a Nexans company
Catalogue 2015
Nexans Network Solutions Div. Euromold COMPANY PRESENTATION
EUROMOLD
International standards
Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of coldshrinkable terminations and joints from 12 to 42 kV. Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
All our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country specifications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are continuously performed in our test fields.
ISO 9001 Certificate Since 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
Laboratory accreditation Since June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards EN 50393, IEC 60502-4, IEC 61442 and HD 629.
05/2015
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
1
SEPARABLE CONNECTORS
INTERFACE C
Table of contents
Interface C1 & C2
480TB - tee connector 484TB - tee connector 489TB - tee connector 800PB - coupling connector 804PB - coupling connector 809PB - coupling connector 450SR - straight connector 800SA - surge arrester 430TB - tee connector 300PBM - coupling connector 300SA - surge arrester 400TR and 800TR - test rod 400TK and 400SW installation tools Accessories Possible arrangements T-HSTBK - Three core heat-shrink breakout kit
Dimensions according to European CENELEC EN 50180 and 50181 (in mm).
Dia. 56±0.2 Dia. 46±0.2 Dia. 22 min for C1 Dia. 32 nominal for C2 M16 x 2 - 6H
0
1.5 -0.5
29 min
90±0.2
In mm.
2
Dia. 70±0.2
05/2015
11 min
Connecting possibilities BUSHINGS / ACCESSORIES
CONNECTION
Equipment interface
dead-ending of equipment
CONNECTORS / ACCESSORIES
(K)(M)400DR-B
Dead-end receptacle
(K)(M)400AR-3
Equipment bushing
(K)(M)400AR-4
Equipment bushing
(K)(M)400AR-5
cable to equipment
(K)(M)480TB/G Tee connector
(K)(M)800PBM/G
Coupling connector
Equipment bushing
(K)(M)400AR-6
Equipment bushing
(K)(M)400SFR-B
Equipment bushing
400A-24B
In-air bushing
(K)(M)400SOP-B
cable isolation
(K)(M)804PB/G
(K)(M)484TB/G
Stand-off plug
Coupling connector
Tee connector
400GP-B
cable earthing
Earthing plug
(K)400RTPA
tap-off 630/250A
Reducing tap plug
800SA
(K)(M)400CP-SC
Surge arrester
in-line junction
Connecting plug
For information on bushings please refer to our bushing catalogue.
(K)(M)489TB/G Tee connector
(K)(M)809PB/G
Coupling connector
(K)450SR
05/2015
Straight connector
3
480TB
INTERFACE C TEE CONNECTOR
Application
Technical characteristics
Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Up to 42 kV 630 A -1250 A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV
Design
185 mm
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor contact. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
4
9 8
5
6
1 2
290 mm
3
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
10
Specifications and standards
7
The 480TB separable connector meets the requirements of CENELEC HD 629.1.
4
Voltage Um (kV)
Current Ir (A)
When using a copper (-11-2) or a bolted (14-5) conductor contact and when installed on an appropriate equipment bushing
480TB/G K480TB/G M480TB/G P480TB/G
12 24 36 42
630 630 630 630
1250 1250 1250 1250
Conductor sizes (mm2) min
max
35 35 50 50
300 300 300 240
05/2015
Current Ir (A)
Separable connector type
Kit contents
The kit also comprises silicone grease, field control mastic, installation rod, gloves, wipers, roll adhesive tape, installation instructions and crimp chart.
The complete (K)(M)(P)480TB/G tee connector kit comprises 3 x the following components:
Conductor contact TMBC-X
Example: The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm. Order 3 x K480TB/G-18-95.240-14-5 tee connector kit.
For use with copper tape screened cables.
Order: Kit MT.
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Dia. over core insulation (mm)
Ordering part number
3 x 480TB/G-11-X 3 x 480TB/G-16-X 3 x 480TB/G-18-X 3 x 480TB/G-27-X 3 x 480TB/G-30-X* * will include an adapted installation instruction
min
max
12.0 17.0 19.0 28.5 36.0
17.5 23.5 32.6 37.5 40.5
Table X
Conductor sizes (mm2) 35 50 70 95 120 150 185 240 300
For use with other cable types.
Please contact our representative.
Aluminium conductor DIN hexagonal
Deep indent
35(K)M-10-2 50(K)M-10-2 70(K)M-10-2 95(K)M-10-2 120(K)M-10-2 150(K)M-10-2 185(K)M-10-2 240(K)M-10-2 300(K)M-10-2
35KM-10-1 50(K)M-10-1 70(K)M-10-1 95(K)M-10-1 120(K)M-10-1 150(K)M-10-1 185(K)M-10-1 240(K)M-10-1 –
For applications outdoors and in humid climate.
Order: +MWS.
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal
This product can also be installed using a stud, nut & washer.
Please contact our representative.
120.300-14-5
To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Table W
95.240-14-5
Ordering instructions
Conductor contact TBC-X
Cable reducer 430CA-W
50.150-14-5
Clamping screw 430TCS
Basic insulating plug (K)(M)(P)800BIPA + rubber cap
16.95-14-5
Connector housing (K)(M)(P)480BT/G
3 x (K)(M)(P)480TB/GW-X connector kit
35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2
This product can also be installed using a 411 CA. Please
contact our representative.
5
484TB
INTERFACE C TEE CONNECTOR
Application Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
Up to 42 kV 630 A - 1250 A
Technical characteristics • The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV
Design
185 mm
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Stud+nut+washer. 10. Earthing lead.
4
9 8
5
6
1 2 360 mm
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
3
10
Specifications and standards
7
The 484TB separable connector meets the requirements of CENELEC HD 629.1.
