Appendix G Module Status

Appendix G – Module Status GENERAL DESCRIPTION Appendix G contains module status information by module type. Table G-1 explains analog master module s...
2 downloads 3 Views 222KB Size
Appendix G – Module Status GENERAL DESCRIPTION Appendix G contains module status information by module type. Table G-1 explains analog master module status. • •

IMAMM03. NAMM02/02A.

Table G-2 explains bus module status. • • •

INBIM02 (bus interface). INBTM01 (bus transfer). NBIM01 (bus interface).

Table G-3 explains network processing and Superloop status. • •

INNPM01 (Controlway – network processing). NSBM01 (Superloop).

Table G-4 explains Plant Loop to Plant Loop communications status. • • •

INPPT01 (transfer module). NGCM01/02 (transfer module). NPPG01 (gateway).

Table G-5 explains miscellaneous communications status. • • • • •

CIC01 (computer interface command). INPCI01/02 (Plant Loop to computer interface). INPCT01 (Plant Loop to computer transfer module). INPTM01 (point table module). NLSM01 (loop storage module).

Table G-6 explains INFI-NET to computer communications status. • • •

INICI01 (INFI-NET to computer interface). INICT01/03 (INFI-NET to computer transfer module). INSEM01 (sequence of events).

Table G-7 explains controller module status. • • • • •

I-E96-200B

CLC01/02/03/04 (loop command). IMCOM03/04. IMQRC01 (quick response). NCOM02/02A/03A/04A. NLCM01/02/03 (large).

Module Status 15 FEB 1995 G-1

Appendix G

®

Tables G-8 and G-9 explain logic master module status. • •

IMLMM02. NLMM01/NLMM01A.

Table G-10 explains multi-function, multi-processor, strategic loop and command controller status. • • • • • •

CBC01 (batch command). CSC01 (sequence command). IMMFC03/04/05 (multi-function). IMMPC01 (multi-processing). NMFC01/02 (multi-function). SLC01/21 (strategic loop).

Table G-11 explains multi-function processor module status. •

IMMFP01/02/03/03B.

Table G-12 explains local transfer module status. • •

INIIT01/03 (INFI-NET to INFI-NET local transfer module). INIPT01 (INFI-NET to Plant Loop local transfer module).

Table G-13 explains remote transfer module status. • •

INIIT02 (INFI-NET to INFI-NET remote transfer module). INIPT02 (INFI-NET to Plant Loop remote transfer module).

Table G-14 explains process interface module status. •

NPIM01 (process interface module).

Table G-13 explains communication processor module status. •

IMCPM02/03 (configuration port module).

Table G-16 explains configuration and tuning, and analog output module status. • • •

Module Status 15 FEB 1995 G-2

CTT01/02 (configuration and tuning terminals). IMAOM01 (analog output module). NCTM01 (configuration and tuning module).

I-E96-200B

Appendix G

ANALOG MASTER MODULES Table G-1. IMAMM03 and NAMM02/02A Analog Master Modules Byte 1

Bit 7

6

ES

5

FTX

BAC

3

REF

IOP

SCF

4

FCG

FCL

ICG

5

1

2

3

4

5

I-E96-200B

3

2

1

0

TYPE

2

Byte

4

MODE LIO CAL

NVF

NVI

CJR

SRV

ICL

EPF

ECS BLK

Field

Field Size or Value

Description

ES

80

Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code = (9)16

FTX

80

First time in execute: 0 = no, 1 = yes

BAC

40

Backup status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad (I/O module not responding or bad quality input)

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

REF

80

Master reference out of range: 0 = no, 1 = yes

IOP

40

Summary open thermocouple status: 0 = good, 1 = bad (configured thermocouple point is open)

SCF

20

I/O module configuration problem: 0 = no, 1 = yes (problem with I/O module definition block - occurs when going from configure to execute mode)

CAL

08

Summary calibration status: 0 = good, 1 = bad

CJR

04

Summary cold junction RTD status: 0 = good, 1 = bad

SRV

02

Summary of points not in service: 0 = no, 1 = yes (point is out of service for calibration)

EPF

01

NVRAM power failure during write: 0 = no, 1 = yes

FCG

80

Failed configuration NVRAM: 0 = no, 1 = yes (NAMM02 only)

FCL

40

Failed calibration NVRAM: 0 = no, 1 = yes (NAMM02 only)

ICG

20

Configuration NVRAM initialized: 0 = no, 1 = yes (NAMM02 only)

ICL

10

Calibration NVRAM initialized: 0 = no, 1 = yes (NAMM02 only)

ECS

0F

Error code status: 0 = good, not 0 = error code 1 = I/O module type and point type disagree (BLK) 2 = input type disagrees with engineering unit type (BLK) 3 = point input type invalid (BLK) 4 = trend type invalid (BLK) 5 = cold junction input invalid (BLK) (IMAMM03 only) 6 = polynomial block address is invalid (BLK) (IMAMM03 only) 7 = DIS block data invalid (BLK) (IMAMM03 only)

BLK

FF

Block number referring to the error code status (ECS)

Module Status 15 FEB 1995 G-3

Appendix G

®

PLANT BUS LOOP MODULES Table G-2. INBIM02 and NBIM01 Bus Interface Modules (Module Bus), and INBTM01 Bus Transfer Module (Module Bus) Byte

