Appendix G – Module Status GENERAL DESCRIPTION Appendix G contains module status information by module type. Table G-1 explains analog master module status. • •
IMAMM03. NAMM02/02A.
Table G-2 explains bus module status. • • •
INBIM02 (bus interface). INBTM01 (bus transfer). NBIM01 (bus interface).
Table G-3 explains network processing and Superloop status. • •
INNPM01 (Controlway – network processing). NSBM01 (Superloop).
Table G-4 explains Plant Loop to Plant Loop communications status. • • •
INPPT01 (transfer module). NGCM01/02 (transfer module). NPPG01 (gateway).
Table G-5 explains miscellaneous communications status. • • • • •
CIC01 (computer interface command). INPCI01/02 (Plant Loop to computer interface). INPCT01 (Plant Loop to computer transfer module). INPTM01 (point table module). NLSM01 (loop storage module).
Table G-6 explains INFI-NET to computer communications status. • • •
INICI01 (INFI-NET to computer interface). INICT01/03 (INFI-NET to computer transfer module). INSEM01 (sequence of events).
Table G-7 explains controller module status. • • • • •
I-E96-200B
CLC01/02/03/04 (loop command). IMCOM03/04. IMQRC01 (quick response). NCOM02/02A/03A/04A. NLCM01/02/03 (large).
Module Status 15 FEB 1995 G-1
Appendix G
®
Tables G-8 and G-9 explain logic master module status. • •
IMLMM02. NLMM01/NLMM01A.
Table G-10 explains multi-function, multi-processor, strategic loop and command controller status. • • • • • •
CBC01 (batch command). CSC01 (sequence command). IMMFC03/04/05 (multi-function). IMMPC01 (multi-processing). NMFC01/02 (multi-function). SLC01/21 (strategic loop).
Table G-11 explains multi-function processor module status. •
IMMFP01/02/03/03B.
Table G-12 explains local transfer module status. • •
INIIT01/03 (INFI-NET to INFI-NET local transfer module). INIPT01 (INFI-NET to Plant Loop local transfer module).
Table G-13 explains remote transfer module status. • •
INIIT02 (INFI-NET to INFI-NET remote transfer module). INIPT02 (INFI-NET to Plant Loop remote transfer module).
Table G-14 explains process interface module status. •
NPIM01 (process interface module).
Table G-13 explains communication processor module status. •
IMCPM02/03 (configuration port module).
Table G-16 explains configuration and tuning, and analog output module status. • • •
Module Status 15 FEB 1995 G-2
CTT01/02 (configuration and tuning terminals). IMAOM01 (analog output module). NCTM01 (configuration and tuning module).
I-E96-200B
Appendix G
ANALOG MASTER MODULES Table G-1. IMAMM03 and NAMM02/02A Analog Master Modules Byte 1
Bit 7
6
ES
5
FTX
BAC
3
REF
IOP
SCF
4
FCG
FCL
ICG
5
1
2
3
4
5
I-E96-200B
3
2
1
0
TYPE
2
Byte
4
MODE LIO CAL
NVF
NVI
CJR
SRV
ICL
EPF
ECS BLK
Field
Field Size or Value
Description
ES
80
Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code = (9)16
FTX
80
First time in execute: 0 = no, 1 = yes
BAC
40
Backup status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad (I/O module not responding or bad quality input)
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
REF
80
Master reference out of range: 0 = no, 1 = yes
IOP
40
Summary open thermocouple status: 0 = good, 1 = bad (configured thermocouple point is open)
SCF
20
I/O module configuration problem: 0 = no, 1 = yes (problem with I/O module definition block - occurs when going from configure to execute mode)
CAL
08
Summary calibration status: 0 = good, 1 = bad
CJR
04
Summary cold junction RTD status: 0 = good, 1 = bad
SRV
02
Summary of points not in service: 0 = no, 1 = yes (point is out of service for calibration)
EPF
01
NVRAM power failure during write: 0 = no, 1 = yes
FCG
80
Failed configuration NVRAM: 0 = no, 1 = yes (NAMM02 only)
FCL
40
Failed calibration NVRAM: 0 = no, 1 = yes (NAMM02 only)
ICG
20
Configuration NVRAM initialized: 0 = no, 1 = yes (NAMM02 only)
ICL
10
Calibration NVRAM initialized: 0 = no, 1 = yes (NAMM02 only)
ECS
0F
Error code status: 0 = good, not 0 = error code 1 = I/O module type and point type disagree (BLK) 2 = input type disagrees with engineering unit type (BLK) 3 = point input type invalid (BLK) 4 = trend type invalid (BLK) 5 = cold junction input invalid (BLK) (IMAMM03 only) 6 = polynomial block address is invalid (BLK) (IMAMM03 only) 7 = DIS block data invalid (BLK) (IMAMM03 only)