484TB/G K484TB/G M484TB/G P484TB/G
6
Current Ir (A)
Voltage Um (kV)
When installed on an appropriate equipment bushing
min
max
12 24 36 42
1250 1250 1250 1250
50 35 35 35
630 630 630 630
Conductor sizes (mm2)
05/2015
Separable connector type
Kit contents The complete (K)(M)(P)484TB/G tee connector kit comprises 3x the following components:
The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.
Conductor contact TMBC-X
For use with copper tape screened cables.
Order: Kit MT.
For use with copper wire screened cables.
No earthing device is necessary.
Dia. over core insulation (mm)
Ordering part number 3 x 484TB/G-S-15-X 3 x 484TB/G-S-19-X 3 x 484TB/G-S-22-X 3 x 484TB/G-S-27-X 3 x 484TB/G-S-32-X 3 x 484TB/G-S-37-X 3 x 484TB/G-S-43-X
min
max
16.0 20.0 23.5 28.5 34.0 39.0 45.5
22.0 26.5 31.0 37.5 42.5 48.5 56.0
Table X Aluminium conductor DIN hexagonal
Deep indent
35
35(K)M-12-2
35KM-12-1
50
50(K)M-12-2
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120
120(K)M-12-2
120KM-12-1
150
150(K)M-12-2
150KM-12-1
185
185(K)M-12-2
185KM-12-1
240
240(K)M-12-2
240KM-12-1
300
300(K)M-12-2
300KM-12-1
400
400(K)M-12-2
400KM-12-1
500
500(K)M-12-2
500KM-12-1
630
–
630KM-12-1
For use with other cable types.
Please contact our representative.
For applications outdoors and in humid climate.
Order: +MWS.
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal 35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2
Components can be ordered individually.
120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2 400.630-14-5
Conductor sizes (mm2)
185.400-14-5
Example: The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm. Order 3 x M484TB/G-S-32-240(K)M-122 tee connector kit.
Table W
95.240-14-5
To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Cable reducer 611CA-W
120.300-14-5
Ordering instructions
Conductor contact TBC-X
50.150-14-5
Stud+nut +washer
Basic insulating plug (K)(M)(P)800BIPA + rubber cap
16.95-14-5
Connector housing (K)(M)(P)484BT/G
(K)(M)(P)484TB/G-SW-X connector kit
400(K)M-11-2 500(K)M-11-2 630(K)M-11-2
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
7
489TB
INTERFACE C TEE CONNECTOR
Application Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
Up to 42 kV 630 A - 1250 A
Technical characteristics • The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV 185 mm
Design
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Stud+nut+washer. 10. Earthing lead.
4
9 8
5
6
1 2 3 460 mm
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
10 7
Specifications and standards The 489TB separable connector meets the requirements of CENELEC HD 629.1.
489TB/G K489TB/G M489TB/G P489TB/G
8
Current Ir (A)
Voltage Um (kV)
When installed on an appropriate equipment bushing
min
max
12 24 36 42
1250 1250 1250 1250
630 630 630 630
1200 1200 1200 1200
Conductor sizes (mm2)
05/2015
Separable connector type
Kit contents The complete (K)(M)(P)489TB/G tee connector kit comprises 3x the following components:
The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.
Conductor contact TMBC-X (K)(M)(P)489TB/G-S-W-X connector kit
Connector housing (K)(M)(P)489BT/G
Stud+nut +washer
Ordering instructions
Conductor contact TBC-X
For use with copper tape screened cables.
Order: Kit MT.
For use with copper wire screened cables.
No earthing device is necessary.
Cable reducer 911CA-W
Table W
To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV. Example: The copper wire screened cable is 36 kV, 1000 mm2 stranded aluminium with a diameter over core insulation of 52 mm. Order 3 x M489TB/G-S-43-1000(K) M-12-1 tee connector kit.
Basic insulating plug (K)(M)(P)800BIPA + rubber cap
Ordering part number
Dia. over core insulation (mm) min
max
40 46 53 56 59 62
48 54 59 62 65 68
3 x 489TB/G-S-37-X 3 x 489TB/G-S-43-X 3 x 489TB/G-S-50-X 3 x 489TB/G-S-53-X 3 x 489TB/G-S-56-X 3 x 489TB/G-S-59-X
Table X Conductor sizes (mm2)
Aluminium conductor
Aluminium and copper conductor
Copper conductor
Deep indent
Bolted
DIN hexagonal
630
630KM-12-1
400.630-14-5
630(K)M-11-2
800
800KM-12-1
1000
1000KM-12-1
1200
1200KM-12-1
For use with other cable types.
Please contact our representative.
For applications outdoors and in humid climate.
Order: +MWS.
800.1000-14-5 1200-14-5
Components can be ordered individually.
800(K)M-11-2 1000(K)M-11-2 -
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
9
800PB
COUPLING CONNECTOR FOR 480TB, 484TB and 489TB
Application
Technical characteristics
Separable coupling connector for dual cable arrangement. It has been designed to be used with 480TB, 484TB and 489TB separable tee connectors. Can also be installed on any 8-series coupling connector for a multiple cable arrangement.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Design
Up to 42 kV 630A - 1250 A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV
290 mm
1. Interface designed to fit 480TB, 484TB and 489TB connectors. 2. Contact rod. 3. Conductor contact. 4. Conductive EPDM insert. 5. Conductive EPDM jacket. 6. Insulating EPDM layer moulded between the insert and the jacket. 7. Cable reducer. 8. Conductive EPDM cap. 9. Basic insulating plug (with VD point). 10. Earthing lead. The screen break design enables cable outer sheath testing without removing or dismantling the connector.
