S.1
S.2
21' - 8 7/16"
36' - 0 3/8" 6"
155' - 6 3/8"
5' - 11" 6"
14' - 0"
3' - 4"
3' - 4"
114' - 2 3/8"
A
A S1.2
S1.2
EXISTING GRADE BEAM
1
A SIM.
P1 W10X12
P P1
S1.2 W10X12
P
P
S1.2
S1.2
(TYP.) NOTE: REMOVE AND REPLACE EXISTING SLAB AS REQUIRED TO INSTALL NEW FOOTINGS
FD C14
M
REMOVE / REPLACE SLAB WHERE RECESS FOR FLOOR FINISH REQUIRED
P2
P1
FJ
P1 FJ
C15
P2
W10X17
P3
W10X12
NEW CONC. SLAB OVER COMPACTED FILL OVER EXISTING SLAB- SEE 3/A6.7 S1.2
A S1.3
K
9' - 10 7/8"
S1.3
(SIM.) 1' - 10 1/8"
4 9/16"
5
G
P4 P4
P4
B
C
D
E
F
G
* PROFESSIONAL
N
EN
TE
GIN E E R
S R S A US
Not Valid Unless Signed
ISSUED FOR: 3
11
CONSTRUCTION ADDENDUM #1 04-11-2016
2 1
CONSTRUCTION ADDENDUM #2 04-22-2016
PHASE 1
A
MJA - WHSIV - GJH
S1.3
DRAWN BY NORTH
PHASE 2 A
ED
RE
No. 19126
(SIM.)
(EXISTING BUILDING)
RG E OG I S TER I A
*
2
C22
6' - 7 3/4"
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
10' - 6"
P4
A
S1.3
W10X19
17' - 1 5/8"
6
W10X17
W10X12
C18
7
4
P4
A
SAVANNAH, GEORGIA
133' - 3"
(SIM.)
P4
(SIM.)
14' - 2 5/16"
2' - 0"
S1.3
W10X17
W10X12
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
GEORGIA
H
C3
A
C21
C17
6' - 3 3/16"
P3
W10X17
W10X17
W10X12
W10X12
21' - 3 1/2"
8
S1.2
P3
TOP OF FOOTINGS INSIDE EXISTING BLDG AT EL. 14.45 U.N.
C16
P3
P3 P3
P2
S1.2
W10X17
W10X12
C10
C11
P3
L
W12X26
DROP SLAB BELOW COOLER/FREEZER 4"- SEE ARCH.
P1 P4
C20
P3
9
HU W.
P4 P2
S1.3
W10X17 7
3' - 4"
2 P1
P3
NEW COMPOSITE DECK SYSTEM OVER BASEMENT W10X17
W10X12
S1.2
REMOVE AND REPLACE EXISTING SLAB W/ NEW 4" THICK SLAB REINFORCED W/ 6x6x8/8 WWF
W12X26
FJ
C8
C23
F
3' - 11 7/8"
C13
P3
2
7"
WFJ
P3
S1.2
P2
W10X17
W10X12
W12X26
FJ
C24
FJ
FJ
FJ
UP
10
P2
H
(13.12)
P4
W10X17
S.5 10.1
P1 P3
(13.12)
FD
P2 P3
C25
FJ P3 P1
W10X12
14' - 3 7/16"
P1
FJ
P3 P3 P1
FJ
P2
C11
C12
P3 P2
P1
7' - 1 9/16"
P2P4
P2 P1 P4 P3
P1 W10X17
P2
FJ
P3
FJ
C9
S.4
FJ
P1
P1
P4
FJ
P3
FJ
G.8
W12X26