Bit 7

6

5

4

3

1

ES

2

LIN

MODE

3

CSP

MOV

NSF

RLB

SBF

4

LIM

LR1

LR2

LT1

LT2

2

1

0

TYPE

5

PSI

Reserved

Byte

Field

Field Size or Value

1

ES

80

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code: (8)16 = NBIM01 and INBIM02, (E)16 = INBTM01

2

LIN

80

LIM/BTM on-line/off-line: 0 = on-line, 1 = off-line (INBTM01 only)

3

CSP

80

Communication status problem: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = good, 1 = bad

NSF

20

Node status flag: 0 = good, 1 = bad

RLB

10

Redundant LIM/BIM configured: 0 = no, 1 = yes (NBIM01 and INBIM02 only)

SBF

08

Secondary BIM failure flag: 0 = good, 1 = fail (NBIM01 and INBIM02 only)

PSI

01

Primary/secondary indicator: 0 = primary, 1 = secondary (NBIM01 and INBIM02 only)

4

5

LIM

80

LIM problem flag: 0 = no, 1 = yes

LR1

40

Plant Loop 1 receive error: 0 = no, 1 = yes

LR2

20

Plant Loop 2 receive error; 0 = no, 1 = yes

LT1

10

Plant Loop 1 transmit error: 0 = no, 1 = yes

LT2

08

Plant Loop 2 transmit error: 0 = no, 1 = yes



00

Reserved

Module Status 15 FEB 1995 G-4

I-E96-200B

Appendix G

INFI-NET NETWORK PROCESSING AND SUPERLOOP BUS MODULES Table G-3. INNPM01 Network Processing Module (Controlway) and NSBM01 Superloop Bus Module (Module Bus) Byte 1

Bit 7

6

ES

5

1

PCU

MOV

4

NSF

RER1

RER2

BKCFG

BKSTS

TER1

TER2

PSI RID1

RID2

ETYPE CWA

CWB

Reserved

8

Reserved NDT1

NDT2

NCD1

10 - 13

Reserved

14

Module nomenclature

15

Revision letter (ASCII)

16

Revision number (ASCII)

Byte

Field

Field Size or Value

1

ES

80

NCD2

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 11 = execute

TYPE

1F

Module type code: (15)16 = enhanced status

2





Reserved

3

PCU

80

Node off-line: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = good, 1 = bad

BKCFG

10

Redundant module configured: 0 = no, 1 = yes

BKSTS

08

Secondary module failure: 0 = good, 1 = bad

PSI

01

Primary/secondary indicator: 0 = primary, 1 = secondary

NSF

80

Node environment status flag: 0 = good, 1 = bad

RER1

40

Receive errors on channel 1: 0 = no, 1 = yes

RER2

20

Receive errors on channel 2: 0 = no, 1 = yes

TER1

10

Transmit errors on channel 1: 0 = no, 1 = yes

TER2

08

Transmit errors on channel 2: 0 = no, 1 = yes

RID1

04

Receiver idle on channel 1: 0 = no, 1 = yes

RID2

02

Receiver idle on channel 2: 0 = no, 1 = yes

RCF

01

Ring communication failure for local ring: 0 = no, 1 = yes

5





Reserved

6

ETYPE

FF

Enhanced module type: (25)16 = INNPM01, (21)16 = NSBM01

7

CWA

80

Controlway bus A failure: 0 = good, 1 = fail (INNPM01 only)

CWB

40

Controlway bus B failure: 0 = good, 1 = fail (INNPM01 only)



00

Reserved

8

RCF

Reserved

6

4

0

TYPE

5

I-E96-200B

2

Reserved

3

9

3

MODE

2

7

4

Module Status 15 FEB 1995 G-5

Appendix G

®

Table G-3. INNPM01 Network Processing Module (Controlway) and NSBM01 Superloop Bus Module (Module Bus) (continued) Byte

Field

Field Size or Value

9

NDT1

01

NIS loop relay drive transistor 1 failure

Description

NDT2

01

NIS loop relay drive transistor 2 failure

NCD1

01

NIS receive channel 1 disable

NCD2

01

NIS receive channel 2 disable

10 - 13





Reserved

14



FF

Module nomenclature: (01)16 = INNPM01 and NSBM01

15



FF

Revision letter (in ASCII code), for example, (44)16 = D

16



FF

Revision number (in ASCII code), for example, (31)16 = 1

Module Status 15 FEB 1995 G-6

I-E96-200B

Appendix G

PLANT LOOP TO PLANT LOOP COMMUNICATIONS Table G-4. INPPT01 Transfer Module, NGCM01/02 Plant Loop to Plant Loop Transfer Module, and NPPGO1 Plant Loop to Plant Loop Gateway Byte

Bit 7

6

5

4

1

ES

2

FTX

BAC

MODE RIO

LIO

3

PCU

MEM

NEF

SL1

SL2

4

LIM

LR1

LR2

LT1

LT2

Field

Field Size or Value

1

ES

80

3

4

5

1

0

NVI

CFG

Reserved

Byte

2

2 TYPE

5

I-E96-200B

3

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code: (11)16 = NGCM01 and INPPT01