BLK
FF
Block number referring to the error code status (ECS)
Module Status 15 FEB 1995 G-3
Appendix G
®
PLANT BUS LOOP MODULES Table G-2. INBIM02 and NBIM01 Bus Interface Modules (Module Bus), and INBTM01 Bus Transfer Module (Module Bus) Byte
Bit 7
6
5
4
3
1
ES
2
LIN
MODE
3
CSP
MOV
NSF
RLB
SBF
4
LIM
LR1
LR2
LT1
LT2
2
1
0
TYPE
5
PSI
Reserved
Byte
Field
Field Size or Value
1
ES
80
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code: (8)16 = NBIM01 and INBIM02, (E)16 = INBTM01
2
LIN
80
LIM/BTM on-line/off-line: 0 = on-line, 1 = off-line (INBTM01 only)
3
CSP
80
Communication status problem: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = good, 1 = bad
NSF
20
Node status flag: 0 = good, 1 = bad
RLB
10
Redundant LIM/BIM configured: 0 = no, 1 = yes (NBIM01 and INBIM02 only)
SBF
08
Secondary BIM failure flag: 0 = good, 1 = fail (NBIM01 and INBIM02 only)
PSI
01
Primary/secondary indicator: 0 = primary, 1 = secondary (NBIM01 and INBIM02 only)
4
5
LIM
80
LIM problem flag: 0 = no, 1 = yes
LR1
40
Plant Loop 1 receive error: 0 = no, 1 = yes
LR2
20
Plant Loop 2 receive error; 0 = no, 1 = yes
LT1
10
Plant Loop 1 transmit error: 0 = no, 1 = yes
LT2
08
Plant Loop 2 transmit error: 0 = no, 1 = yes
—
00
Reserved
Module Status 15 FEB 1995 G-4
I-E96-200B
Appendix G
INFI-NET NETWORK PROCESSING AND SUPERLOOP BUS MODULES Table G-3. INNPM01 Network Processing Module (Controlway) and NSBM01 Superloop Bus Module (Module Bus) Byte 1
Bit 7
6
ES
5
1
PCU
MOV
4
NSF
RER1
RER2
BKCFG
BKSTS
TER1
TER2
PSI RID1
RID2
ETYPE CWA
CWB
Reserved
8
Reserved NDT1
NDT2
NCD1
10 - 13
Reserved
14
Module nomenclature
15
Revision letter (ASCII)
16
Revision number (ASCII)
Byte
Field
Field Size or Value
1
ES
80
NCD2
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 11 = execute
TYPE
1F
Module type code: (15)16 = enhanced status
2
—
—
Reserved
3
PCU
80
Node off-line: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = good, 1 = bad
BKCFG
10
Redundant module configured: 0 = no, 1 = yes
BKSTS
08
Secondary module failure: 0 = good, 1 = bad
PSI
01
Primary/secondary indicator: 0 = primary, 1 = secondary
NSF
80
Node environment status flag: 0 = good, 1 = bad
RER1
40
Receive errors on channel 1: 0 = no, 1 = yes
RER2
20
Receive errors on channel 2: 0 = no, 1 = yes
TER1
10
Transmit errors on channel 1: 0 = no, 1 = yes
TER2
08
Transmit errors on channel 2: 0 = no, 1 = yes
RID1
04
Receiver idle on channel 1: 0 = no, 1 = yes
RID2
02
Receiver idle on channel 2: 0 = no, 1 = yes
RCF
01
Ring communication failure for local ring: 0 = no, 1 = yes
5
—
—
Reserved
6
ETYPE
FF
Enhanced module type: (25)16 = INNPM01, (21)16 = NSBM01
7
CWA
80
Controlway bus A failure: 0 = good, 1 = fail (INNPM01 only)
CWB
40
Controlway bus B failure: 0 = good, 1 = fail (INNPM01 only)
—
00
Reserved
8
RCF
Reserved
6
4
0
TYPE
5
I-E96-200B
2
Reserved
3
9
3
MODE
2
7
4
Module Status 15 FEB 1995 G-5
Appendix G
®
Table G-3. INNPM01 Network Processing Module (Controlway) and NSBM01 Superloop Bus Module (Module Bus) (continued) Byte
Field
Field Size or Value
9
NDT1
01
NIS loop relay drive transistor 1 failure
Description
NDT2
01
NIS loop relay drive transistor 2 failure
NCD1
01
NIS receive channel 1 disable
NCD2
01
NIS receive channel 2 disable
10 - 13
—
—
Reserved
14
—
FF
Module nomenclature: (01)16 = INNPM01 and NSBM01
15
—
FF
Revision letter (in ASCII code), for example, (44)16 = D
16
—
FF
Revision number (in ASCII code), for example, (31)16 = 1
Module Status 15 FEB 1995 G-6
I-E96-200B
Appendix G
PLANT LOOP TO PLANT LOOP COMMUNICATIONS Table G-4. INPPT01 Transfer Module, NGCM01/02 Plant Loop to Plant Loop Transfer Module, and NPPGO1 Plant Loop to Plant Loop Gateway Byte
Bit 7
6
5
4
1
ES
2
FTX
BAC
MODE RIO
LIO
3
PCU
MEM
NEF
SL1
SL2
4
LIM
LR1
LR2
LT1
LT2
Field
Field Size or Value
1
ES
80
3
4
5
1
0
NVI
CFG
Reserved
Byte
2
2 TYPE
5
I-E96-200B
3
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code: (11)16 = NGCM01 and INPPT01
FTX
80
First time in execute: 0 = no, 1 = yes
BAC
40
Backup status: 0 = good, 1 = bad
RIO
20
Summary remote I/O status: 0 = good, 1 = bad
LIO
10
Summary local I/O status: 0 = good, 1 = bad
NVI
04
NVRAM checksum error: 0 = good, 1 = bad
CFG
02
Default configuration: 0 = no, 1 = yes
PCU
80