P1 FJ
EXISTING CMU WALL
C19
C4
P3
P1
(EXISTING BUILDING)
13' - 11 3/8"
S1.3
W10X12
P1
CL
2 A
EXISTING GRADE BEAM
C7
P3 P2
S1.2
12' - 7 1/4"
EAST VICTORY LANE
CL
R
P2
A
14' - 4 5/16"
S1.2
S1.2
P3
(13.12)
B
18' - 2"
(13.12)
B
FJ
(11.79)
FJ
FOUNDATION PLAN
FJ (11.79)
54' - 10 1/8"
FJ
FJ
FJ
FJ
FJ
P3
P3
P2 P3
P2
P3
P4
III
P2
26' - 1 7/8"
P2
10.3
8' - 9 1/16"
P2
P2
5' - 2 7/16"
P2
FJ
P3 R
9' - 3 13/16"
P2
P4 P3
P2
9' - 9 11/16"
P2
P2
8' - 4"
R
P2
3' - 3 11/16"
P2
P3
FJ
FJ
3' - 11 3/16"
P2
P3
P3
P3 P2
P2
FJ
Y,
FJ
FJ
FJ R
S1.2
2' - 10"
P2
10.4
2' - 10"
P2
C3
P3 P2 P1
C5 C2
P3
BLESSED SACRAMENT SCHOOL- PHASE I
FJ FJ
(13.12)
8' - 4"
P2
P2
FJ
P3
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
P2
3' - 5 1/2"
P2
G.9 P2 P3 P3
S1.2 P2
6"
FJ FJ
P1
C
P3 P2
FJ
WFJ
WFJ FJ
P2
J
P2 P4
FJ
FJ
FJ
FJ
FJ
FJ
S1.2
P1
FJ
FJ
FJ
R R
FJ
FJ
3' - 9"
DN
s
P2
P3
FJ
7' - 3 5/8"
P4
FJ
P2
R
FJ
S1.2
FJ
SUMP PITSEE PLUMB'G DRAWINGS AND DETAIL ON S1.2
P3
R
P2 P3
S1.2
FJ
A
FJ
FJ
P3 P2 FJ
FJ P2
P1
P2 P3
P3
C
A
FJ
R
FJ
FJ
P3
FJ
FJ P1 P1
FJ WFJ
FJ
FJ
FJ
FJ
P3
FJ FJ
FJ
FJ
P2
FJ
FJ
P1 P3
P3
FJ
FJ
P2
ELEVATOR
FJ
FJ
FJ
P1 P1 FJ
FJ WFJ
S1.2
P1
1' - 2"
WFJ
P3
P2
P3
(11.12)
FJ
P2
FJ
P3
D
(-4'-0")
FJ
FJ
FJ
FJ
FJ FJ
FJ
WFJ
P3
P1 FJ
P4
(13.12)
R
(13. 12)
FJ
P2
P3
P3
P2
P3
P4
S1.2
FJ
S1.2
FJ
FJ
FD
P3
C FJ
FJ
FJ
S1.2
P2
S1.2
P3
FJ
P3
4" THICK CONCRETE SLAB ON GRADE REINF. WITH 6x6x8/8 WWF
FJ
FJ
C
WFJ
C
FJ
69' - 1 1/2"
A
FJ
WFJ
P2
P1
WFJ
BEAM OVER
P1
FJ 19.657 ° CMU
WFJ P1
FD
FJ
FJ
P2
1
FJ
FJ FJ
FJ
FJ
FJ
FJ
P3
P1
FJ
FJ
FJ
R
FJ
FJ
FJ
FD
P2
P1 FJ
P3
7' - 3 13/16"
FJ
P3
R
76' - 0 1/8"
FJ
FJ
FJ
FINISHED FLOOR ELEVATION = 15.12 (MATCH EXISTING)
P3
FJ
P3 P3 P2
FJ
FJ
P2 P3
P3
FJ
FJ
P1
P1 FJ
P3 R
A S1.2
P4
S1.2
5' - 0"
R
P3 P1 P1 P3
P3
FJ
FJ
P4
FJ
FJ
FJ
FJ
FJ
FJ
P1 P3
C
P3 P2
FJ
P2
P3
WFJ
P1 P4
P4
FJ
FJ FJ
FJ
FJ
FJ
P1
56' - 10 1/2"
P1
FJ
P4
C1
TOP OF PIER AT 8" BELOW MAIN BLDG. F.F.
