward to deal with the issue caused by the
grid-tied mode, the load voltage
is decided by
the utility. The load voltage and current reference are irrelevant due to saturation of PI compensator in Daxis and the output of P compensator being zero in Q-axis. Thus,
the inverter operates as a current
source. Voltage controller takes automatically to control the load voltage by regulating current reference when islanding occurs and makes the inverter to operate as a voltage source to provide
nonlinear local load, by which load voltage quality in islanded mode is enhanced and the grid current waveform in grid-tied can also improved. It should be noted that the unbalance three-phase local load currents cannot be fed by the DG with the proposed control strategy, because there is no flow path for the zero sequence current of unbalanced load, and the regulation of zero sequence current is beyond the scope of the proposed control strategy.
stable voltage to the local loads. The advantage of this control scheme is that it relieves from different control architecture. The other distinguished function of the current generation module is the load current feedforward. In order to compensate the harmonic component the sensed load current is added as a part of the inductor reference current
in the grid current under the nonlinear
local load. But in the islanded mode still the load current feedforward operates and the disturbance caused by the nonlinear load can be suppressed by
FUZZY LOGIC CONTROLLER The error value of the dc-bus voltage Δvdc= v∗dc−vdc is passed through a Fuzzy-type compensator to regulate the voltage of dc bus (vdc) at a fixed value. The operation of FLC is as follows. FLC contains three basic parts: Fuzzification, Base rule, and Defuzzification. FLC has two inputs which are: error and the change in error, and one output. The Fuzzy Controller structure is represented in fig.6. The role of each block is the following:
the fast inner inductor current loop and finally the quality of the load voltage is improved.
IJPRES 223
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
Fig 4. Membership function of voltage error
Fig 2: The general structure of Fuzzy Logic Controller
Fuzzifier converts a numerical variable into a linguistic label.. In a closed loop control system, the
Fig 5. Membership function of output field voltage
error (e) between the reference voltage and the output voltage and the rate of change of error (del e) can be labeled as zero (ZE), positive small (PS), negative small (NS), etc. In the real world, measured quantities are real numbers (crisp). The FLC takes two inputs, i.e., the error and the rate of change of
Rule base stores the data that defines the input and the output fuzzy sets, as well as the fuzzy rules that describe the control strategy. Mamdani method is used in this paper. Seven membership functions were used leading to 49 rules in the rule base.
error. Based on these inputs, The FLC takes an intelligent decision on the amount of field voltage to
Table 1
be applied which is taken as the output and applied
Rule base for fuzzy controller
directly to the field winding of generator. Triangular membership functions were used for the controller.
Fig 3. Membership function of voltage
Inference engine applies the fuzzy rules to the input fuzzy variables to obtain the output values. Defuzzifier achieves output signals based on the output fuzzy sets obtained as the result of fuzzy reasoning. Centroid defuzzifier is used here.
IJPRES 224
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
----------- (5)
PARAMETER DESIGN AND SMALL Where
SIGNAL ANALYSIS OF THE
= magnitude of the grid voltage, ∗
= the actual phase angle.
PROPOSED CONTROL SYSTEM
is regulated to zero by the PLL, so magnitude of the utility voltage The fuzzy based proposed unified control strategy with operating principle of DG is illustrated in detail in this section. The four states of DG are as follows:1) grid-tied mode, 2) transition from the gridtied mode to islanded mode, 3) the islanded mode, 4)
equals the
. As the filter
capacitor voltage equals the utility voltage in the gird-tied mode, utility voltage
equals the magnitude of the , and
equals zero. In the D-axis,
the inductor current reference
can be expressed
by (6) according to Fig. 3
from islanded mode to the grid-tied mode.
=
i. Grid-Tied mode: under normal case of utility, by
+
−
∙ ------- (6)
inductor current loop the DG is controlled as current source and will supply active and reactive power
In steady state, the given voltage reference
through current D- and Q- axis independently. For
larger than the magnitude of the utility voltage
that utility voltage phase angle is obtained through
and the first part is the output of the limiter. So the PI
PLL by park transformation, PI controller, a limiter
compensator, denoted by GVD in the following part
and an integrator.
will saturate and the limiter outputs its upper
2 = 3
cos
cos
− sin
− sin
2 3 2 − 3
+
− cos − sin
value
2 3 2 + 3 +
×
An inductor current reference
seems little
complex and compared with the instantaneous filter inductor current which is transformed into SRF by the park transformation. The inductor current is regulated to track the reference compensator
= cos
∗
cos
cos( ∗
∗
−
−
2 3
∗
− ) ∗ − )
the
·
,
is the
capacitance of the filter capacitor. It is fixed as depends on the utility voltage. The given reference and the load current the current reference
=
is being imposed by and independent of the
consists of four parts as ∙
+
+
+
∙ ------ (7)
Where
The SRF transformation of the utility voltage is cos( sin(
that
is the rated angle frequency, and
reference
------- (4)
= =
is
load current.