One or more PCUs off-line: 0 = no, 1 = yes
MEM
40
Memory overflow: 0 = good, 1 = bad
NEF
20
Node environment failure: 0 = good, 1 = bad
SL1
—
Serial link 1 status: 0 = good, 1 = bad
SL2
—
Serial link 2 status: 0 = good, 1 = bad
LIM
80
LIM problem flag: 0 = no, 1 = yes
LR1
40
Loop receive error channel 1: 0 = no, 1 = yes
LR2
20
Loop receive error channel 0: 0 = no, 1 = yes
LT1
10
Loop transmit error channel 1: 0 = no, 1 = yes
LT2
08
Loop transmit error channel 0: 0 = no, 1 = yes
—
00
Reserved
Module Status 15 FEB 1995 G-7
Appendix G
®
PLANT LOOP TO COMPUTER COMMUNICATIONS - COMPUTER INTERFACE COMMAND Table G-5. CIC01 Computer Interface Command, INPCI01/02 Plant Loop to Computer Interface, INPCT01 Plant Loop to Computer Transfer Module, INPTM01 Point Table Module, and NLSM01 Loop Storage Module Byte
Bit 7
6
5
4
RIO
LIO
1
ES
2
FTX
3
CSP
MOV
NSF
4
LIM
LR1
LR2
MODE
Field
Field Size or Value
1
ES
80
4
5
1
0
NODE TYPE LT1
LT2 HOST
Byte
3
2 TYPE
5
2
3
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode:
TYPE
1F
Module type code: (0A)16 = INPTM01, INPCI01 (10)16 = NLSM01, INPCT01, INPCI02 (17)16 = CIC01
00 = configure, 10 = error, 11 = execute
FTX
80
First time in execute: 0 = no, 1 = yes
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
CSP
80
Communication status problem: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = good, 1 = bad
NSF
20
Node status flag: 0 = good, 1 = bad
NODE TYPE
07
Node type: 0 = computer interface unit, 1 = operator interface station or management command system, 2 = operator interface unit
LIM
80
LIM problem flag: 0 = no, 1 = yes
LR1
40
Plant Loop 1 receive error: 0 = no, 1 = yes
LR2
20
Plant Loop 2 receive error: 0 = no, 1 = yes
LT1
10
Plant Loop 1 transmit error: 0 = no, 1 = yes
LT2
08
Plant Loop 2 transmit error: 0 = no, 1 = yes
HOST
FF
Value set by the computer (when non-zero, ES = 1)
Module Status 15 FEB 1995 G-8
I-E96-200B
Appendix G
INFI-NET TO COMPUTER COMMUNICATIONS AND SEQUENCE OF EVENTS MONITOR Table G-6. INICI01 INFI-NET to Computer Interface, INICT01/03 INFI-NET to Computer Transfer Module (Local), and INSEM01 Sequence of Events Monitor Byte
Bit 7
6
1
ES
2
FTX
3
CSP
MOV
4
NSF
LR1
5
4
3
RIO
LIO
CFM
LOP
SDF
MODE
LR2
LT1 ETYPE
Reserved NDT2
NCD1 Reserved
14
Module nomenclature
15
Revision letter (ASCII)
16
Revision number (ASCII)
3
4
I-E96-200B
NDT1
10 - 13
2
ERM NODE TYPE
LT2
6
1
0
RI1
RI2
RCF
HOST
7-8
Byte
1
TYPE
5
9
2
Field
Field Size or Value
NCD2
Description
ES
80
Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 01 = fail, 10 = error, 11 = execute
TYPE
1F
Module type code: (15)16 = enhanced status
FTX
80
First time in execute: 0 = no, 1 = yes
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
CFM
08
Module in configure mode (MODE = 00): 0 = no, 1 = yes
ERM
01
Module in error mode (MODE = 10): 0 = no, 1 = yes
CSP
80
Communication status problem: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = good, 1 = bad
LOP
10
Off-line bridge for remote loop: 0 = no, 1 = yes
SDF
01
Security device failure
NODE TYPE
07
Node type: 0 = computer interface, 1 = operator interface unit or management command system, 2 = operator interface unit
NSF
80
Node environment status flag: 0 = good, 1 = bad
LR1
40
INFI-NET 1 receive error: 0 = no, 1 = yes
LR2
20
INFI-NET 2 receive error: 0 = no, 1 = yes
LT1
10
INFI-NET 1 transmit error: 0 = no, 1 = yes
LT2
08
INFI-NET 2 transmit error: 0 = no, 1 = yes
RI1
04
Receiver idle on channel 1 of central loop: 0 = no, 1 = yes
RI2
02
Receiver idle on channel 2 of central loop: 0 = no, 1 = yes
RCF
01
Ring communication failure: 0 = no, 1 = yes
5
HOST
FF
Value set by the computer (when non-zero, ES = 1)
6
ETYPE
20
Enhanced module type (20)16 = INICT01/03, (2A)16 = INSEM01
7-8
—
00
Reserved
Module Status 15 FEB 1995 G-9
Appendix G
®
Table G-6. INICI01 INFI-NET to Computer Interface, INICT01/03 INFI-NET to Computer Transfer Module (Local), and INSEM01 Sequence of Events Monitor (continued) Byte
Field
Field Size or Value
9
NDT1
01
NIS loop relay drive transistor 1 failure
Description
NDT2
01
NIS loop relay drive transistor 2 failure
NCD1
01
NIS receive channel 1 disable
NCD2
01
NIS receive channel 2 disable
10 - 13
—
—
Reserved
14
—
FF
Module nomenclature (01)16 = INICT01 and INSEM01, (03)16 = INICT03
15
—