FJ
FJ
S1.2
FJ
FJ
E
TOP OF PIER AT 8" BELOW MAIN BLDG. F.F.
P4
FJ
P3 P3
P3
FJ P1
FJ
FJ
P3
P1
P4
FJ
UNLESS NOTED , TOP OF INTERIOR WALL FOOTINGS AT ELEV. 13.12
FJ
P4
DN
P2
C1
13' - 9 3/4"
(13. 12)
S1.2
FJ
FJ
FJ
FJ
FJ
WFJ 7 5/8" FJ
S1.2
P2
P2
B
EDGE OF STAGE
FJ P4
P4 C
FJ
P1
FJ
P1
P4
DN
P3
P3
WFJ
P3
P2
FJ
P3
P2
P2
P3 P3
P2
P2
FJ
FJ
P2
FJ
FJ
P1
P2
FJ
FJ
DN
P3
P2
R
FJ
P3 FJ
(13.12)
FJ
FJ
19' - 8 1/2"
P1
P3
R
P2 P3 R
R
FJ
P2
FJ
G S1.2
FJ
RAMP SLOPE DN.
P2
P4
P3
P4
R
S1.2
P2
RAMP SLOPE DN.
19' - 8 1/2"
P2
FJ
P2
LA ND 'G
P2
FJ
P2
FJ
P2
FJ
P2
P2
FJ
P2
FJ
P3
S1.2 WFJ
P3
P2
R
A
P2
P3 (13.12)
P3 G
FJ
S1.2 P3
14' - 0"
(13.12) P4
P2
P2
A
FJ
R
P3 P3
F
3' - 10 3/8"
(13.12) P3
P3
NOTE: RECESS STAGE SLAB AS REQ'D. TO RECEIVE WOOD FLOOR'GCOORD. EXACT RECESS REQ'D. W/ WOOD FLOOR MFR.
6"
6"
S1.2
3' - 8 13/16" 3' - 7 3/16"
3'. - 4"
(13.12)
6' - 5 1/2"
G.9
EXISTING
KEY PLAN
WHSIII CHECKED BY
WHS III APPROVED BY
03/24/2016 PROJECT DATE
10114 PROJECT NUMBER
SHEET NUMBER:
FOUNDATION PLAN SCALE: 1/8"=1'-0"
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
S1.1 Copyright (c) 2008 All Rights Reserved.
1" E.J. 2" CONCRETE TOPPING SLAB
STEEL CAP PLATE
10"
61/4"
2nd FLOOR
REMOVE EXISTING BRICK AND CMU AS REQ'D TO INSTALL STEEL COLUMN 2ND FLOOR
3 _" 8
W12x14 8" PCHC SLAB
COLUMN AND FOUNDATION SCHEDULE COLUMN
HSS4x4x3/8SEE SCHEDULE
4" BRICKSEE ARCH 8" CMU REINF W/ #5@32"O.C.
MARK
LOAD (KIPS)
SIZE
BASE PLATE
C1
40
W10x33
C2
50
REMOVE 8" CONC WALL AS REQ'D TO INSTALL COLUMN AND BASE PLATE ASSEMBLY
B S1.3
POUR STOP 1 1/2" (TYP.)
61/4"
1ST FLOOR
6"
W8
4"
4"
(EXISTING BSMT)
W8
4-3/4" DIAMETER ANCHOR RODS (U.N.)