2 1
8 9
3 4
290 mm
6
480TB, 484TB or 489TB connector
800PB coupling connector
5
10 7
Specifications and standards The 800PB coupling connector meets the requirements of CENELEC HD 629.1.
10
110 mm
Voltage Um (kV)
Current Ir (A)
800PB/G K800PB/G M800PB/G P800PB/G
12 24 36 42
630 630 630 630
Current Ir (A)
When using a copper (-11-2) or a bolted (14-5) conductor contact and when installed on an appropriate equipment bushing
1250 1250 1250 1250
Conductor sizes (mm2) min
max
35 35 50 50
300 300 300 240
05/2015
Separable connector type
Kit contents The complete (K)(M)(P) 800PB/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, gloves, wipers, roll adhesive tape, installation instructions and crimp chart.
Conductor contact TMBC-X
3 x (K)(M)(P)800PBM/G-SW-X coupling connector kit Cable reducer 430CA-W
Order: Kit MT.
For use with copper wire screened cables.
No earthing device is necessary.
Dia. over core insulation (mm)
Ordering part number
3 x 800PB/G-S-11-X 3 x 800PB/G-S-16-X 3 x 800PB/G-S-18-X 3 x 800PB/G-S-27-X 3 x 800PB/G-S-30-X* * will include an adapted installation instruction
min
max
12.0 17.0 19.0 28.5 36.0
17.5 23.5 32.6 37.5 40.5
Table X
35 50 70 95 120 150 185 240 300
For use with other cable types.
Please contact our representative.
Aluminium conductor DIN hexagonal
Deep indent
35(K)M-10-2 50(K)M-10-2 70(K)M-10-2 95(K)M-10-2 120(K)M-10-2 150(K)M-10-2 185(K)M-10-2 240(K)M-10-2 300(K)M-10-2
35KM-10-1 50(K)M-10-1 70(K)M-10-1 95(K)M-10-1 120(K)M-10-1 150(K)M-10-1 185(K)M-10-1 240(K)M-10-1 –
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal
For outdoor applications.
Order: +MWS.
120.300-14-5
Conductor sizes (mm2)
95.240-14-5
Example: The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm. Order 3 x K800PB/ G-S-18-95.240-14-5 coupling connector kit.
Table W
50.150-14-5
Ordering instructions To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
For use with copper tape screened cables.
Conductor contact TBC-X
Contact rod and stud
16.95-14-5
Connector housing (K)(M)(P)800BP/G
35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2
This product can also be installed using a 411 CA. Please
contact our representative.
11
804PB
COUPLING CONNECTOR FOR 480TB, 484TB AND 489TB
Application
Technical characteristics
Separable coupling connector for dual cable arrangement. It has been designed to be used with 480TB, 484TB and 489TB separable tee connectors. Can also be installed on any 8-series coupling connector for a multiple cable arrangement.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Design
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV 290 mm
2
1
5 360 mm
6
480TB, 484TB or 489TB connector
10
7
The 804PB coupling connector meets the requirements of CENELEC HD 629.1.
804PB/G K804PB/G M804PB/G P804PB/G
12
9
4
Specifications and standards
Separable connector type
8
3
110 mm
Voltage Um (kV)
Current Ir (A)
12 24 36 42
1250 1250 1250 1250
Conductor sizes (mm2) min
max
50 35 35 35
630 630 630 630
05/2015
1. Interface designed to fit 480TB, 484TB and 489TB connector. 2. Bus for 804PB. 3. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 4. Conductive EPDM insert. 5. Conductive EPDM jacket. 6. Insulating EPDM layer moulded between the insert and the jacket. 7. Cable reducer. 8. Conductive EPDM cap. 9. Basic insulating plug (with VD point). 10. Earth lead.
Up to 42 kV 1250 A
Kit contents The complete (K)(M)(P)804PB/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.
Conductor contact TMBC-X
Contact rod and stud
For use with copper tape screened cables.
Order: Kit MT.
For use with copper wire screened cables.
No earthing device is necessary.
Dia. over core insulation (mm)
Ordering part number 3 x 804PB/G-S-15-X 3 x 804PB/G-S-19-X 3 x 804PB/G-S-22-X 3 x 804PB/G-S-27-X 3 x 804PB/G-S-32-X 3 x 804PB/G-S-37-X 3 x 804PB/G-S-43-X
min
max
16.0 20.0 23.5 28.5 34.0 39.0 45.5
22.0 26.5 31.0 37.5 42.5 48.5 56.0
Table X
Deep indent
35
35(K)M-12-2
35KM-12-1
50
50(K)M-12-2
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120
120(K)M-12-2
120KM-12-1
150
150(K)M-12-2
150KM-12-1
185
185(K)M-12-2
185KM-12-1
240
240(K)M-12-2
240KM-12-1
300
300(K)M-12-2
300KM-12-1
400
400(K)M-12-2
400KM-12-1
500
500(K)M-12-2
500KM-12-1
630
–
630KM-12-1
For use with other cable types.
Please contact our representative.
For applications outdoors and in humid climate.
Order: +MWS.
Copper conductor
Bolted
DIN hexagonal 35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2
Components can be ordered individually.
150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2 400.630-14-5
DIN hexagonal
Aluminium and copper conductor
120.300-14-5
Aluminium conductor
Conductor sizes (mm2)
185.400-14-5
Example: The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm. Order 3 x M804PB/G-S32-240(K)M-12-2 coupling connector kit.
