AIR COMFORT AIR DIFFUSSION AIR HEATERS
AIR HEATERS LVDV >> TECHNICAL CATALOGUE
AIR HEATERS - Technical catalogue
LVDV
2
LVDV - CEILING-MOUNTED AIR HEATERS FOR HOT WATER
LVDV ceiling-mounted fans are used for heating entrances, warehouses, industrial premises, workshops, sports halls, garages and shops. Due to its low overall height the LVDV can be built into the ceiling. The fans are designed for 230V~ power supply, which makes the installation very simple. The fans have a low sound level and offer reliable operation. • Three sizes and two models • Available with built-in control equipment for sensor control or for external 0...10V:s control signal • The hinged front panel makes the coil and fan easily accessible for inspection and cleaning • Suspended from the ceiling – leaves the wall surface clear • Low overall height – can be built into the ceiling • Simple 230V~ installation • Two fan speeds as standard Design The casing is made of galvanized sheet steel painted white. The coil has copper tubes and aluminium fins. The ball-bearing mounted fan with overheating protection has a low sound level and offers reliable operation. The front panel is hinged, which makes it easy to open for inspecting the coil and fan. The LVDV is available in two models: LVDV-aa-1 and LVDV-aa-0.
CONTROL Built-in control equipment LVDV-aa-1 Fan heater with built-in control equipment for external sensor and setpoint adjustment. Can also be controlled by an external 0...10V control signal. See pages 4 and 5. External control equipment LVDV-aa-0 Fan heater for external control equipment. Has two fanspeeds. See pages 6 and 7.
Capacity Pages 8 and 9 give examples of capacities for each size. Installation Can be installed directly on the ceiling or suspended from hangers.
APPROVALS The AIR HEATERS are manufactured in accordance with: LVD Directive: EN 60355-1 and EN 60335-2-30 EMC Directive: EN 61000-6-2 and EN 61000-6-3 EMF Directive: EN 62233
Fläkt Woods
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogue
LVDV
3
PRODUCT RANGE OVERVIEW WITH DIMENSIONAL DRAWING Type Power supply
LVDV 51
230V~
230V~
230V~
0.4
0.6
1.0
Air flow rate (low/high speed)
m³/h
700 / 1100
1300 / 2000
2500 / 3900
Sound level
dB
37 / 53
44 / 57
48 / 60
m
2.2 / 4
2.7 / 4.5
4.5 / 7.5
m
4/7
5/8
7 / 12
Connecting pipes
mm dia.
22
22
28
Max. operating water temp., LVDV-aa-1
°C
80°C
80°C
80°C
Max. operating water temp., LVDV-aa-0
°C
80°C
80°C
80°C
Max. operating pressure (water)
bar
10
10
10
Ambient temperature
°C
3-30°C
3-30°C
3-30°C
IPX4
IPX4
IPX4 3)
1)
(low/high speed)
Vertical throw
2)
(low/high speed)
Vertical throw speed)
2)
with LVDVE (low/high
Degree of protection Weight
Fläkt Woods
LVDV 41
A
Current, max.
LVDV 31
kg
3)
19
3)
26
41
Dimensions A mm
B mm
C mm
D mm
E mm
F mm
G mm
H mm
K mm
L mm
LVDV 31
535
640
280
670
705
125
195
330
135
305
LVDV 41
675
760
420
790
825
115
195
355
160
355
LVDV 51
710
1070
480
1100
1135
110
300
415
115
430
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogue
LVDV
4
LVDV-aa-1 FAN HEATER FOR HOT WATER WITH BUILT-IN CONTROL EQUIPMENT FOR FAN AND WATER CONTROL The LVDV-aa-1 with built-in control equipment gives a simple installation due to fewer cable runs, etc. This, in turn, lowers the installation cost and reduces the risk of incorrect connections. The control equipment is suitable for an external temperature sensor and setpoint adjuster or external 0...10V control signal. Model –aa-1 The LVDV-aa-1 has built-in control equipment with electronic thermostat that starts/stops the fan and opens/ shuts off the water flow. The thermostat controls automatically in three steps: Step 1 – Fan runs only at low speed, without hot water. This function puts to use of the warm air stored under the ceiling, which results in efficient energy utilization and saves money. Step 2 – The fan runs at low speed and the hot water valve opens. Step 3 - The fan runs at high speed and the hot water valve opens. Control
Installation The LVDV-aa-1 is mounted directly on the ceiling or on hangers.
The LVDV-aa-1 must be supplemented with an external room sensor and setpoint adjuster. See the next page for examples. The LVDV-a can also be controlled by an external 0...10V control signal. A LVDV-aa-1 with sensor connected can carry out slave control of an unlimited number of LVDV-aa-1 units and/or our wall-mounted type AW-a AIR HEATERS. The slavecontrolled units then need no sensors and receive their control signals from the LVDV-aa-1 with sensor. See next page for sensors. Accessories See next page for sensors suitable for the LVDV-aa-1.