SEE SCHEDULE FOR COLUMN SIZE
6"
W10 / W12 / W14
W10 / W12 / W14
TUBES
"B"
WIDE FLANGES LAP 2'-6"
SOLID GROUTED CMU REINF W/ 2#5@24" O.C. NEW FOOTING
SECTION
TYPICAL COLUMN BASE PLATE DETAILS
EXISTING CONC BASEMENT WALL
20x20
8#6
8
6'-0"x6'-0"
14"
7#6
W18x50
10x1 1_4x20
16x24
10#6
6
7'-0"x7'-0"
18"
10#6
16x24
10#6
6
7'-0"x7'-0"
18"
10#6
C4
50
W10x33
12x3/4x12
-
-
-
5'-0"x5'-0"
12"
7#5
C5
35
W12x40
10x 3_4x14
18x18
8#6
8
5'-6"x5'-6"
14"
7#6
C6
110
HSS6x6x3/8
12x1x12
-
-
-
9'-0"x9'-0"
12"
8#6
C7
10
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
C8
16
HSS5x5x1/4
11x 5_8x11
-
-
-
5'-6"x5'-6"
14"
7#6
C9
20
HSS6x6x1/4
12x 5_8x12
-
-
-
6'-0"x6'-0"
14"
7#6
C10
15
HSS6x6x1/4
12x 5_8x12
-
-
-
5'-6"x5'-6"
14"
7#6
C11
11
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
C12
21
HSS5x5x1/4
11x 5_8x11
-
-
-
5'-0"x5'-0"
12"
7#5
C13
45
HSS6x6x3/8
12x 3_4x12
-
-
-
7'-6"x7'-6"
18"
7#6
C14
22
HSS5x5x1/4
11x 5_8x11
-
-
-
5'-0"x5'-0"
12"
7#5
C15
20
HSS5x5x1/4
11x 5_8x11
-
-
-
5'-0"x5'-0"
12"
7#5
C16
13
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
C17
61
HSS6x6x1/2
14x1x14
-
-
-
8'-6"x8'-6"
18"
8#6
2
C18
10
W10x33
12x3/4x12
16x16
8#6
8"
4'-6"x4'-6"
12"
6#5
2
C19
10
W10x33
12x3/4x12
16x16
8#6
8"
4'-6"x4'-6"
12"
6#5
C20
10
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
C21
41
HSS6x6x3/8
12x 3_4x12
-
-
-
7'-0"x7'-0"
18"
10#6
C22
10
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
C23
72
HSS6x6x1/2
14x1x14
-
-
-
9'-6"x9'-6"
18"
7#7
C24
79
HSS6x6x5/8
16x1 1_4x16
-
-
-
9'-6"x9'-6"
18"
7#7
C25
14
HSS4x4x1/4
10x 5_8x10
-
-
-
4'-6"x4'-6"
12"
6#4
LEVELING NUTS
(UNLESS DETAILED OTHERWISE) ALIGN BOTTOM OF NEW FOOTING W/ BSMT FIN. FLOOR ELEV
1'-0"
10x 3_4x12
DEPTH REINF. E.W.
W18x50
BASE PLATE-SEE SCHEDULE 2"± NON-SHRINK GROUT
SIZE
50
4-3/4" DIAMETER ANCHOR RODS (U.N.)
"B"
VERT. SPACG. #3 SIZE REINF. TIES
C3 2
3 1/2" PROJECTION
PROVIDE CONT TEMPORARY SHORING TO FACE OF EXISTING WALL PRIOR TO DEMOLITION OF STAGE FLOOR OVER. L6x4x 3_8(LLO) W/ 6- 3_4"DIA. EXP BOLTS SHORING TO REMAIN UNTIL ALL NEW FRAMING INSTALLED
"D"
4" 3" 2" 4"
1'-0"
W12x26
2'-6"
(MIN.)
SEE SCHEDULE FOR COLUMN SIZE
FOOTING
10x1 1_4x20
"D"
8" LAP 2'-6"
REMOVE AND REPLACE EXISTING PAVING AS REQ'D TO INSTALL FOOTING- SEE CIVIL
1 1/2" (TYP.)