Table W
50.150-14-5
To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Cable reducer 611CA-W
95.240-14-5
Ordering instructions
Conductor contact TBC-X
16.95-14-5
Connector housing (K)(M)(P)804BP/G
3 x (K)(M)(P)804PB/G-SW-X coupling connector kit
400(K)M-11-2 500(K)M-11-2 630(K)M-11-2
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
13
809PB
COUPLING CONNECTOR FOR 480TB, 484TB AND 489TB
Application
Technical characteristics
Separable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 480TB, 484TB and 489TB separable tee connectors. Can also be installed on any 8-series coupling connector for a multiple cable arrangement.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Design 1. Interface designed to fit 480TB, 484TB and 489TB connector. 2. Bus for 809PB. 3. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 4. Conductive EPDM insert. 5. Conductive EPDM jacket. 6. Insulating EPDM layer moulded between the insert and the jacket. 7. Cable reducer. 8. Conductive EPDM cap. 9. Basic insulating plug (with VD point). 10. Earth lead.
Up to 42 kV 1250 A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV
300 mm
2
8
3
9
4
1
5 6 480TB, 484TB or 489TB connector
460 mm
10
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
7
Specifications and standards The 809PB coupling connector meets the requirements of CENELEC HD 629.1.
809PB/G K809PB/G M809PB/G P809PB/G
14
Voltage Um (kV)
Current Ir (A)
12 24 36 42
1250 1250 1250 1250
Conductor sizes (mm2) min
max
630 630 630 630
1200 1200 1200 1200
05/2015
Separable connector type
120 mm
Kit contents The complete (K)(M)(P)809PB/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.
Conductor contact TMBC-X
Connector housing (K)(M)(P)809BP/G
Ordering instructions To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Example: The copper wire screened cable is 36 kV, 1000 mm2 stranded aluminium with a diameter over core insulation of 52 mm. Order 3 x M809PB/G-S-431000(K)M-12-1 coupling connector kit.
For use with copper tape screened cables.
Order: Kit MT.
Conductor contact TBC-X
Contact rod and stud
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
3 x (K)(M)(P)809PB/G-S-W-X coupling connector kit
Cable reducer 911CA-W
Table W Ordering part number 3 x 809PB/G-S-37-X 3 x 809PB/G-S-43-X 3 x 809PB/G-S-50-X 3 x 809PB/G-S-53-X 3 x 809PB/G-S-56-X 3 x 809PB/G-S-59-X
Dia. over core insulation (mm) min
max
40 46 53 56 59 62
48 54 59 62 65 68
Table X
Conductor sizes (mm2)
Aluminium conductor
Aluminium and copper conductor
Copper conductor
Deep indent
Bolted
DIN hexagonal
630
630KM-12-1
400.630-14-5
630(K)M-11-2
800
800KM-12-1
1000
1000KM-12-1
1200
1200KM-12-1
For use with Alupe or C 33-226 cables.
Please contact our representative.
For use with other cable types.
Please contact our representative.
800.1000-14-5 1200-14-5
For applications outdoors and in humid climate.
800(K)M-11-2 1000(K)M-11-2 -
Components can be ordered individually.
Order: +MWS.
15
450SR
INTERFACE C STRAIGHT CONNECTOR
Application
Technical characteristics
Separable straight connector designed to connect polymeric insulated cable to equipment (transformers, switch gear, motors...).
• The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Up to 24 kV - 630A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV
Design Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector assembly. 6. Retaining ring. 7. Cable reducer.
4
1 2 380 mm
5 6 3 7
Specifications and standards The separable connector 450SR meets the requirements of CENELEC HD 629.1 S1. Dia. 78 mm
16
Separable connector type
Voltage Um (kV)
Current Ir (A)
min.
max.
450SR K450SR
12 24
630 630
50 25
300 300
05/2015
Conductor size (mm2)
Kit contents The complete (K)450SR straight connector kit comprises the following components:
The kit also comprises lubricant, wipers, installation instructions and crimp chart.
Type 1
+
+
+
+
or
+
=
(K)450SR-W-X+11TL connector kit
Type 2
Connector housing (K)450SRH
Locking disc 450SRD
Retaining ring + hex key 400RR-X
Ordering instructions
Contact assembly 450SRC-X-Assy
Cable reducer 450CA-W
Cable adaptor 11TL
Table W
To order the straight connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV.
Dia. over core insulation (mm)
Ordering part number 450SR-06-X+11TL 450SR-08-X+11TL 450SR-10-X+11TL 450SR-12-X+11TL 450SR-14-X+11TL
min.
max.
16.5 19.9 23.2 26.1 30.0
21.5 24.4 28.0 31.0 36.1
Table X Conductor size (mm2)
Example: The copper wire screened cables are 24 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 32.2 mm. Order 3 x K450SR-14-240KM12-2+11TL straight connector kit.
For use with copper tape screened cables.
Order: Kit MT.
For use with Alupe or C 33-226 cables.
Please contact our representative.
25 35 50 70 95 120 150 185 240 300
For use with fabric tape (graphite) screened cables.
Order additional semi-conductive tape (type TSC).
Conductor contact type (DIN standards only) Type 1
Type 2
Aluminium
Copper
Aluminium
–
25KM-11-2 35KM-11-2 50KM-11-2 70KM-11-2 95KM-11-2 120KM-11-2 150KM-11-2 185KM-11-2 240KM-11-2 300KM-11-2
–
–
35KM-12-2-L 50KM-12-2-L 70KM-12-2-L 95KM-12-2-L 120KM-12-2-L – – – –
35KM-11-2-L 50KM-11-2-L 70KM-11-2-L 95KM-11-2-L 120KM-11-2-L – – – –
35KM-12-2 50KM-12-2 70KM-12-2 95KM-12-2 120KM-12-2 150KM-12-2 185KM-12-2 240KM-12-2 300KM-12-2
For use with other cable types.