PROJECT DESIGN/ORDERING DESCRIPTIVE TEXT - LVDV-aa-1 Ceiling-mounted fan heater for hot water, Fläkt Woods type LVDV-aa-1, with casing of galvanized sheet steel, painted white. Water coils with copper tubes and aluminium fins. The hinged front panel makes the coil and fan easily accessible for inspection and cleaning. Built-in control equipment for fan and water control. Setpoint adjustment is carried out externally. Accessories such as room sensor, setpoint adjuster, filter and extension duct must be ordered separately.
Fläkt Woods
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogue
LVDV
5
ACCESSORIES Product
Range
Degree of protection
Room sensor LVDZ-04-1 (TG-R430)
Range 0-30°C
IP30
Range 0-30°C
IP30
Range 0-30°C
IP54
With setpoint adjustment.
Room sensor LVDZ-04-2 (TG-R530) Supplemented with LVDZ-04-1 (TG-R430) for setpoint adjustment.
Room sensor LVDZ-04-3 (TG-R630) Supplemented with TG-R430 for setpoint adjustment.
Extension duct LVDZ-02 The duct is used for greater ceiling heights in order to increase the throw. Length: 350 mm. Filter LVDZ-01 Filter for installation in the LVDV
Air deflector LVDZ-03 Aluminium blades. Used for directing the air sideways.
LVDZ-01
LVDV
LVDZ-03
LVDZ-02
Fläkt Woods
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogues
LVDV
6
LVDV-aa-0 FAN HEATER FOR HOT WATER FOR EXTERNAL CONTROL EQUIPMENT The LVDV-aa-0 for external control equipment is the alternative if you require a simple fan heater, but without compromising on quality. Model –aa-0 The LVDV-aa-0 for external control equipment has two fan speeds. The speed can be selected on installation or by external type AWD selector switch. Control The LVDV-aa-0 is supplemented with external room thermostat, speed selector switch, and also actuator and valve. See next page for examples. Accessories See the next page for accessories suitable for the LVDV-aa-0. Installation The LVDV-aa-0 is mounted directly on the ceiling or on hangers.
PROJECT DESIGN/ORDERING DESCRIPTIVE TEXT - LVDV-aa-0 Ceiling-mounted fan heater for hot water, Fläkt Woods type LVDV-aa-0, with casing of galvanized sheet steel, painted white. Water coils with copper tubes and aluminium fins. Fan motor with two speeds. The hinged front panel makes the coil and fan easily accessible for inspection and cleaning. Accessories such as thermostat, speed selector switch, actuator and valve, and also extension duct must be ordered separately.
Fläkt Woods
9807SE 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogues
LVDV
7
ACCESSORIES Product
Range
Actuator and valve LVDZ-05 (AWTV),
Max 90°C, 25 bar.
Degree of protection IP44
IP44 Used together with thermostat TI-N
LVDV 31-41: 4,6 Kvs
or SR 121/1.
LVDV 51: 8,4 Kvs
IP65
Speed selector switch LVDZ-06-1 Can control up to four LVDV-aa-0 units. 0 = shut off 1 = low speed 2 = high speed
Thermostat LVDZ-06-2 (SR121/1)
Range 0-40°C
IP54
Range 5-30°C
IP30
Can control four LVDV-aa-0.
Room thermostat TI-N. Can control up to three LVDV-aa-0 units. Max. load 10 A (3 A) 250V AC.
Extension duct LVDZ-02 LVDZ-02 is used for greater ceiling heights in order to increase the throw. Length: 350 mm. Filter LVDZ-01 Panel filter for installation in the LVDV.
Air deflector LVDZ-03 Aluminium blades. Used for directing the air sideways.
Fläkt Woods
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogue
LVDV
8
Capacity of LVDV 31 Water temp.
in/out 80°C/60°C
in/out 60°C/40°C
Pressure Flow Output drop. Air out of water water
in/out 55°C/45°C
Pressure Flow Output drop. Air out of water water
Output
Flow of water
Pressure drop. water
°C
kW
l/s
kPa
4.5
34.4
5.9
0.14
16.7
0.09
7.6
31.0
8.0
0.19
28.8
4.9
0.06
3.4
36.4
5.1
0.12
12.8
32.6
6.6
0.08
5.8
33.4
6.9
0.17
22.1
6.4
37.4
4.1
0.05
2.5
38.4
4.3
0.10
9.4
11.0
34.9
5.5
0.07
4.1
35.8
5.8
0.14
16.2
Air flow rate
Air in
Air out
m³/h
°C
°C
kW
l/s
kPa
°C
kW
l/s
kPa
700
+10
46.6
8.9
0.11
9.4
33.6
5.7
0.07
1100
+10
41.5
12.0
0.15
16.1
30.2
7.7
700
+ 15
48.7
8.1
0.10
7.8
35.6
1100
+ 15
44.0
10.9
0.13
13.5
700
+ 20
50.8
7.2
0.09
1100
+ 20
46.5
9.8
0.12
Capacity of LVDV 41 Water temp.