FF
Revision letter (in ASCII code), for example, (45)16 = E
16
—
FF
Revision number (in ASCII code), for example, (30)16 = 0
Module Status 15 FEB 1995 G - 10
I-E96-200B
Appendix G
CONTROLLER MODULES Table G-7. CLC01/02/03/04 Loop Command Controller Module, IMCOM03/04 and NCOM02/02A/03A/04A Controller Module, IMQRC01 Quick Response Controller Module, and NLCM01/02/03 Large Controller Module Byte
Bit 7
1
ES
2
FTX
6
4
3
2
RIO
LIO
SEG
MODE Error code
4
Error code descriptor (1)
5
Error code descriptor (2)
1
2
Field
Field Size or Value
0
NVF
NVI
DSS
Description
ES
80
MODE
60
Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code: (5)16 = COM and QRC, (6)16 = CLC, (0F)16 = NLCM01, (1E)16 = NLCM02, (1F)16 = NLCM03
FTX
80
First time in execute: 0 = no, 1 = yes
Error summary: 0 = good, 1 = errors
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
SEG
08
Summary segment alarm status: 0 = no, 1 = yes
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
DSS 3-5
1
TYPE
3
Byte
I-E96-200B
5
Error Code
01
Digital station status: 0 = good, 1 = bad
3
4
5
01
01 02 03 FF
— — — —
NVRAM error: Write failure Checksum failure Bad data Reset during write
02
00
04 05
AI reference error: 1-V reference 5-V reference
03
00
—
Missing I/O expansion board
05
(1)
(2)
Configuration error – undefined block: (1) = block number making reference (2) = block number being referenced
06
(1)
(2)
Configuration error – input data type is incorrect: (1) = block number making reference (2) = block number being referenced
08
(1)
—
Trip block activated: (1) = block number of trip block
09
(1)
(2)
Function not allowed in segment: (1) = segment block number (2) = block number in error
0A
—
—
Too many segment control blocks
0B
(1)
(2)
Segment control block priority violation: (1) = block number of first segment (2) = block number of segment in error
Module Status 15 FEB 1995 G - 11
Appendix G
®
LOGIC MASTER MODULES Table G-8. NLMM01 Logic Master Module Byte
Bit 7
1
ES
2
FTX
6
5
4
3
RIO
LIO
2
MODE MOV
NVF
Error code
4
Error code descriptor (1)
5
Error code descriptor (2)
1
2
3-5
Field
Field Size or Value
0
NVI
DSS
TYPE
3
Byte
1
Description
ES
80
MODE
60
Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code = (7)16
FTX
80
First time in execute: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = no, 1 = yes
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
DSS
01
Digital station status: 0 = good, 1 = bad
Error Code
3
4
5 NVRAM error: Write failure Checksum failure Bad data Reset during write
01 01 02 03 FF
— — — —
03
(1)
—
Missing I/O module block or module number of I/O module or DLS: (1) = group number
05
(1)
(2)
Configuration error – undefined block: (1) = block number making reference (2) = block number being referenced
07
(1)
—
Insufficient memory in remote memory: (1) = block number of digital input list (function code 46)
08
(1)
—
Trip block activated: (1) = block number of trip block
Module Status 15 FEB 1995 G - 12
I-E96-200B
Appendix G
Table G-9. IMLMM02 or NLMM01A Logic Master Module Byte
Bit 7
1
ES
2
FTX
6
5
4
3
RIO
LIO
2
MODE MOV
NVF
Error code
4
Error code descriptor (1)
5
Error code descriptor (2)
1
2
3-5
Field
Field Size or Value
0
NVI
DLS
TYPE
3
Byte
1
Description
ES
80
MODE
60
Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code = (C)16 First time in execute: 0 = no, 1 = yes
FTX
80
MOV
40
Memory overflow: 0 = no, 1 = yes
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
DLS
01
Digital logic station status: 0 = good, 1 = bad
Error Code
3
4
5 NVRAM error: Write failure Checksum failure Bad data Reset during write
01 01 02 03 FF
— — — —
03
(1)
(2)
Missing I/O module block or module number of I/O module or DLS: (1), (2) = I/O module address
05
(1)
(2)
Configuration error – undefined block: (1), (2) = block number making reference
06
(1)
(2)
Configuration error – input data type is incorrect: (1), (2) = block number making reference
07
(1)
(2)
Insufficient memory in remote memory: (1), (2) = block number of digital input list (function code 46)
08
(1)
(2)
Trip block activated: (1) = block number of trip block
—
Too many segment control blocks
—
Configuration error, sequencing too complex
0A 0C
—
NOTE: All numbers in bytes 4 and 5 are in binary coded decimal (BCD) format.