Please contact our representative.
For outdoor applications.
Order: +MWS.
Copper
Components can be ordered individually.
17
800SA
SURGE ARRESTER FOR 480TB, 484TB AND 489TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to protect 12, 24, 36 and 42 kV class components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching. It has been designed to be used with the 480TB, 484TB and 489TB separable tee connectors.
• This surge arrester is a metal oxide varistor surge arrester in an elbow configuration. • Each arrester is tested for AC withstand, partial discharge and critical voltage prior to leaving the factory.
Design
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV 170 mm 105 mm
Surge arrester comprising: 1. Interface designed to fit the 484TB and 489TB tee connector. 2. Conductive EPDM insert. 3. Conductive EPDM jacket. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Receptacle for contact rod. 6. Metal oxide valve elements. 7. Steel cap. 8. Earth connection. 9. Earth lead.
Dia. 75 mm
1
5 2 L2 L1
3
9
4 6 Dia. 65 mm
Specifications and standards
7
The 800SA surge arresters meet the test requirements of IEC 60099-4.
18
Up to 42 kV
8
Surge arrester type
Nominal discharge current In (kA)
Rated voltage Ur (kV)
Max. continuous operating voltage Uc (kV)
L1
L2
800SA-10-6N 800SA-10-9N 800SA-10-12N 800SA-10-15N 800SA-10-18N 800SA-10-22N 800SA-10-24N 800SA-10-30N 800SA-10-33N 800SA-10-36N 800SA-10-45N 800SA-10-51N
10 10 10 10 10 10 10 10 10 10 10 10
6 9 12 15 18 22 24 30 33 36 45 51
4.8 7.2 9.6 12.0 14.4 17.6 19.2 24.0 26.4 28.8 36.0 40.8
270 270 270 270 270 270 370 370 370 370 470 470
310 310 310 310 310 310 410 410 410 410 510 510
05/2015
Dimensions (mm)
Typical application and dimensions
Ordering instructions To order the surge arrester, specify the surge arrester type, as described on previous page.
290 mm 180 mm
Example: For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA. Order a 800SA-10-30N surge arrester.
110 mm
Type 800SA surge arrester
Type 484TB tee connector
For use in potentially explosive atmospheres (for 12 kV max).
Note: the surge arrester body needs to be positioned vertically after installation.
Add -/ATEX to part number.
Technical data Surge arrester type
Steep current residual voltage @ 10 kA [1/20 µs] (kV)
800SA-10-6N 800SA-10-9N 800SA-10-12N 800SA-10-15N 800SA-10-18N 800SA-10-22N 800SA-10-24N 800SA-10-30N 800SA-10-33N 800SA-10-36N 800SA-10-45N 800SA-10-51N
20.4 28.5 38.0 48.1 58.1 70.1 77.0 97.0 103.4 115.9 144.1 166.0
Lightning current residual voltage [8/20 µs] (kV)
Switching impulse residual voltage [36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
16.8 23.5 31.4 39.7 48.0 57.9 63.6 80.1 85.4 95.7 119.0 137.1
18.3 25.6 34.2 43.2 52.2 63.0 69.2 87.2 93.0 104.2 129.5 149.2
20.5 28.7 38.3 48.4 58.5 70.6 77.6 97.7 104.2 116.8 145.1 167.2
12.9 18.0 24.1 30.5 36.8 44.4 48.8 61.5 65.6 73.5 91.3 105.2
13.7 19.2 25.7 32.5 39.2 47.3 52.0 65.5 69.9 78.3 97.3 112.1
High current impulse withstand (kA) 100 100 100 100 100 100 100 100 100 100 100 100
19
430TB
INTERFACE C TEE CONNECTOR
Application
Technical characteristics
Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Up to 36 kV 630 A -1250 A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV
Design
185 mm
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
4
9
8
5
6
1 2
290 mm
3
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
10
7
Specifications and standards The 430TB separable connector meets the requirements of CENELEC HD 629.1.
20
Voltage Um (kV)
Current Ir (A)
When using a copper (-11-2) or a bolted (14-5) conductor contact and when installed on an appropriate equipment bushing
430TB/G K430TB/G M430TB/G
12 24 36
630 630 630
1250 1250 1250
Conductor sizes (mm2) min
max
35 35 50
300 300 300
05/2015
Current Ir (A)
Separable connector type
Kit contents
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
The complete (K)(M)430TB/G tee connector kit comprises 3 x the following components:
Conductor contact TMBC-X
Connector housing (K)(M)430BT/G
Clamping screw 430TCS
Ordering instructions To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV.
3 x (K)(M)430TB/G-W-X connector kit Basic insulating plug (K)(M)300BIPA + rubber cap
Conductor contact TBC-X
Cable reducer 430CA-W
Table W Dia. over core insulation (mm)
Ordering part number 3 x 430TB/G-11-X 3 x 430TB/G-16-X 3 x 430TB/G-18-X 3 x 430TB/G-27-X 3 x 430TB/G-30-X*
min
max
12.0 17.0 19.0 28.5 36.0
17.5 23.5 32.6 37.5 40.5
* will include an adapted installation instruction
Table X
For use with copper tape screened cables.
Order: Kit MT.