where
2 ) 3
expressed as
part
load voltage. In the Q-axis, the inductor current
three-phase utility voltages are expressed as =
second
The third is the proportional part −
by the PI
. The utility is assumed stiff, the
The
characteristics of local load will determine Daxis
-------- (3)
.
is
denoted by the output of
= parameter of the P compensator, in the following part. The first part is , which is zero as the
has been
regulated to zero by the PLL. The second part is the given current reference
, and the third part
represents the load current in Q-axis. The final part
IJPRES 225
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
is the proportional part− since
·
Volume V /Issue 4 /SEP 2015
, which is fixed
inverter switch
. As switch
is in ON state, in first
interval the utility voltage
depends on the utility voltage.
voltage
will be same as load
because dynamic of the inductor
current loop and the voltage loop is much faster than the PLL [15] but load voltage and current are varying dramatically
considering
load
voltage
angle
frequency to be not varied. In the grid-tied mode, it is assumed that the DG injects active and reactive power into the utility, which can be expressed by (8) and (9), and that the local critical load, shown in (10), represented by a series connected RLC circuit with the lagging power factor Fig. 4. Simplified block diagram of the unified control strategy when DG operates in the grid-tied mode Therefore, external voltage drop will not influence the current reference
.but, the current reference
will determine the given reference the load current
and
Fig. 5. Operation sequence during the transition from the grid-tied mode to the islanded mode.
.the control diagram of the
inverter is simplified n grid-tied mode, with the analysis of previous cases and the inverter is controlled as a current source with inductor current reference
and
the
load
Fig. 6. Transient process of the voltage and current
current
determined by the inductor current loop will track the current
reference
and
the
load
when the islanding happens.
current.
represents the grid currents if steady state
=
3 ∙ 2
+
=
3 2
error is zero will be explained in next section.
------- (8)
ii. Transition mode from grid –tied mode to the islanded mode: By opening utility switch
, the
=
3 ∙ 2
+
=
3 2 --------- (9)
islanding mode begins; frequency and load voltage will drift because of active and reactive power
=
+
−
mismatch between DG and the load demand. The transition is divided into two time intervals where first is from the instant of turning off of turning off
to the instant
when islanding mode is confirmed.
=
+ =
−
1
1
+ ------- (10)
The second one starts from instant of turning off
IJPRES
226
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
In islanding mode,
Volume V /Issue 4 /SEP 2015
will decrease from positive to
If
is fixed, load voltage in Q-axis
will be
will increase from negative to zero.
negative. With the help of power relationship the
During this time load current will vary in the opposite
variation of frequency and amplitude can be
direction. From equations (11) and (12) it can be
understandable. When the islanding happens, the
concluded that D- and Q-axes load voltage each
local load must absorb the extra power injected to the
consists of two terms. The load voltage in D-axis
grid, as the output power of inverter is not changed
will increase as both terms increase. But in Q-axis
instantaneously. From (1) the magnitude of load
zero, and
is uncertain because the first term decreases and
voltage
will rise with the increase of
. In
the second term increases, and it is not concerned for
meanwhile the angle frequency ω should drop, in
a while
order to consume more power with (2). Results from =
∙
−
power relationship coincide with the previous
∙ ------ (11)
=
∙
−
from the instant when the switch
∙ ------ (12)
The input of PI compensator
analysis. The second time interval transition begins
will become
opens after the
islanding detection method. If switch load voltage
opens the
is independent with the grid
negative with the increase of the load voltage in D-
voltage
. In the mean time
will reduce to
axis
zero theoretically as the switch
has opened. The
, when it reaches and exceeds
so its
output will decrease. Then the output of limiter will
angle frequency is invariable and then, input of the
not imposed to
compensator
reference
any longer and the current will drop. In the regulation of the
inductor current loop, D-axis
load current will
decrease. The load voltage in D-axis and recover to
. If
will drop
has almost fallen to the
normal value, the load voltage in Q-axis
will
drop according to (12). The PI compensator
will
going to be negative if
is decreased from zero to
negative and its output will drop. The angle frequency ω will be reduced. If it falls to the lower value of the limiter at
, the angle will be fixed
. At the end of the first time interval the load
voltage in D-axis
will increase and fix at
drop.PLL can still operate normally if the value is
the load voltage in Q-axis
will be zero.
of the first time interval. The inverter is controlled to be a voltage source when
is regulated by the voltage loop. Under
islanding operation, the load voltage is restricted to particular range to drift the amplitude and frequency and the inverter is transferred from the current source operation mode to the voltage source operation mode autonomously. With the increase in the time of delay, the drift becomes worse in the hybrid voltage and current mode control. So, the time delay of islanding detection is critical to drift of the frequency and magnitude in the load voltage. In proposed control strategy this phenomenon is avoided.