I-E96-200B
Module Status 15 FEB 1995 G - 13
Appendix G
®
MULTI-FUNCTION, MULTI-PROCESSOR, STRATEGIC LOOP AND COMMAND CONTROLLERS Table G-10. CBC01 Batch Command Controller, CSC01 Sequence Command Controller, IMMFC03/04/05 and NMFC01/02 Multi-Function Controller Module, IMMPC01 MultiProcessing Controller Module, and SLC01/21 Strategic Loop Controller Byte
Bit 7
1
ES
2
FTX
6
5
4
3
2
RIO
LIO
CFG
MODE BAC
Error code
4
Error code descriptor (1)
5
Error code descriptor (2)
1
2
3-5 Byte 3 is displayed on the front panel LEDs when the module is in ERROR mode. Under MONITOR/ STATUS screen for SLC.
Field
Field Size or Value
0
NVI
DSS
TYPE
3
Byte
1
NVF
Description
ES
80
MODE
60
Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code: (B)16 = NMFC01/02 and IMMFC03/04/05, (D)16 = IMMPC01, (13)16 = CBC01, (14)16 = CSC01, (19)16 = SLC01/21
FTX
80
First time in execute: 0 = no, 1 = yes
BAC
40
Backup status: 0 = good, 1 = bad
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
CFG
08
On-line configuration changes being made
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
DSS
01
Digital station status: 0 = good, 1 = bad
Error Code
3
4
5
01
01 02 03 FF
— — — —
02
(1)
(2)
Analog input reference error: (1), (2) = block number of control interface I/O module block
03
(1)
(2)
Missing I/O module or expander board: (1), (2) = block number of I/O module or station
05
(1)
(2)
Configuration error – undefined block: (1), (2) = block number making reference
06
(1)
(2)
Configuration error – input data type is incorrect: (1), (2) = block number making reference
08
(1)
(2)
Trip block activated: (1), (2) = block number of trip block
0F
—
—
Primary module has failed and the redundant module configuration is not current
10
—
—
Primary module has failed and the dynamic RAM data in the redundant module is not current
14
—
—
Module is set for INFI-NET but is in a Plant Loop environment
Module Status 15 FEB 1995 G - 14
NVRAM error: Write failure Checksum failure Bad data Reset during write
I-E96-200B
Appendix G
Table G-10. CBC01 Batch Command Controller, CSC01 Sequence Command Controller, IMMFC03/04/05 and NMFC01/02 Multi-Function Controller Module, IMMPC01 MultiProcessing Controller Module, and SLC01/21 Strategic Loop Controller (continued)
I-E96-200B
Byte
Field
3-5 (cont)
Error Code
Field Size or Value
Description
3
4
5
20
—
—
Program format error - inconsistent format table (IMMFC03 only)
21
(1)
(2)
File system error (IMMFC03 only) (1), (2) = file number
22
(1)
(2)
Invoke C error (IMMFC03 only) (1), (2) = block number making reference
24
(1)
(2)
C program stack overflow (IMMFC03 only) (1), (2) = block number making reference
28
(1)
(2)
User defined function (UDF) reference is invalid (IMMFC03/04 only) (1), (2) = block number making reference
29
(1)
(2)
UDF block cannot read program file (IMMFC03/04 only) (1), (2) = block number making reference
2A
(1)
(2)
Not enough memory for UDF (IMMFC03/04 only) (1), (2) = block number making reference
2B
(1)
(2)
Missing UDF declaration (IMMFC03/04 only) (1), (2) = block number making reference
2C
(1)
(2)
Wrong UDF type (IMMFC03/04 only) (1), (2) = block number making reference
2D
(1)
(2)
Missing UDF auxiliary block (IMMFC03/04 only) (1), (2) = block number making reference
2E
(1)
(2)
UDF compiler and firmware are incompatible (IMMFC03/04 only) (1), (2) = block number making reference
2F
(1)
(2)
BASIC program error (IMMFC03 and NMFC02 only) (1), (2) = line number of error
Module Status 15 FEB 1995 G - 15
Appendix G
®
MULTI-FUNCTION PROCESSOR MODULES Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules Byte
Bit 7
1
ES
2
FTX
6
5
4
3
2
RIO
LIO
CFG
MODE BAC
Error code
4
Error code descriptor (1)
5
Error code descriptor (2)
6 CWA
8
SIM
CWB
R1F
R2F
NVI
DSS
PF
Reserved
Reserved
9 - 13
Reserved
14
Module nomenclature
15
Revision letter (ASCII)
16
Revision number (ASCII)
Byte
Field
Field Size or Value
1
ES
80
Byte 3 is displayed on the front panel LEDs when the module is in ERROR mode.