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
35(K)M-10-2 50(K)M-10-2 70(K)M-10-2 95(K)M-10-2 120(K)M-10-2 150(K)M-10-2 185(K)M-10-2 240(K)M-10-2 300(K)M-10-2
35KM-10-1 50(K)M-10-1 70(K)M-10-1 95(K)M-10-1 120(K)M-10-1 150(K)M-10-1 185(K)M-10-1 240(K)M-10-1 –
Up to 24 kV this product can also be installed using a 300BIPR (without VD point) Order: BIPR.
For use with other cable types.
Please contact our representative.
Bolted
DIN hexagonal
For applications outdoors and in humid climate.
Order: +MWS.
120.300-14-5
Deep indent
Copper conductor
95.240-14-5
35 50 70 95 120 150 185 240 300
DIN hexagonal
Aluminium and copper conductor
50.150-14-5
Aluminium conductor
Conductor sizes (mm2)
16.95-14-5
Example: The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm. Order 3 x K430TB/G-18-95.240-14-5 tee connector kit.
35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2
This product can also be installed using a 411 CA. Please
contact our representative.
21
300PBM
COUPLING CONNECTOR FOR 430TB
Application
Technical characteristics
Separable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 430TB separable tee connector.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Up to 36 kV 800 A
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV
290 mm
Design 1. Interface designed to fit 430TB connector. 2. Bus for 300PBM. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug (with VD point). 8. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 9. Cable reducer. 290 mm 10. Earthing lead. The screen break design enables cable outer sheath testing without removing or dismantling the connector.
2 6
1
8
7
3
4 430TB connector
300PBM coupling connector
5
10
Specifications and standards
9
The 300PBM coupling connector meets the requirements of CENELEC HD 629.1.
22
105 mm Voltage Um (kV)
Current Ir (A)
300PBM/G K300PBM/G M300PBM/G
12 24 36
800 800 800
Conductor sizes (mm2) min
max
35 35 50
300 300 240
05/2015
Separable connector type
Kit contents The complete (K)(M)300PBM/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
Conductor contact TMBC-X
3 x (K)(M)300PBM/G-W-X coupling connector kit Cable reducer 430CA-W
Contact rod 300PB-CR
For use with copper tape screened cables.
Order: Kit MT.
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Dia. over core insulation (mm)
Ordering part number 3 x 300PBM/G-11-X 3 x 300PBM/G-16-X 3 x 300PBM/G-18-X 3 x 300PBM/G-27-X 3 x 300PBM/G-30-X*
min
max
12.0 17.0 19.0 28.5 36.0
17.5 23.5 32.6 37.5 40.5
* will include an adapted installation instruction
Table X
35 50 70 95 120 150 185 240 300
For use with copper wire screened cables.
No earthing device is necessary.
Aluminium conductor DIN hexagonal
Deep indent
35(K)M-10-2 50(K)M-10-2 70(K)M-10-2 95(K)M-10-2 120(K)M-10-2 150(K)M-10-2 185(K)M-10-2 240(K)M-10-2 300(K)M-10-2
35KM-10-1 50(K)M-10-1 70(K)M-10-1 95(K)M-10-1 120(K)M-10-1 150(K)M-10-1 185(K)M-10-1 240(K)M-10-1 –
For use with other cable types.
Please contact our representative.
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal
For outdoor applications.
Order: +MWS.
120.300-14-5
Conductor sizes (mm2)
95.240-14-5
Example: The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm. Order 3 x K300PBM/G-18-95.240-14-5 coupling connector kit.
Table W
50.150-14-5
Ordering instructions To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV.
Conductor contact TBC-X
16.95-14-5
Connector housing (K)(M)300BP/G
35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2
This product can also be installed using a 411 CA. Please
contact our representative.
23
300SA
SURGE ARRESTER FOR 430TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to protect 12, 24 and 36 kV class components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching. It has been designed to be used with the 430TB separable tee connector.
• This surge arrester is a metal oxide varistor surge arrester in an elbow configuration. • Each arrester is tested for AC withstand, partial discharge and critical voltage prior to leaving the factory.
Up to 36 kV
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 170 mm
Design
105 mm
Surge arrester comprising: 1. Interface designed to fit the 430TB tee connector. 2. Conductive EPDM insert. 3. Conductive EPDM jacket. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Receptacle for contact rod. 6. Metal oxide valve elements. 7. Steel cap. 8. Earth connection. 9. Earth lead.
Dia. 75 mm
1
5 2 3
L2 L1
9
4 6
Specifications and standards
Dia. 65 mm
7
The 300SA surge arresters meet the test requirements of IEC 60099-4.
24
8
Surge arrester type
Nominal discharge current In (kA)
Rated voltage Ur (kV)
Max. continuous operating voltage Uc (kV)
L1
L2
300SA-10-6N 300SA-10-9N 300SA-10-12N 300SA-10-15N 300SA-10-18N 300SA-10-22N 300SA-10-24N 300SA-10-30N 300SA-10-33N 300SA-10-36N 300SA-10-45N 300SA-10-51N
10 10 10 10 10 10 10 10 10 10 10 10
6 9 12 15 18 22 24 30 33 36 45 51
4.8 7.2 9.6 12.0 14.4 17.6 19.2 24.0 26.4 28.8 36.0 40.8
270 270 270 270 270 270 370 370 370 370 470 470
310 310 310 310 310 310 410 410 410 410 510 510
05/2015
Dimensions (mm)
Typical application and dimensions
Ordering instructions To order the surge arrester, specify the surge arrester type, as described on previous page.
290 mm 180 mm
Example: For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA. Order a 300SA-10-30N surge arrester.