PIER
NOTES:
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
4"
11 5/8"
GEORGIA
81_4"x10"x 1_2" KNIFE PLATE EXISTING STAGE FLOOR
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
W14
SAVANNAH, GEORGIA
3-3/4"DIA. H.S. BOLTS
BLESSED SACRAMENT SCHOOL- PHASE I
#4x12"x12" EACH GROUTED KEYWAY (4'-0" +/- O.C.)
NOTES: 1. "N/A" = NOT APPLICABLE
BSMT FLOOR
3#4 CONT OVER #3@18"O.C.
2'-4"
SEE SCHEDULE FOR COLUMN SIZE
SQUARE PIERS EMBED. SEE DETAIL
FND. LEVEL "C" TIES
"C" TIES
DOWELS TO BE SAME SIZE NUMBER AND POSITION AS SCHEDULED REINF. OVER.
6" TO 10" CMU 4 BARS
SEE SCHEDULE FOR SIZE AND SPACING OF TIES. 6 BARS
10 BARS
RECTANGULAR PIERS
12"
8"-10"
12"
8"-10"
12"
12'-0"
1#5 @ 48"
2#5 @ 48"
1#5 @ 48"
2#5 @ - 48"
1#5 @ 48"
2#5 @ 48"
1#5 @ 48"
2#5 @ 48"
16'-0"
1#5 @ 32"
2#5 @ 48"
1#5 @ 48"
2#5 @ 48"
1#5 @ 32"
2#5 @ 48"
1#5 @ 48"
2#5 @ 48"
20'-0"
1#5 @ 24"
2#5 @ 32"
1#5 @ 32"
2#5 @ 48"
2#5 @ 32"
1#5 @ 32"
2#5 @ 32"
SEE PLAN THICKNESS
SEE PLAN
FOOTING WITHOUT PIER
FOOTING WITH PIER
24'-0"
2#5 @ 24"
2#5 @ 48"
2#5 @ 24"
2#5 @ 24"
30'-0"
2#6 @ 16"
2#5 @ 32"
2#6 @ 16"
2#5 @ 32"
TUBE SHAPED COLUMNS SEE SCHEDULE FOR COLUMN SIZE BASE PLATE-SEE SCHEDULE- OVER 2"± NON-SHRINK GROUT
4-3/4"Øx16" HEADED ANCHOR RODS W/ LEVELING NUTS
NOTES: NOTE (1) INTERMEDIATE BOND BEAMS MAY BE ADJUSTED IN ELEV. WITHIN 8' MAX. INCREMENTS TO INCORPORATE INTO LINTELS OR BEARING LEVELS FOR JOISTS OR BEAMS. SEE STANDARD DETAILS. USE CHANNEL BLOCK BETWEEN VERTICAL BARS OR PLUS CELLS BELOW WHERE NOT REQ'D FOR GROUTING. NOTE (2) WHEN FILLING CELLS MAX. LIFT PER POUR IS 8'-0" ALL REINF. MUST BE TIED IN PLACE PRIOR TO GROUTING. SEE GENERAL NOTES. NOTE (3) SEE STANDARD DETAIL FOR REINF. CONC. MASONRY PIERS FOR ADDITIONAL BARS REQ'D AT JAMBS, CORNERS, ETC. NOTE (4) HEIGHT "H" IS THE MAX. DISTANCE BETWEEN LATERAL SUPPORTS PROVIDED BY FLOORS, ROOFS, FOOTINGS, OR OTHER HORIZONTAL PLANES. WHERE WALL IS LATERALLY SUPPORTED AT INTERMEDIATE FLOOR OF ROOF LEVELS, THE REINFORCING SHALL BE THAT SCHEDULED FOR THE MAX. DISTANCE BETWEEN SUPPORTS. WHERE WALL CONTINUES ABOVE ROOF LEVEL (PARAPET). CONT. SCHEDULE REINFORCING FULL HEIGHT, U.N. NOTE (5) INTERIOR WALLS ARE THOSE IN WHICH NO PORTION BELOW HIGHEST ADJACENT ROOF IS EXPOSED TO WIND FORCES (EXTERIOR EXPOSURE). IF ANY PORTION OF A WALL SYSTEM IS EXPOSED TO THE EXTERIOR, IT SHALL BE CLASSIFIED "EXTERIOR" EXPOSURE FOR IT'S FULL HEIGHT AND REINF. ACCORDINGLY. NOTE (6) ALL REINFORCED MASONRY WALLS SUPPORTING ROOFS SHALL BE CLASSIFIED AS "LOAD BEARING". WHERE A REINF. MASONRY WALL IS NOT SUPPORTING A ROOF, IT SHALL BE LATERALLY BRACED AS SPECIFIED.