NVF
ETYPE
7
3-5
0
TYPE
3
2
1
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 10 = error, 11 = execute
TYPE
1F
Module type code: (15)16 = Enhanced status
FTX
80
First time in execute: 0 = no, 1 = yes
BAC
40
Backup status: 0 = good, 1 = bad
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad
CFG
08
On-line configuration changes being made
NVF
04
Summary NVRAM failure status: 0 = good, 1 = fail
NVI
02
Summary NVRAM initialized state: 0 = no, 1 = yes
DSS
01
Digital station status: 0 = good, 1 = bad
Error Code
3
4
5
01
01 02 03 FF
— — — —
02
(1)
(2)
Analog input reference error: (1), (2) = block number of control interface I/O module block
03
(1)
(2)
Missing I/O module or expander board: (1), (2) = block number of I/O module or station
05
(1)
(2)
Configuration error – undefined block: (1), (2) = block number making reference
06
(1)
(2)
Configuration error – input data type is incorrect: (1), (2) = block number making reference
08
(1)
(2)
Trip block activated: (1), (2) = block number of trip block
0F
—
—
Primary module has failed and the redundant module configuration is not current
Module Status 15 FEB 1995 G - 16
NVRAM error: Write failure Checksum failure Bad data Reset during write
I-E96-200B
Appendix G
Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules (continued) Byte
Field
3-5 (cont)
Error Code
Field Size or Value 3
4
5
10
—
—
Primary module has failed and the dynamic RAM data in the redundant module is not current
11
—
—
NVRAM write failure error
1B
20
01 02 03 04 05 06 07 08 09 0A 0B 0C
File system initialization error: 01 = root INODE could not be made 02 = file system parameters out of range 03 = could not open BCONFIG.SYS file 04 = could not write BCONFIG.SYS file 05 = could not make DEV directory 06 = could not open HD0 file 07 = error occurred while writing system files to disk 08 = malloc error occurred on system buffer 09 = malloc error occurred on system buffer 0A = malloc error occurred on system buffer 0B = error found in super block 0C = file system check found errors during start-up
1B
22
01 02
Super block error: 01 = error occurred while trying to load bit maps 02 = could not find a matching device type
1B
23
01 02
1B
26
01 02
Bit map error: 01 = unexpected value found in bit map 02 = error occurred while unloading bit maps during a mount operation
1B
2B
01
I/O error, unexpected I/O operation parameter
1B
32
01
Timer error; file system synchronization timer unable to be created
1B
40
01
Bad major device number; unexpected device type found during operation
01 02 03 04
Format error: 01 = failure during mode select command 02 = failure during format command 03 = failure during capacity command 04 = incompatible block size found (not 512)
NOTE
1B
Error Code
I-E96-200B
Description
4D
Cache buffer error: 01, 02 = no cache buffers available
20
—
—
Program format error - inconsistent format table
21
(1)
(2)
File system error: (1), (2) = file number
22
(1)
(2)
Invoke C error: (1), (2) = block number making reference
24
(1)
(2)
C program stack overflow: (1), (2) = block number making reference
28
(1)
(2)
User defined function (UDF) reference is invalid: (1), (2) = block number making reference
29
(1)
(2)
UDF block cannot read program file: (1), (2) = block number making reference
2A
(1)
(2)
Not enough memory for UDF: (1), (2) = block number making reference
2B
(1)
(2)
Missing UDF declaration: (1), (2) = block number making reference
2C
(1)
(2)
Wrong UDF type: (1), (2) = block number making reference
Module Status 15 FEB 1995 G - 17
Appendix G
®
Table G-11. IMMFP01/02/03/03B Multi-Function Processor Modules (continued) Byte
Field
3-5 (cont)
Error Code
Field Size or Value
Description
3
4
5
2D
(1)
(2)
Missing UDF auxiliary block: (1), (2) = block number making reference
2E
(1)
(2)
UDF compiler and firmware are incompatible: (1), (2) = block number making reference
2F
(1)
(2)
BASIC program error: (1), (2) = line number of error
6
ETYPE
1F
Enhanced module type = (24)16 = IMMFP01/02/03
7
CWA
80
Controlway bus A failure: 0 = good, 1 = fail
CWB
40
Controlway bus B failure: 0 = good, 1 = fail
R1F
20
Redundancy link channel 1 failure: 0 = good, 1 = fail (IMMFP03 only)
R2F
10
Redundancy link channel 2 failure: 0 = good, 1 = fail (IMMFP03 only)
PF
08
Peripheral failure: 0 = good, 1 = fail (IMMFP03 only)
8
SIM
80
Simulation mode: 0 = normal operation, 1 = simulation active
9 - 13
—
00
Reserved
14
—
FF
Module nomenclature: (01)16 = IMMFP01, (02)16 = IMMFP02, (03)16 = IMMFP03
15
—
FF
Revision letter (in ASCII code), for example, (46)16 = F
16
—
FF
Revision number (in ASCII code), for example, (30)16 = 0
NOTE: Hard drive file system errors (byte 3 = 1B) pertain only to an IMMFP03 configured to operate with an IMMPI02.
Module Status 15 FEB 1995 G - 18
I-E96-200B
Appendix G
LOCAL TRANSFER MODULES Table G-12. INIIT01/03 INFI-NET to INFI-NET Transfer Module (Local) and INIPT01 INFI-NET to Plant Loop Transfer Module (Local) Byte 1
Bit 7
6
ES
5
4
3
2
MODE
2
1
0
TYPE SIO
CIO
3
PCUs
MOV
NODS
BKCFG
BKSTS
RINGs
41
NSFC
RER1C
RER2C
TER1C
TER2C
RID1C
RID2C
RCFC
51
NSFS
RER1S
RER2S
TER1S
TER2S
RID1S
RID2S
RCFS
6
NVI PSI
ETYPE
7 - 13
Reserved
14
Module nomenclature
15
Revision letter (ASCII)
16
Revision number (ASCII)
NOTE: 1. The last letter of the codes (S or C) in bytes 4 and 5 indicate if the status applies to the satellite ring or the central ring.