and angle frequency of the load voltage ω will also
higher than the lower value of the limiter
becomes zero and fixed to the end
, and
iii. Islanded Mode: in this state switching
and
both in OFF state. The PLL cannot track the utility voltage normally, and angle frequency is fixed. Since voltage compensator load voltage
and
can regulate the
, the DG is controlled as a voltage
IJPRES 227
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
source. In D-axis the voltage reference is
Volume V /Issue 4 /SEP 2015
and in
b. The magnitude of the load voltage
is larger
Q-axis voltage reference is zero respectively and the
than the utility voltage magnitude
, the reference
magnitude of the load voltage equals to
voltage
by toggling the
approximately, elaborated in next section. The
selector S from terminals 1 to 2. The load voltage
control diagram of three-phase inverter for islanded
will equal t the utility voltage in both phase and
mode can be simplified and is shown in figure 7. If
magnitude.
there is any disturbance in the load current, it will be
c. The switch
suppressed quickly by the inductor current loop and a
reset to terminal 1 where load voltage is held by
stiff load voltage can be achieved. Finally, the load
utility. As
current
magnitude
is partial reference of the inductor
current loop.
Tied Mode:
is turned on, and the selector S is =
of
compensator
iv. Transition from the Islanded Mode to the Grid-
which is larger than the
the
utility
voltage
,
so
PI
will saturate, and the output of
limiter is its upper value
meanwhile
is
regulated to zero by the PLL from equation 5. The
a. If the utility switch
made ON after the restoring
output of
the utility, the DG should be connected with utility by turning ON switch
. There are several steps
before preparation before turning on switch
.as
soon as utility voltage is restored, the PLL will track the phase of the utility voltage which results that the phase angle of utility voltage grid voltage
will be changed to
will follow the
. If the load voltage
is in
phase with the utility voltage, according to equation 5 will equal the magnitude of the utility voltage.
and
will be zero. By inactivating , DG is controlled as a current source by
inductor current loop. Analysis and Design: This section briefs about the proposed fuzzy based control strategy is analyzed and designed in both steady state and transient state along with three-phase inverter. In the steady state, the operating points of both gridtied and islanded modes of DG are analyzed where limiters and references are selected. Whereas in transient state, compensators in both inductor current loop and the external loop are designed based on the small-signal model and the effect of load current feedforward is also analyzed as well. A. Steady State 1) Analysis of Operation Points: 2) Selection of References and Limiters
1) Analysis of Operation Points: in the grid-tied mode, the inverter is controlled as a current source, and the current reference for the inductor current Fig 7 Simplified block diagram of the unified control strategy when DG operates in the islanded mode.
loop
is expressed according equation (6) and
(7). The steady-state error will be zero with the Fuzzy Logic Compensator in the inductor current loop, so
IJPRES 228
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
Volume V /Issue 4 /SEP 2015
the inductor current in steady state can be expressed
compensator
as follows:
zero and = ∙
=
− +
∙
can be expressed as follows:
+
∙
=
+
+
------- (18)
------- (13)
Where
In the SRF, the relationship between the voltage and the current of the filter capacitor in steady state can be expressed by =− =
, so the steady state error will be
is
is in D-axis. In the Q-axis, the regulator compensator, so the steady state error may
not be zero. As the load current is added to the inductor reference, the condition shown as below can
∙
be achieved
∙
∙
-------- (14)
=0
represents the angle frequency of the DG
------ (19)
denotes capacitance of the filter capacitor. As a
And then, the load voltage in Q-axis can be expressed
Where and
+
result, the output current of the inverter
can be
by (20). It should be noted that the absolute value of
gained = − = = − = +( − ) ∙
−( ∙
which is related to the reactive power injected
− ) +
∙
+
rises with the increase of the current reference
into the utility . =−
------- (15)
------ (20)
As angle frequency ω is very close to the rated angle frequency
, it can be found that the output current
follows
and the load current
, as
equals
The magnitude of the load voltage represented
as
follows.
zero in the grid-tied mode. The active and reactive
approximately, because
power injected into utility can be obtained as follows.
than
It
can be
equals
to
should be much lower
with proper current reference
Consequently, the active power and reactive power =
flowing from the inverter to utility can be given by
and
⎧ ⎪ ⎪ ⎨ ⎪ ⎪ ⎩
3 = ∙ 2
≈
, respectively
------- (21) During islanding operation, the angle frequency is
(
− =
3 = ∙ 2
+
(
)+
−
restricted in the given range by the limiter. During
3 ∙ 2 −
transition from grid-tied mode to the islanded mode, In first-time interval only the angle frequency is )−
−
determined. If current reference
3 = ∙ 2
then
is set to zero,
is zero. It means that the angle frequency
----- (17)
does not vary in the first time interval of the
In the islanded mode, the inverter is controlled as a
transition, and it should equal the angle frequency of
voltage source by the external voltage loop. In the D-
the utility before islanding happens
axis,
is
regulated
by
the
Fuzzy
. the angle
Logic
IJPRES 229
INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES
frequency of the load voltage
Volume V /Issue 4 /SEP 2015
in the islanded mode
is determined by the current reference
, where
represent the upper values of the limiter and
Besides,
the
between
angle and
frequency
is
restricted
in the islanded mode, and it
should not drift from the normal value too far. So, and
represent the lower values of the limiter shown
are selected as the maximum and
minimum angle frequencies allowed by the utility
in fig 2 ,
>0 =0