ENCASE WITH CONCRETE AFTER COLUMN SET
SEE SCHEDULE FOR COLUMN SIZE
3#3 TIES
CONCRETE PIERSEE SCHEDULE
#3 TIES (1 1/2" CL.) VERTICAL BARS- SEE PIER SCHEDULE
ADD 2#3 HOOPS IN FOOTING
BASE PLATE-SEE SCHEDULE OVER 1/4" LEVELING PLATE ON 3/4"± NON-SHRINK GROUT
4-3/4"Øx12" HEADED ANCHOR RODS-W/ LEVELING NUTSTYPICAL U.N.
* PROFESSIONAL
N
EN
TE
GIN E E R
S R S A US
Not Valid Unless Signed
ISSUED FOR: CONCRETE ENCASEMENT
3" MIN.
2
CONSTRUCTION ADDENDUM #1 04-11-2016 CONSTRUCTION ADDENDUM #2 04-22-2016
3" CL.
3" CL. SEE SCHEDULE FOR FOOTING SIZE AND REINFORCING
ED
RE
No. 19126
1
COMPACTED SUBGRADESEE SPECS.
RG E OG I S TER I A
*
1/4" P.E.J.
COMPACTED SUBGRADESEE SPECS.
SEE SCHEDULE FOR FOOTING SIZE AND REINFORCING
12" CMU FOOTING WITHOUT PIER
FOOTING WITH PIER
MJA - WHSIV - GJH DRAWN BY
WHSIII CHECKED BY
STANDARD SCHEDULE FOR REINFORCED CONCRETE MASONRY WALLS (V= 120 MPH)
WIDE FLANGE COLUMNS
WHSIII APPROVED BY
TYPICAL COLUMN FOOTING DETAILS
03/24/2016
CONCRETE PIER DETAILS NOTES: 1. SEE SCHEDULE & SECTIONS FOR PIER SIZE & REINFORCING. 2. TERMINATE VERTICAL BARS IN FOOTING WITH 90° HOOK (12) BAR DIAMETERS (MIN). 3. ALTERNATE LOCATION OF 90° AND 135° BENDS. 4. ALL PIERS TO BE BOARD FORMED. 5. TOP OF PIERS SHALL BE 8" BELOW FINISHED FLOOR U.N. 6. TOP OF VERTICAL DOWELS SHALL EXTEND TO 1 1/2" FROM TOP OF PIER.
G
SECTIONS & SCHEDULES
8"-10"
III
12"
SEE SCHEDULE FOR FOOTING SIZE AND REINFORCING
Y,
8" U.N. 8"-10"
COMPACTED SUBGRADESEE SPECS.
SEE SCHEDULE FOR FOOTING SIZE AND REINFORCING
3" CL.
8 BARS
NOM. WIDTH
COMPACTED SUBGRADESEE SPECS.
3" CL.
SEE PLAN
WHERE CMU EXTENDS BELOW GROUND SLAB LEVEL. FILL ALL CELLS WITH CONC. 48 DIA. (2'-6" MIN.)
4 BARS
INTERIOR
3" MIN.