Byte 1
2
3
4 - 51
Field
Field Size or Value
Description
ES
80
MODE
60
Error summary: 0 = good, 1 = errors Module mode: 01 = fail, 11 = execute
TYPE
1F
Module type code: (15)16 = INIIT01/03, (16)16 = INIPT01
SIO
20
I/O status for data sourced by satellite ring PCUs: 0 = good, 1 = bad
CIO
10
I/O status for data sourced by central ring PCUs: 0 = good, 1 = bad
NVI
02
Default configuration: 0 = blocks configured, 1 = no blocks configured (INIPT01 only)
PCUs
80
Nodes off-line: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = no, 1 = yes
NODS
20
Combined node environment status for both rings: 0 = good, 1 = bad (INIPT01 only)
BKCFG
10
Redundant configuration: 0 = no, 1 = yes
BKSTS
08
Secondary failed: 0 = no, 1 = yes
RINGs
04
Rings off-line: 0 = on-line, 1 = off-line bridge for remote rings
PSI
01
Primary/secondary indicator: 0 = primary, 1 = secondary
NSF
80
Node environment status flag: 0 = good, 1 = bad
RER1
40
Receive errors on channel 1: 0 = no, 1 = yes
RER2
20
Receive errors on channel 2: 0 = no, 1 = yes
TER1
10
Transmit errors on channel 1: 0 = good, 1 = errors
TER2
08
Transmit errors on channel 2: 0 = good, 1 = errors
RID1
04
Receiver idle of channel 1: 0 = no, 1 = yes
RID2
02
Receiver idle of channel 2: 0 = no, 1 = yes
RCF
01
Ring communication failure (INIIT03 only) Extended module type: (16)16 = INIPT01, (23)16 = INIIT01/03
6
ETYPE
FF
7 - 13
—
00
Reserved
14
—
FF
Module nomenclature: (01)16 = INIPT01 and INIIT01, (03)16 = INIIT03
15
—
FF
Revision letter (in ASCII code), for example, (42)16 = B
16
—
FF
Revision number (in ASCII code), for example, (31)16 = 1
NOTE: 1. The last letter of the codes (S or C) in bytes 4 and 5 indicate if the status applies to the satellite ring or the central ring.
I-E96-200B
Module Status 15 FEB 1995 G - 19
Appendix G
®
REMOTE TRANSFER MODULES Table G-13. INIIT02 INFI-NET to INFI-NET Transfer Module (Remote) and INIPT02 INFI-NET to Plant Loop Transfer Module (Remote) Byte 1
Bit 7
6
ES
5
4
3
MODE
2
2
SIO
CIO
3
PCUs
MOV
SLSTA
BKCFG
BKSTS
RINGs
4
NSF
RER1
RER2
TER1
TER2
RID1
5
SLST1
DO3ST
SLST2
6
NVI
NDT2
NCD1
14
Module nomenclature = 02 (decimal)
15
Revision letter (ASCII)
16
Revision number (ASCII)
2
3
4
5
RCF
NCD2
Reserved
1
PSI RID2
Reserved NDT1
10 - 13
Byte
0
Module ETYPE
7-8 9
1
TYPE
Field
Field Size or Value
Description
ES
80
MODE
60
Error summary: 0 = good, 1 = errors Module mode: 00 = configure, 01 = fail, 11 = execute
TYPE
1F
Module type code: (15)16 = INIIT02; (18)16 = INIPT02 (see byte 6 for INIIT02 extended code)
SIO
20
I/O status for data sourced by satellite ring PCUs: 0 = good, 1 = bad
CIO
10
I/O status for data sourced by central ring PCUs: 0 = good, 1 = bad
NVI
02
Default nonvolatile memory configuration (INIPT02 only): 0 = blocks configured, 1 = no blocks configured
PCUs
80
Nodes off-line: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = no, 1 = yes
SLSTA
20
Serial link status: 0 = good, 1 = failed
BKCFG
10
Backup module configured: 0 = no, 1 = yes
BKSTS
08
Status of backup module: 0 = good, 1 = bad
RINGs
04
Rings off-line: 0 = on-line, 1 = off-line bridge for remote rings
PSI
01
Primary/secondary indicator: 0 = primary, 1 = secondary
NSF
80
Node environment status flag: 0 = good, 1 = bad
RER1
40
Receive errors on channel 1: 0 = no, 1 = yes
RER2
20
Receive errors on channel 2: 0 = no, 1 = yes
TER1
10
Transmit errors on channel 1: 0 = no, 1 = yes
TER2
08
Transmit errors on channel 2: 0 = no, 1 = yes
RID1
04
Receiver idle on channel 1: 0 = no, 1 = yes
RID2
02
Receiver idle on channel 2: 0 = no, 1 = yes
RCF
01
Ring communication failure: 0 = no, 1 = yes (INIPT02 only) Status of serial link 1: 0 = good, 1 = bad
SLST1
80
DO3ST
10
Digital output 3 state: 0 = de-energized, 1 = energized
SLST2
08
Status of serial link 2: 0 = good, 1 = bad
6
ETYPE