in/out 80°C/60°C
Air flow rate
Air in
Air out
m³/h
°C
°C
in/out 60°C/40°C
Pressure Flow Output drop. Air out of water water kW
l/s
kPa
°C
in/out 55°C/45°C
Pressure Flow Output drop. Air out of water water kW
l/s
kPa
°C
Output
Flow of water
Pressure drop. water
kW
l/s
kPa
1300
+10
44.2
15.5
0.19
11.5
32.0
9.9
0.12
5.5
32.8
10.3
0.25
20.5
2000
+10
39.3
20.4
0.25
19.0
28.8
13.0
0.16
8.9
29.6
13.6
0.33
33.9
1300
+ 15
46.5
14.0
0.17
9.6
34.1
8.5
0.10
4.1
35.0
8.9
0.22
15.6
2000
+ 15
42.0
18.4
0.23
15.8
31.3
11.1
0.14
6.7
32.2
11.7
0.28
25.9
1300
+ 20
48.8
12.5
0.15
7.9
36.2
7.1
0.09
3.0
37.2
7.5
0.18
11.5
2000
+ 20
44.6
16.5
0.20
12.9
33.8
9.2
0.11
4.8
34.8
9.9
0.24
19.0
Capacity of LVDV 51 Water temp.
in/out 80°C/60°C
Air flow rate
Air in
Air out
m³/h
°C
°C
kW
Fläkt Woods
in/out 60°C/40°C
Pressure Flow Output drop. Air out of water water l/s
kPa
in/out 55°C/45°C
Pressure Flow Output drop. Air out of water water
°C
kW
l/s
kPa
°C
Output
Flow of water
Pressure drop. water
kW
l/s
kPa
2500
+10
47.4
32.5
0.40
8.3
34.0
20.9
0.25
3.9
34.9
21.7
0.53
14.8
3900
+10
41.7
43.0
0.53
13.8
30.2
27.4
0.33
6.4
31.2
28.7
0.70
24.8
2500
+ 15
49.4
29.4
0.36
6.9
35.9
17.8
0.22
2.9
36.9
18.7
0.45
11.3
3900
+ 15
44.1
38.8
0.48
11.5
32.5
23.3
0.28
4.8
33.6
24.7
0.60
18.9
2500
+ 20
51.4
26.3
0.32
5.7
37.6
14.8
0.18
2.1
38.8
15.7
0.38
8.3
3900
+ 20
46.6
24.7
0.43
9.4
34.8
19.3
0.23
3.4
35.9
20.8
0.50
13.8
9807GB 2015.11.17
Subject to changes.
AIR HEATERS - Technical catalogues
CODES - AIR HEATERS LVDV-aa-b aa (Size) 31 41 51 b (Controls) 0 = Without controls 1 = With controls
ACCESSORIES
LVDZ-01-bb Filter bb (Size) 31 41 51 LVDZ-02-bb Extension connection bb (Size) 31 41 51
Fläkt Woods
9807GB 2015.11.17
LVDV
9
LVDZ-03-bb Air deflector bb (Size) 31 41 51 LVDZ-04-b Room sensor (For LVDV-aa-1) b (Typ) 1 = Room sensor with setpoint adjustment (TG-R430) 2 = Room sensor IP 30 (TG-R530) 3 = Room sensor IP 54 (TG-R630) LVDZ-05-bb Valve and actuator (for LVDV-aa-0) bb (Size) 31 = For size 31/41 (AWTV 12-22) 51 = For size 51 (AWTV 42-62) LVDZ-06-b Controls (for LVDV-aa-0) b = 1 Speed switch IP 65 b = 2 Thermostat IP 54 (SR121/1) b = 3 Thermostat IP 30 (TI-N)
Subject to changes.
Copyright 2015 Fläkt Woods Group ©
FWG-LVDV AIR HEATERS - TECHNICAL CATALOGUE GB-2015.11.17 9807GB
WE BRING BETTER AIR TO LIFE
™
With over a century of innovation and expertise to share with our customers, Fläkt Woods is a global leader in Air Technology products and solutions. We specialize in the design and manufacturing of a wide range of products and solutions for Air Movement, Air Treatment, Air Distribution, Air Management and Air Diffusion with focus on two major benefi ts – Air Comfort and Fire Safety. With market presence in 65 countries we are in a unique position to be a local supplier and an international partner in our customer’s projects. Our product brands such as SEMCO®, eQ®, eQ Prime®, JM Aerofoil®, Econet®, Veloduct®, Optivent®, Econovent® and Cleanvent® are well-known and trusted by customers all over the world to deliver high quality and energy efficient solutions.
» To learn more about our offering and get in contact with your nearest sales representative please visit www.flaktwoods.com
WWW.FLAKTWOODS.COM
AIR HEATERS | 9807GB | 20151117