FTX

80

First time in execute: 0 = no, 1 = yes

BAC

40

Backup status: 0 = good, 1 = bad

RIO

20

Summary remote I/O status: 0 = good, 1 = bad

LIO

10

Summary local I/O status: 0 = good, 1 = bad

NVI

04

NVRAM checksum error: 0 = good, 1 = bad

CFG

02

Default configuration: 0 = no, 1 = yes

PCU

80

One or more PCUs off-line: 0 = no, 1 = yes

MEM

40

Memory overflow: 0 = good, 1 = bad

NEF

20

Node environment failure: 0 = good, 1 = bad

SL1



Serial link 1 status: 0 = good, 1 = bad

SL2



Serial link 2 status: 0 = good, 1 = bad

LIM

80

LIM problem flag: 0 = no, 1 = yes

LR1

40

Loop receive error channel 1: 0 = no, 1 = yes

LR2

20

Loop receive error channel 0: 0 = no, 1 = yes

LT1

10

Loop transmit error channel 1: 0 = no, 1 = yes

LT2

08

Loop transmit error channel 0: 0 = no, 1 = yes



00

Reserved

Module Status 15 FEB 1995 G-7

Appendix G

®

PLANT LOOP TO COMPUTER COMMUNICATIONS - COMPUTER INTERFACE COMMAND Table G-5. CIC01 Computer Interface Command, INPCI01/02 Plant Loop to Computer Interface, INPCT01 Plant Loop to Computer Transfer Module, INPTM01 Point Table Module, and NLSM01 Loop Storage Module Byte

Bit 7

6

5

4

RIO

LIO

1

ES

2

FTX

3

CSP

MOV

NSF

4

LIM

LR1

LR2

MODE

Field

Field Size or Value

1

ES

80

4

5

1

0

NODE TYPE LT1

LT2 HOST

Byte

3

2 TYPE

5

2

3

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode:

TYPE

1F

Module type code: (0A)16 = INPTM01, INPCI01 (10)16 = NLSM01, INPCT01, INPCI02 (17)16 = CIC01

00 = configure, 10 = error, 11 = execute

FTX

80

First time in execute: 0 = no, 1 = yes

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

CSP

80

Communication status problem: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = good, 1 = bad

NSF

20

Node status flag: 0 = good, 1 = bad

NODE TYPE

07

Node type: 0 = computer interface unit, 1 = operator interface station or management command system, 2 = operator interface unit

LIM

80

LIM problem flag: 0 = no, 1 = yes

LR1

40

Plant Loop 1 receive error: 0 = no, 1 = yes

LR2

20

Plant Loop 2 receive error: 0 = no, 1 = yes

LT1

10

Plant Loop 1 transmit error: 0 = no, 1 = yes

LT2

08

Plant Loop 2 transmit error: 0 = no, 1 = yes

HOST

FF

Value set by the computer (when non-zero, ES = 1)

Module Status 15 FEB 1995 G-8

I-E96-200B

Appendix G

INFI-NET TO COMPUTER COMMUNICATIONS AND SEQUENCE OF EVENTS MONITOR Table G-6. INICI01 INFI-NET to Computer Interface, INICT01/03 INFI-NET to Computer Transfer Module (Local), and INSEM01 Sequence of Events Monitor Byte

Bit 7

6

1

ES

2

FTX

3

CSP

MOV

4

NSF

LR1

5

4

3

RIO

LIO

CFM

LOP

SDF

MODE

LR2

LT1 ETYPE

Reserved NDT2

NCD1 Reserved

14

Module nomenclature

15

Revision letter (ASCII)

16

Revision number (ASCII)

3

4

I-E96-200B

NDT1

10 - 13

2

ERM NODE TYPE

LT2

6

1

0

RI1

RI2

RCF

HOST

7-8

Byte

1

TYPE

5

9

2

Field

Field Size or Value

NCD2

Description

ES

80

Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 01 = fail, 10 = error, 11 = execute

TYPE

1F

Module type code: (15)16 = enhanced status

FTX

80

First time in execute: 0 = no, 1 = yes

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

CFM

08

Module in configure mode (MODE = 00): 0 = no, 1 = yes

ERM

01

Module in error mode (MODE = 10): 0 = no, 1 = yes

CSP

80

Communication status problem: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = good, 1 = bad

LOP

10

Off-line bridge for remote loop: 0 = no, 1 = yes

SDF

01

Security device failure

NODE TYPE

07

Node type: 0 = computer interface, 1 = operator interface unit or management command system, 2 = operator interface unit

NSF

80

Node environment status flag: 0 = good, 1 = bad

LR1

40

INFI-NET 1 receive error: 0 = no, 1 = yes

LR2

20

INFI-NET 2 receive error: 0 = no, 1 = yes

LT1

10

INFI-NET 1 transmit error: 0 = no, 1 = yes

LT2

08

INFI-NET 2 transmit error: 0 = no, 1 = yes

RI1

04

Receiver idle on channel 1 of central loop: 0 = no, 1 = yes

RI2

02

Receiver idle on channel 2 of central loop: 0 = no, 1 = yes

RCF

01

Ring communication failure: 0 = no, 1 = yes

5

HOST

FF

Value set by the computer (when non-zero, ES = 1)