FF
Extended module type: (27)16 = INIIT02, (18)16 = INIPT02
7-8
—
00
Reserved
Module Status 15 FEB 1995 G - 20
I-E96-200B
Appendix G
Table G-13. INIIT02 INFI-NET to INFI-NET Transfer Module (Remote) and INIPT02 INFI-NET to Plant Loop Transfer Module (Remote) (continued)
I-E96-200B
Byte
Field
Field Size or Value
9
NDT1
01
NIS loop relay drive transistor 1 failure
NDT2
01
NIS loop relay drive transistor 2 failure
NCD1
01
NIS receive channel 1 disable
NCD2
01
NIS receive channel 2 disable
10 - 13
—
—
Reserved
14
—
FF
Module nomenclature: (02)16 = INIIT02, INIPT02
15
—
FF
Revision letter (in ASCII code), for example, (42)16 = B
16
—
FF
Revision number (in ASCII code), for example, (30)16 = 0
Description
Module Status 15 FEB 1995 G - 21
Appendix G
®
PROCESS INTERFACE MODULE Table G-14. NPIM01 Process Interface Module Byte 1
Bit 7
6
ES
5
4
3
MODE
0
Reserved
3
PCUs
MOV
NSF
4
LIM
RER1
RER2
5
TER1
TER2
Reserved
Byte
Field
Field Size or Value
1
ES
80
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 01 = fail, 11 = execute
TYPE1
1F
Module type code = (01)16
2
—
—
Reserved
3
PCUs
80
Nodes off-line: 0 = no, 1 = yes
MOV
40
Memory overflow: 0 = no, 1 = yes
5
1
TYPE 1
2
4
2
NSF
80
Node environment status flag: 0 = good, 1 = bad
LIM
80
LIM internal error: 0 = no, 1 = yes
RER1
40
Receive errors on channel 1: 0 = no, 1 = yes
RER2
20
Receive errors on channel 2: 0 = no, 1 = yes
TER1
10
Transmit errors on channel 1: 0 = good, 1 = errors
TER2
08
Transmit errors on channel 2: 0 = good, 1 = errors
—
—
Reserved
Module Status 15 FEB 1995 G - 22
I-E96-200B
Appendix G
COMMUNICATION PROCESSOR MODULES Table G-15. IMCPM02/03 Communication Port Modules Byte
Bit 7
1
ES
2
FTX
3
PCU
6
5
4
RIO
LIO
MOV
LOP
SDF
Reserved CIU Status
6
Module ETYPE CWA
CWB
NDT1
NDT2
8
NODE TYPE
NCD1
NCD2
Reserved
14
Module nomenclature
15
Revision letter (ASCII)
16
Revision number (ASCII)
Byte
Field
Field Size or Value
1
ES
80
3
0
Reserved
10 - 13
2
1
TYPE
5
9
2
MODE
4
7
I-E96-200B
3
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 00 = configure, 01 = fail, 11 = execute
TYPE
15
Module type: (= 21) enhanced module type (see status byte 6 for enhanced module type code)
FTX
80
First time in execute: 0 = no, 1 = yes
RIO
20
Summary remote input status: 0 = good, 1 = bad
LIO
10
Summary local input status: 0 = good, 1 = bad Node off-line: 0 = no, 1 = yes
PCU
80
MOV
40
Module memory overflow: 0 = no, 1 = yes
LOP
10
Off-line bridge for remote loop: 0 = good, 1 = bad
SDF
01
Security device failure
NODE TYPE
07
Node type set by computer via the SET CIU STATUS command (IMCPM03 only)
4
—
00
Reserved
5
CIU STATUS
FF
CIU status set by computer via the SET CIU STATUS command (IMCPM03 only)
6
ETYPE
29
Enhanced module type: (41) = IMCPM02/03
7
CWA
80
Controlway bus A failure: 0 = good, 1 = fail
CWB
40
Controlway bus B failure: 0 = good, 1 = fail
8
—
00
Reserved
9
NDT1
01
NIS loop relay drive transistor 1 failure
NDT2
01
NIS loop relay drive transistor 2 failure
NCD1
01
NIS receive channel 1 disable
NCD2
01
NIS receive channel 2 disable
10 - 13
—
—
Reserved
14
—
FF
Module nomenclature: (3) = IMCPM02/03
15
—
FF
Revision letter (in ASCII code), for example, (42)16 = B
16
—
FF
Revision number (in ASCII code), for example, (30)16 = 0
Module Status 15 FEB 1995 G - 23
Appendix G
®
CONFIGURATION AND TUNING, AND ANALOG OUTPUT Table G-16. CTT01/02 Configuration and Tuning Terminal, IMAOM01 Analog Output Module, and NCTM01 Configuration and Tuning Module Byte 1
Bit 7
6
ES
5
3
MODE
2-5
2
1
0
TYPE Reserved
Byte
Field
Field Size or Value
1
ES
80
2-5
4
Description Error summary: 0 = good, 1 = errors
MODE
60
Module mode: 01 = fail, 11 = execute
TYPE
1F
Module type code: (2)16 = NCTM01, (12)16 = CTT01/02, (4)16 = IMAOM01
—
00
Reserved
Module Status 15 FEB 1995 G - 24
I-E96-200B