107 mm
Type 300SA surge arrester Type 430TB tee connector
Note: the surge arrester body needs to be positioned vertically after installation. For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Technical data Surge arrester type
Steep current residual voltage @ 10 kA [1/20 µs] (kV)
300SA-10-6N 300SA-10-9N 300SA-10-12N 300SA-10-15N 300SA-10-18N 300SA-10-22N 300SA-10-24N 300SA-10-30N 300SA-10-33N 300SA-10-36N 300SA-10-45N 300SA-10-51N
20.4 28.5 38.0 48.1 58.1 70.1 77.0 97.0 103.4 115.9 144.1 166.0
Lightning current residual voltage [8/20 µs] (kV)
Switching impulse residual voltage [36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
16.8 23.5 31.4 39.7 48.0 57.9 63.6 80.1 85.4 95.7 119.0 137.1
18.3 25.6 34.2 43.2 52.2 63.0 69.2 87.2 93.0 104.2 129.5 149.2
20.5 28.7 38.3 48.4 58.5 70.6 77.6 97.7 104.2 116.8 145.1 167.2
12.9 18.0 24.1 30.5 36.8 44.4 48.8 61.5 65.6 73.5 91.3 105.2
13.7 19.2 25.7 32.5 39.2 47.3 52.0 65.5 69.9 78.3 97.3 112.1
High current impulse withstand (kA) 100 100 100 100 100 100 100 100 100 100 100 100
25
400TR and 800TR
INTERFACE C TEST RODS
Application • The test rod can be used for: - cable fault location - cable testing - phasing checks, etc. • Connections may be made with a cable lug, a 4 mm plug or spring clips.
Technical characteristics • The 400TR test rod can be used with 430TB connectors. • The 800TR is for use with the 480TB, 484TB and 489TB.
400TR
Design
800TR
1. Insulating shroud. 2. Threaded rod for test connection. 3. Two nuts M12. 4. Insulation. 5. Copper test rod stem. An insulating shroud is provided to allow the application of test voltages when bushings are closely spaced.
1 2 3
M12
2 40
3 480
Installation The test rod is mounted on to the clamping screw in the type C interface tee and coupling connectors. The test cable is connected to the threaded stem and the insulating shroud moved to its final position over the end of the test rod.
1
M12
480
321,5
4
288
4 5
5
Ordering instructions Simply specify: 400TR or 800TR test rod.
26
Test rod type
Maximum A.C. test voltage (50 Hz - 1 min)
Maximum D.C. test voltage (8 x U0 - 30 min)
Impulse voltage (1.2 x 50 µs) min
400TR 800TR
36 kV 36 kV
96 kV 96 kV
95 kV 95 kV
05/2015
In mm.
400TK and 400SW
INSTALLATION TOOL
Application
• The 400SW box spanner key fits on the hex nut of the 400BIPA basic insulating plug.
• The box spanner and box spanner key are designed to facilitate assembly of 400TE, 400TB and 440TB connectors. • The 400TK box spanner is used to install the 400TEF clamping pin contact or 400TCS clamping screw.
400SW 400TK
Ordering instructions
05/2015
Simply specify: - 400TK box spanner - 400SW box spanner key.
27
ACCESSORIES INTERFACE C
Application For use with connectors and bushings with an interface C as described by CENELEC EN 50180 and 50181.
400DR-B/G Dead-end receptacle Fits over a bushing with a type C interface to provide 'deadend' facility. The dead-end receptacle is supplied with an earth lead.
400SOP-B Stand-off plug Is designed to support and 'dead-end' connectors with a type C interface when removed from equipment.
400GP-B Earthing plug Is designed to support and earth connectors with a type C interface when removed from equipment.
Technical characteristics All these products, except the earthing plugs, are tested for AC withstand and partial discharge prior to leaving the factory.
Up to 42kV
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV Ordering instructions Order 400DR-B/G for 12 kV, K400DR-B/G for 24 kV or M400DR-B/G for 36 kV applications.
Ordering instructions Order 400SOP-B for 12 kV, K400SOP-B for 24 kV, M400SOP-B for 36 kV or P400SOP-B for 42 kV applications.
Ordering instructions Order 400GP-B for 12, 24, 36 or 42 kV applications.
05/2015
Order 400GP-SBT for a version with a straight bolt terminal.
28
800GP-B Earthing plug Is designed to earth the 484TB and 804PB connectors when it is fixed-mounted to the equipment (maintenance earthing).
400BIPA Basic insulating plug Acts as a tightening nut for the 400TB and 440TB tee connector kits. The plug contains a voltage detection point. The conductive rubber protection cap is included.
Kit MT Earthing kit for copper tape screened cables Contains a tinned copper braid (25 mm² - L = 500 mm), a tinned copper wire for cleating and some water sealing mastic.
400BE/G Bushing extender Provides an extension piece to allow cables to stand away from equipment. Is used in conjunction with the 400CP, 440CP or 440PB. The bushing extender is supplied with an earth lead.
480BE/G Bushing extender Provides an extension piece to allow cables to stand away from equipment. Is used in conjunction with the 800PB, 804PB or 809PB. The bushing extender is supplied with an earth lead.
Ordering instructions Order 800GP-B for 12, 24, 36 or 42 kV applications. Order 800GP-SBT for a version with a straight ball terminal.
Ordering instructions Order 400BIPA for 12 kV, K400BIPA for 24 kV M400BIPA for 36 kV or P400BIPA for 42 kV applications.
Ordering instructions Order Kit MT for 12 kV, 24 kV, 36 kV or 42 kV applications.