6

ETYPE

20

Enhanced module type (20)16 = INICT01/03, (2A)16 = INSEM01

7-8



00

Reserved

Module Status 15 FEB 1995 G-9

Appendix G

®

Table G-6. INICI01 INFI-NET to Computer Interface, INICT01/03 INFI-NET to Computer Transfer Module (Local), and INSEM01 Sequence of Events Monitor (continued) Byte

Field

Field Size or Value

9

NDT1

01

NIS loop relay drive transistor 1 failure

Description

NDT2

01

NIS loop relay drive transistor 2 failure

NCD1

01

NIS receive channel 1 disable

NCD2

01

NIS receive channel 2 disable

10 - 13





Reserved

14



FF

Module nomenclature (01)16 = INICT01 and INSEM01, (03)16 = INICT03

15



FF

Revision letter (in ASCII code), for example, (45)16 = E

16



FF

Revision number (in ASCII code), for example, (30)16 = 0

Module Status 15 FEB 1995 G - 10

I-E96-200B

Appendix G

CONTROLLER MODULES Table G-7. CLC01/02/03/04 Loop Command Controller Module, IMCOM03/04 and NCOM02/02A/03A/04A Controller Module, IMQRC01 Quick Response Controller Module, and NLCM01/02/03 Large Controller Module Byte

Bit 7

1

ES

2

FTX

6

4

3

2

RIO

LIO

SEG

MODE Error code

4

Error code descriptor (1)

5

Error code descriptor (2)

1

2

Field

Field Size or Value

0

NVF

NVI

DSS

Description

ES

80

MODE

60

Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code: (5)16 = COM and QRC, (6)16 = CLC, (0F)16 = NLCM01, (1E)16 = NLCM02, (1F)16 = NLCM03

FTX

80

First time in execute: 0 = no, 1 = yes

Error summary: 0 = good, 1 = errors

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

SEG

08

Summary segment alarm status: 0 = no, 1 = yes

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

DSS 3-5

1

TYPE

3

Byte

I-E96-200B

5

Error Code

01

Digital station status: 0 = good, 1 = bad

3

4

5

01

01 02 03 FF

— — — —

NVRAM error: Write failure Checksum failure Bad data Reset during write

02

00

04 05

AI reference error: 1-V reference 5-V reference

03

00



Missing I/O expansion board

05

(1)

(2)

Configuration error – undefined block: (1) = block number making reference (2) = block number being referenced

06

(1)

(2)

Configuration error – input data type is incorrect: (1) = block number making reference (2) = block number being referenced

08

(1)



Trip block activated: (1) = block number of trip block

09

(1)

(2)

Function not allowed in segment: (1) = segment block number (2) = block number in error

0A





Too many segment control blocks

0B

(1)

(2)

Segment control block priority violation: (1) = block number of first segment (2) = block number of segment in error

Module Status 15 FEB 1995 G - 11

Appendix G

®

LOGIC MASTER MODULES Table G-8. NLMM01 Logic Master Module Byte

Bit 7

1

ES

2

FTX

6

5

4

3

RIO

LIO

2

MODE MOV

NVF

Error code

4

Error code descriptor (1)

5

Error code descriptor (2)

1

2

3-5

Field

Field Size or Value

0

NVI

DSS

TYPE

3

Byte

1

Description

ES

80

MODE

60

Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code = (7)16

FTX

80

First time in execute: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = no, 1 = yes

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

DSS

01

Digital station status: 0 = good, 1 = bad

Error Code

3

4

5 NVRAM error: Write failure Checksum failure Bad data Reset during write

01 01 02 03 FF

— — — —

03

(1)



Missing I/O module block or module number of I/O module or DLS: (1) = group number

05

(1)

(2)

Configuration error – undefined block: (1) = block number making reference (2) = block number being referenced

07

(1)



Insufficient memory in remote memory: (1) = block number of digital input list (function code 46)

08

(1)



Trip block activated: (1) = block number of trip block

Module Status 15 FEB 1995 G - 12

I-E96-200B

Appendix G

Table G-9. IMLMM02 or NLMM01A Logic Master Module Byte

Bit 7

1

ES

2

FTX

6

5

4

3

RIO

LIO

2

MODE MOV

NVF

Error code

4

Error code descriptor (1)

5

Error code descriptor (2)

1

2

3-5

Field

Field Size or Value

0

NVI

DLS

TYPE

3

Byte

1

Description

ES

80

MODE

60

Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code = (C)16 First time in execute: 0 = no, 1 = yes

FTX

80

MOV

40

Memory overflow: 0 = no, 1 = yes

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

DLS

01

Digital logic station status: 0 = good, 1 = bad

Error Code

3

4

5 NVRAM error: Write failure Checksum failure Bad data Reset during write

01 01 02 03 FF

— — — —

03

(1)

(2)

Missing I/O module block or module number of I/O module or DLS: (1), (2) = I/O module address

05

(1)

(2)

Configuration error – undefined block: (1), (2) = block number making reference

06

(1)

(2)

Configuration error – input data type is incorrect: (1), (2) = block number making reference

07

(1)

(2)

Insufficient memory in remote memory: (1), (2) = block number of digital input list (function code 46)

08

(1)

(2)

Trip block activated: (1) = block number of trip block



Too many segment control blocks



Configuration error, sequencing too complex

0A 0C



NOTE: All numbers in bytes 4 and 5 are in binary coded decimal (BCD) format.

I-E96-200B

Module Status 15 FEB 1995 G - 13

Appendix G

®

MULTI-FUNCTION, MULTI-PROCESSOR, STRATEGIC LOOP AND COMMAND CONTROLLERS Table G-10. CBC01 Batch Command Controller, CSC01 Sequence Command Controller, IMMFC03/04/05 and NMFC01/02 Multi-Function Controller Module, IMMPC01 MultiProcessing Controller Module, and SLC01/21 Strategic Loop Controller Byte

Bit 7

1

ES

2

FTX

6

5

4

3

2

RIO

LIO

CFG

MODE BAC

Error code

4

Error code descriptor (1)

5

Error code descriptor (2)

1

2

3-5 Byte 3 is displayed on the front panel LEDs when the module is in ERROR mode. Under MONITOR/ STATUS screen for SLC.

Field

Field Size or Value

0

NVI

DSS

TYPE

3

Byte

1

NVF

Description

ES

80

MODE

60

Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code: (B)16 = NMFC01/02 and IMMFC03/04/05, (D)16 = IMMPC01, (13)16 = CBC01, (14)16 = CSC01, (19)16 = SLC01/21

FTX

80

First time in execute: 0 = no, 1 = yes

BAC

40

Backup status: 0 = good, 1 = bad

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

CFG

08

On-line configuration changes being made

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

DSS

01

Digital station status: 0 = good, 1 = bad

Error Code

3

4

5

01

01 02 03 FF

— — — —

02

(1)

(2)

Analog input reference error: (1), (2) = block number of control interface I/O module block

03

(1)

(2)

Missing I/O module or expander board: (1), (2) = block number of I/O module or station

05

(1)

(2)

Configuration error – undefined block: (1), (2) = block number making reference

06

(1)

(2)

Configuration error – input data type is incorrect: (1), (2) = block number making reference

08

(1)

(2)

Trip block activated: (1), (2) = block number of trip block

0F





Primary module has failed and the redundant module configuration is not current

10





Primary module has failed and the dynamic RAM data in the redundant module is not current

14





Module is set for INFI-NET but is in a Plant Loop environment

Module Status 15 FEB 1995 G - 14

NVRAM error: Write failure Checksum failure Bad data Reset during write

I-E96-200B

Appendix G

Table G-10. CBC01 Batch Command Controller, CSC01 Sequence Command Controller, IMMFC03/04/05 and NMFC01/02 Multi-Function Controller Module, IMMPC01 MultiProcessing Controller Module, and SLC01/21 Strategic Loop Controller (continued)

I-E96-200B

Byte

Field

3-5 (cont)

Error Code

Field Size or Value

Description

3

4

5

20





Program format error - inconsistent format table (IMMFC03 only)

21

(1)

(2)

File system error (IMMFC03 only) (1), (2) = file number

22

(1)

(2)

Invoke C error (IMMFC03 only) (1), (2) = block number making reference

24

(1)

(2)

C program stack overflow (IMMFC03 only) (1), (2) = block number making reference

28

(1)

(2)

User defined function (UDF) reference is invalid (IMMFC03/04 only) (1), (2) = block number making reference

29

(1)

(2)

UDF block cannot read program file (IMMFC03/04 only) (1), (2) = block number making reference

2A

(1)

(2)

Not enough memory for UDF (IMMFC03/04 only) (1), (2) = block number making reference

2B

(1)

(2)

Missing UDF declaration (IMMFC03/04 only) (1), (2) = block number making reference

2C

(1)

(2)

Wrong UDF type (IMMFC03/04 only) (1), (2) = block number making reference

2D

(1)

(2)

Missing UDF auxiliary block (IMMFC03/04 only) (1), (2) = block number making reference

2E

(1)

(2)

UDF compiler and firmware are incompatible (IMMFC03/04 only) (1), (2) = block number making reference

2F

(1)

(2)

BASIC program error (IMMFC03 and NMFC02 only) (1), (2) = line number of error

Module Status 15 FEB 1995 G - 15

Appendix G

®

MULTI-FUNCTION PROCESSOR MODULES Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules Byte

Bit 7

1

ES

2

FTX

6

5

4

3

2

RIO

LIO

CFG

MODE BAC

Error code

4

Error code descriptor (1)

5

Error code descriptor (2)

6 CWA

8

SIM

CWB

R1F

R2F

NVI

DSS

PF

Reserved

Reserved

9 - 13

Reserved

14

Module nomenclature

15

Revision letter (ASCII)

16

Revision number (ASCII)

Byte

Field

Field Size or Value

1

ES

80

Byte 3 is displayed on the front panel LEDs when the module is in ERROR mode.