Ordering instructions Order 400BE/G for 12 kV, K400BE/G for 24 kV, M400BE/G for 36 kV or P400BE/G for 42 kV applications.
Ordering instructions Order 480BE/G for 12 kV, K480BE/G for 24 kV, M480BE/G for 36 kV or P480BE/G for 42 kV applications.
29
POSSIBLE ARRANGEMENTS
INTERFACE C
480TB
480TB-P2
Single cable arrangement. Order 480TB for 12 kV, K480TB for 24 kV, M480TB for 36 kV or P480TB for 42 kV applications.
Dual cable arrangement. Order 480TB-P2 for 12 kV, K480TB-P2 for 24 kV, M480TB-P2 for 36 kV or P480TB-P2 for 42 kV applications.
185 800BIPA basic insulating plug
800BIPA basic insulating plug
480TB tee connector
800PBM coupling connector 480TB tee connector
110
480TB-P3
480TB-L3
Triple cable arrangement. Order 480TB-P3 for 12 kV, K480TB-P3 for 24 kV, M480TB-P3 for 36 kV or P480TB for 42 kV applications.
3-way connection. Order 480TB-L3 for 12 kV, K480TBM-L3 for 24 kV, M480TBM-L3 for 36 kV or P480TB for 42 kV applications. 425
395 800BIPA basic insulating plug
480TB tee connector
400BIPA basic insulating plug
800PBM coupling connector 480TB tee connector
In mm.
30
05/2015
800PBM coupling connector
800BIPA basic insulating plug
484TB
484TB-P2
Single cable arrangement. Order 484TB for 12 kV, K484TB for 24 kV, M484TB for 36 kV or P484TB for 42 kV applications.
Dual cable arrangement. Order 484TB-P2 for 12 kV, K484TB-P2 for 24 kV or M484TB-P2 for 36 kV or P484TB-P2 for 42kV applications.
185
290 800BIPA basic insulating plug
800BIPA basic insulating plug
484TB tee connector
804PB coupling connector
484TB tee connector
110
110
110
484TB-P2 + 800SA
400BE+480TB
Dual cable arrangement with surge arrester. Order 484TB-P2+800SA for 12 kV, K484TB-P2+800SA for 24 kV, M484TB-P2+800SA for 36 kV or P484TB-P2+800SA for 42 kV applications.
Order 400BE+480TB for 12 kV, K400BE+480TB for 24 kV or M400BE+480TB for 36 kV applications.
400
435 800BIPA basic insulating plug
440CP 800SA surge arrester
400BE bushing extender
800BIPA basic insulating plug 480TB tee connector
804PB coupling connector 110
110
484TB tee connector
In mm.
31
489TB
489TB-P2
Single cable arrangement. Order 489TB for 12 kV, K489TB for 24 kV, M489TB for 36 kV or P484TB for 42 kV applications.
Dual cable arrangement. Order 489TB-P2 for 12 kV, K489TB-P2 for 24 kV or M489TB-P2 for 36 kV or P489TB-P2 for 42kV applications.
185
300
800BIPA basic insulating plug
800BIPA basic insulating plug 489TB tee connector
809PB coupling connector
110
110
120
489TB tee connector
480BE+800PB Single cable arrangement. Order 480BE+800PB for 12 kV, K480BE+800PB for 24 kV, M480BE+800PB for 36 kV or P480BE+800PB for 42 kV applications. 300
480BE bushing extender
800PB coupling connector
In mm.
32
Earthing plug on connector Order 800GP-B for 12 kV, 24 kV and 36 kV applications.
800GP-B earthing plug
484TB tee connector
Cable and equipment testing
800TR test rod
insulating shroud
484TB tee connector
110
In mm.
33
T-HSBK
THREE CORE HEAT-SHRINK BREAKOUT KIT
Application
Technical characteristics
For sealing of three core polymeric insulated cable crutches and earthing of the metallic screens and armour. For use with Euromold separable connectors with ground lead (/G) or with terminations.
The installed breakout fullfills the requirements of IP54. The armouring and screen connection systems have short circuit rating (Isc) of up to 5,1 kA/1s.
Design The three core heat-shrink breakout kit consists of (depending on cable type): a heat-shrinkable breakout, 3 sleeves of 500 mm, earth braid and roll springs, hose clamp, water sealing mastic and installation instructions.
For tail lengths up to 700 mm
Ordering instructions To order the 3-core kit, select the part number, which gives you the best centering over the cable core insulation diameter and substitute X using table X, according to your cable type.
Ordering part number T-HSBK-20-X T-HSBK-30-X T-HSBK-40-X T-HSBK-50-X
Typical use Conductor sizes (mm²) 36 kV 12, 17 & 24 kV 16-95 95-240 185-400 -
Diameter over Diameter core isolation over armour (mm) (mm)
16-95 95-240 185-400
12-23 19-31 24-35 32-40
50-70 60-80 70-90 80-100
34
X depending on cable type
X
Unarmoured, individual copper tape screen Unarmoured, individual copper wire screen Unarmoured, common copper wire screen Armoured, individual copper tape or wire screen Armoured, common copper wire screen
DR1K DR2K DR3K DR1F/DR2F DR3F
05/2015
Table X
05/2015
NOTES
35
36
05/2015
Additional catalogue information on power cable accessories is available by contacting us at the address below:
Distributed by:
Nexans Network Solutions N.V. - Div. Euromold Zuid III, Industrielaan 12, B-9320 Erembodegem Tel.: +32 (0)53 85 02 11 •
[email protected] • www.euromold.be Catalogue also available on CD-ROM, Website and Mobile Apps
05/2015
a Nexans company