NVF

ETYPE

7

3-5

0

TYPE

3

2

1

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 10 = error, 11 = execute

TYPE

1F

Module type code: (15)16 = Enhanced status

FTX

80

First time in execute: 0 = no, 1 = yes

BAC

40

Backup status: 0 = good, 1 = bad

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad

CFG

08

On-line configuration changes being made

NVF

04

Summary NVRAM failure status: 0 = good, 1 = fail

NVI

02

Summary NVRAM initialized state: 0 = no, 1 = yes

DSS

01

Digital station status: 0 = good, 1 = bad

Error Code

3

4

5

01

01 02 03 FF

— — — —

02

(1)

(2)

Analog input reference error: (1), (2) = block number of control interface I/O module block

03

(1)

(2)

Missing I/O module or expander board: (1), (2) = block number of I/O module or station

05

(1)

(2)

Configuration error – undefined block: (1), (2) = block number making reference

06

(1)

(2)

Configuration error – input data type is incorrect: (1), (2) = block number making reference

08

(1)

(2)

Trip block activated: (1), (2) = block number of trip block

0F





Primary module has failed and the redundant module configuration is not current

Module Status 15 FEB 1995 G - 16

NVRAM error: Write failure Checksum failure Bad data Reset during write

I-E96-200B

Appendix G

Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules (continued) Byte

Field

3-5 (cont)

Error Code

Field Size or Value 3

4

5

10





Primary module has failed and the dynamic RAM data in the redundant module is not current

11





NVRAM write failure error

1B

20

01 02 03 04 05 06 07 08 09 0A 0B 0C

File system initialization error: 01 = root INODE could not be made 02 = file system parameters out of range 03 = could not open BCONFIG.SYS file 04 = could not write BCONFIG.SYS file 05 = could not make DEV directory 06 = could not open HD0 file 07 = error occurred while writing system files to disk 08 = malloc error occurred on system buffer 09 = malloc error occurred on system buffer 0A = malloc error occurred on system buffer 0B = error found in super block 0C = file system check found errors during start-up

1B

22

01 02

Super block error: 01 = error occurred while trying to load bit maps 02 = could not find a matching device type

1B

23

01 02

1B

26

01 02

Bit map error: 01 = unexpected value found in bit map 02 = error occurred while unloading bit maps during a mount operation

1B

2B

01

I/O error, unexpected I/O operation parameter

1B

32

01

Timer error; file system synchronization timer unable to be created

1B

40

01

Bad major device number; unexpected device type found during operation

01 02 03 04

Format error: 01 = failure during mode select command 02 = failure during format command 03 = failure during capacity command 04 = incompatible block size found (not 512)

NOTE

1B

Error Code

I-E96-200B

Description

4D

Cache buffer error: 01, 02 = no cache buffers available

20





Program format error - inconsistent format table

21

(1)

(2)

File system error: (1), (2) = file number

22

(1)

(2)

Invoke C error: (1), (2) = block number making reference

24

(1)

(2)

C program stack overflow: (1), (2) = block number making reference

28

(1)

(2)

User defined function (UDF) reference is invalid: (1), (2) = block number making reference

29

(1)

(2)

UDF block cannot read program file: (1), (2) = block number making reference

2A

(1)

(2)

Not enough memory for UDF: (1), (2) = block number making reference

2B

(1)

(2)

Missing UDF declaration: (1), (2) = block number making reference

2C

(1)

(2)

Wrong UDF type: (1), (2) = block number making reference

Module Status 15 FEB 1995 G - 17

Appendix G

®

Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules (continued) Byte

Field

3-5 (cont)

Error Code

Field Size or Value

Description

3

4

5

2D

(1)

(2)

Missing UDF auxiliary block: (1), (2) = block number making reference

2E

(1)

(2)

UDF compiler and firmware are incompatible: (1), (2) = block number making reference

2F

(1)

(2)

BASIC program error: (1), (2) = line number of error

6

ETYPE

1F

Enhanced module type = (24)16 = IMMFP01/02/03

7

CWA

80

Controlway bus A failure: 0 = good, 1 = fail

CWB

40

Controlway bus B failure: 0 = good, 1 = fail

R1F

20

Redundancy link channel 1 failure: 0 = good, 1 = fail (IMMFP03 only)

R2F

10

Redundancy link channel 2 failure: 0 = good, 1 = fail (IMMFP03 only)

PF

08

Peripheral failure: 0 = good, 1 = fail (IMMFP03 only)

8

SIM

80

Simulation mode: 0 = normal operation, 1 = simulation active

9 - 13



00

Reserved

14



FF

Module nomenclature: (01)16 = IMMFP01, (02)16 = IMMFP02, (03)16 = IMMFP03

15



FF

Revision letter (in ASCII code), for example, (46)16 = F

16



FF

Revision number (in ASCII code), for example, (30)16 = 0

NOTE: Hard drive file system errors (byte 3 = 1B) pertain only to an IMMFP03 configured to operate with an IMMPI02.

Module Status 15 FEB 1995 G - 18

I-E96-200B

Appendix G

LOCAL TRANSFER MODULES Table G-12. INIIT01/03 INFI-NET to INFI-NET Transfer Module (Local) and INIPT01 INFI-NET to Plant Loop Transfer Module (Local) Byte 1

Bit 7

6

ES

5

4

3

2

MODE

2

1

0

TYPE SIO

CIO

3

PCUs

MOV

NODS

BKCFG

BKSTS

RINGs

41

NSFC

RER1C

RER2C

TER1C

TER2C

RID1C

RID2C

RCFC

51

NSFS

RER1S

RER2S

TER1S

TER2S

RID1S

RID2S

RCFS

6

NVI PSI

ETYPE

7 - 13

Reserved

14

Module nomenclature

15

Revision letter (ASCII)

16

Revision number (ASCII)

NOTE: 1. The last letter of the codes (S or C) in bytes 4 and 5 indicate if the status applies to the satellite ring or the central ring.

Byte 1

2

3

4 - 51

Field

Field Size or Value

Description

ES

80

MODE

60

Error summary: 0 = good, 1 = errors Module mode: 01 = fail, 11 = execute

TYPE

1F

Module type code: (15)16 = INIIT01/03, (16)16 = INIPT01

SIO

20

I/O status for data sourced by satellite ring PCUs: 0 = good, 1 = bad

CIO

10

I/O status for data sourced by central ring PCUs: 0 = good, 1 = bad

NVI

02

Default configuration: 0 = blocks configured, 1 = no blocks configured (INIPT01 only)

PCUs

80

Nodes off-line: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = no, 1 = yes

NODS

20

Combined node environment status for both rings: 0 = good, 1 = bad (INIPT01 only)

BKCFG

10

Redundant configuration: 0 = no, 1 = yes

BKSTS

08

Secondary failed: 0 = no, 1 = yes

RINGs

04

Rings off-line: 0 = on-line, 1 = off-line bridge for remote rings

PSI

01

Primary/secondary indicator: 0 = primary, 1 = secondary

NSF

80

Node environment status flag: 0 = good, 1 = bad

RER1

40

Receive errors on channel 1: 0 = no, 1 = yes

RER2

20

Receive errors on channel 2: 0 = no, 1 = yes

TER1

10

Transmit errors on channel 1: 0 = good, 1 = errors

TER2

08

Transmit errors on channel 2: 0 = good, 1 = errors

RID1

04

Receiver idle of channel 1: 0 = no, 1 = yes

RID2

02

Receiver idle of channel 2: 0 = no, 1 = yes

RCF

01

Ring communication failure (INIIT03 only) Extended module type: (16)16 = INIPT01, (23)16 = INIIT01/03

6

ETYPE

FF

7 - 13



00

Reserved

14



FF

Module nomenclature: (01)16 = INIPT01 and INIIT01, (03)16 = INIIT03

15



FF

Revision letter (in ASCII code), for example, (42)16 = B

16



FF

Revision number (in ASCII code), for example, (31)16 = 1

NOTE: 1. The last letter of the codes (S or C) in bytes 4 and 5 indicate if the status applies to the satellite ring or the central ring.

I-E96-200B

Module Status 15 FEB 1995 G - 19

Appendix G

®

REMOTE TRANSFER MODULES Table G-13. INIIT02 INFI-NET to INFI-NET Transfer Module (Remote) and INIPT02 INFI-NET to Plant Loop Transfer Module (Remote) Byte 1

Bit 7

6

ES

5

4

3

MODE

2

2

SIO

CIO

3

PCUs

MOV

SLSTA

BKCFG

BKSTS

RINGs

4

NSF

RER1

RER2

TER1

TER2

RID1

5

SLST1

DO3ST

SLST2

6

NVI

NDT2

NCD1

14

Module nomenclature = 02 (decimal)

15

Revision letter (ASCII)

16

Revision number (ASCII)

2

3

4

5

RCF

NCD2

Reserved

1

PSI RID2

Reserved NDT1

10 - 13

Byte

0

Module ETYPE

7-8 9

1

TYPE

Field

Field Size or Value

Description

ES

80

MODE

60

Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 01 = fail, 11 = execute

TYPE

1F

Module type code: (15)16 = INIIT02; (18)16 = INIPT02 (see byte 6 for INIIT02 extended code)

SIO

20

I/O status for data sourced by satellite ring PCUs: 0 = good, 1 = bad

CIO

10

I/O status for data sourced by central ring PCUs: 0 = good, 1 = bad

NVI

02

Default nonvolatile memory configuration (INIPT02 only): 0 = blocks configured, 1 = no blocks configured

PCUs

80

Nodes off-line: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = no, 1 = yes

SLSTA

20

Serial link status: 0 = good, 1 = failed

BKCFG

10

Backup module configured: 0 = no, 1 = yes

BKSTS

08

Status of backup module: 0 = good, 1 = bad

RINGs

04

Rings off-line: 0 = on-line, 1 = off-line bridge for remote rings

PSI

01

Primary/secondary indicator: 0 = primary, 1 = secondary

NSF

80

Node environment status flag: 0 = good, 1 = bad

RER1

40

Receive errors on channel 1: 0 = no, 1 = yes

RER2

20

Receive errors on channel 2: 0 = no, 1 = yes

TER1

10

Transmit errors on channel 1: 0 = no, 1 = yes

TER2

08

Transmit errors on channel 2: 0 = no, 1 = yes

RID1

04

Receiver idle on channel 1: 0 = no, 1 = yes

RID2

02

Receiver idle on channel 2: 0 = no, 1 = yes

RCF

01

Ring communication failure: 0 = no, 1 = yes (INIPT02 only) Status of serial link 1: 0 = good, 1 = bad

SLST1

80

DO3ST

10

Digital output 3 state: 0 = de-energized, 1 = energized

SLST2

08

Status of serial link 2: 0 = good, 1 = bad

6

ETYPE

FF

Extended module type: (27)16 = INIIT02, (18)16 = INIPT02

7-8



00

Reserved

Module Status 15 FEB 1995 G - 20

I-E96-200B

Appendix G

Table G-13. INIIT02 INFI-NET to INFI-NET Transfer Module (Remote) and INIPT02 INFI-NET to Plant Loop Transfer Module (Remote) (continued)

I-E96-200B

Byte

Field

Field Size or Value

9

NDT1

01

NIS loop relay drive transistor 1 failure

NDT2

01

NIS loop relay drive transistor 2 failure

NCD1

01

NIS receive channel 1 disable

NCD2

01

NIS receive channel 2 disable

10 - 13





Reserved

14



FF

Module nomenclature: (02)16 = INIIT02, INIPT02

15



FF

Revision letter (in ASCII code), for example, (42)16 = B

16



FF

Revision number (in ASCII code), for example, (30)16 = 0

Description

Module Status 15 FEB 1995 G - 21

Appendix G

®

PROCESS INTERFACE MODULE Table G-14. NPIM01 Process Interface Module Byte 1

Bit 7

6

ES

5

4

3

MODE

0

Reserved

3

PCUs

MOV

NSF

4

LIM

RER1

RER2

5

TER1

TER2

Reserved

Byte

Field

Field Size or Value

1

ES

80

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 01 = fail, 11 = execute

TYPE1

1F

Module type code = (01)16

2





Reserved

3

PCUs

80

Nodes off-line: 0 = no, 1 = yes

MOV

40

Memory overflow: 0 = no, 1 = yes

5

1

TYPE 1

2

4

2

NSF

80

Node environment status flag: 0 = good, 1 = bad

LIM

80

LIM internal error: 0 = no, 1 = yes

RER1

40

Receive errors on channel 1: 0 = no, 1 = yes

RER2

20

Receive errors on channel 2: 0 = no, 1 = yes

TER1

10

Transmit errors on channel 1: 0 = good, 1 = errors

TER2

08

Transmit errors on channel 2: 0 = good, 1 = errors





Reserved

Module Status 15 FEB 1995 G - 22

I-E96-200B

Appendix G

COMMUNICATION PROCESSOR MODULES Table G-15. IMCPM02/03 Communication Port Modules Byte

Bit 7

1

ES

2

FTX

3

PCU

6

5

4

RIO

LIO

MOV

LOP

SDF

Reserved CIU Status

6

Module ETYPE CWA

CWB

NDT1

NDT2

8

NODE TYPE

NCD1

NCD2

Reserved

14

Module nomenclature

15

Revision letter (ASCII)

16

Revision number (ASCII)

Byte

Field

Field Size or Value

1

ES

80

3

0

Reserved

10 - 13

2

1

TYPE

5

9

2

MODE

4

7

I-E96-200B

3

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 00 = configure, 01 = fail, 11 = execute

TYPE

15

Module type: (= 21) enhanced module type (see status byte 6 for enhanced module type code)

FTX

80

First time in execute: 0 = no, 1 = yes

RIO

20

Summary remote input status: 0 = good, 1 = bad

LIO

10

Summary local input status: 0 = good, 1 = bad Node off-line: 0 = no, 1 = yes

PCU

80

MOV

40

Module memory overflow: 0 = no, 1 = yes

LOP

10

Off-line bridge for remote loop: 0 = good, 1 = bad

SDF

01

Security device failure

NODE TYPE

07

Node type set by computer via the SET CIU STATUS command (IMCPM03 only)

4



00

Reserved

5

CIU STATUS

FF

CIU status set by computer via the SET CIU STATUS command (IMCPM03 only)

6

ETYPE

29

Enhanced module type: (41) = IMCPM02/03

7

CWA

80

Controlway bus A failure: 0 = good, 1 = fail

CWB

40

Controlway bus B failure: 0 = good, 1 = fail

8



00

Reserved

9

NDT1

01

NIS loop relay drive transistor 1 failure

NDT2

01

NIS loop relay drive transistor 2 failure

NCD1

01

NIS receive channel 1 disable

NCD2

01

NIS receive channel 2 disable

10 - 13





Reserved

14



FF

Module nomenclature: (3) = IMCPM02/03

15



FF

Revision letter (in ASCII code), for example, (42)16 = B

16



FF

Revision number (in ASCII code), for example, (30)16 = 0

Module Status 15 FEB 1995 G - 23

Appendix G

®

CONFIGURATION AND TUNING, AND ANALOG OUTPUT Table G-16. CTT01/02 Configuration and Tuning Terminal, IMAOM01 Analog Output Module, and NCTM01 Configuration and Tuning Module Byte 1

Bit 7

6

ES

5

3

MODE

2-5

2

1

0

TYPE Reserved

Byte

Field

Field Size or Value

1

ES

80

2-5

4

Description Error summary: 0 = good, 1 = errors

MODE

60

Module mode: 01 = fail, 11 = execute

TYPE

1F

Module type code: (2)16 = NCTM01, (12)16 = CTT01/02, (4)16 = IMAOM01



00

Reserved

Module Status 15 FEB 1995 G - 24

I-E96-200B