CONCRETE ENCASEMENT
HU W.
1 1/2" CL. (MIN.) TYP.
VERT. BARSSEE SCHEDULE
EXTERIOR
1/4" PEJ ISOLATION JOINT
48 DIA. (2'-6" MIN.)
B S1.3
SECTION
2 1/2"
INTERIOR
1/4" P.E.J.
3" CL.
THICKNESS
1'-1"
2 1/2"
EXTERIOR
NON−LOAD BEARING WALLS & PARTITIONS (SEE NOTE 6)
THICKNESS
INTERMEDIATE "V" BARS IN CENTERLINE (U.N.) GROUTED CELLS. SEE NOTE (3).
LOAD BEARING WALLS (SEE NOTE 6)
8" U.N.
8'-0" O.C. (MAX.) SEE NOTE 1 & 2
TOP OF EXISTING CONCRETE WALL
EXPOSURE SEE NOTE (5)
ADD 2#3 TIES IN FOOTING
THICKNESS
10"
8"
INTERMEDIATE 8" DEEP BOND BEAMS W/ 2#5 CONT. LAP BARS 1'-6" @ SPLICES
CLASS
3"
48 DIA. (2'-6" MIN.)
1/4
31/2"
VERTICAL BARS- SEE PIER SCHEDULE
SCHEDULE OF MINIMUM INTERMEDIATE VERTICAL REINFORCING- ("V" BARS)
INTERMEDIATE "V" BARS EA. FACE. SEE NOTE (3)
11/2"
11/2"
SHOP DRAWINGS SHALL BE FURNISHED BY GENERAL CONTRACTOR INCLUDING WALL ELEVATIONS AND PLANS DETAILING FINAL LAYOUT OF ALL VERTICAL AND HORIZONTAL REINFORCING REQUIRED BY THIS SCHEDULE DETAILS AND GENERAL NOTES IN THESE DOCUMENTS.
SEE PLAN
HEIGHT- SEE SECTION, ETC.
31/2"
31/2"
11/2"
11 5/8"
5"
7 5/8" 9 5/8"
3" CL.
HSS4x4x3/8
MAX. HEIGHT "H" SEE NOTE (4)
THICK BASE PLATE 4-34" DIA. EXP BOLTS
CONCRETE PIERSEE SCHEDULE
#3 TIES (1 1/2" CL.)
3" CL.
5 5/8"
5 8"
3#3 TIES
BASE PLATE-SEE SCHEDULE- OVER 2"± NON-SHRINK GROUT
4-3/4"Øx12" HEADED ANCHOR RODS-W/ LEVELING NUTSTYPICAL U.N.
5"
PROVIDE 8" DEEP (MIN.) CMU CONT. BOND BEAM REINF. WITH 2#5 BELOW ALL CHANGES IN WALL THICKNESS. SEE DETAILS FOR DOWELS, ETC. INTO CONSTRUCTION OVER.
4"
SEE SCHEDULE FOR COLUMN SIZE
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
ENCASE WITH CONCRETE AFTER COLUMN SET
1/4" PEJ ISOLATION JOINT
3" CL.
A S1.3
SECTION
BASE PLATE-SEE SCHEDULE- OVER 2"± NON-SHRINK GROUT
4-3/4"Øx16" HEADED ANCHOR RODS W/ LEVELING NUTS
PROJECT DATE
10114 PROJECT NUMBER
PRELIMINARY NOT FOR CONSTRUCTION USE
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
SHEET NUMBER:
S1.3 Copyright (c) 2008 All Rights Reserved.
2
S.2 36' -. 03/4"
6"
8" DEEP H.C. PLANKS
H
1' - 2"
S2.2 4'-0" x 8 " H.C. PLANKS
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
S2.2 K H
S3.2
17' - 1 5/8"
C S2.2
S2.2
E
G
7 5/8"
7 5/8"
DOWN
P1
C12x20.7
C6x8.2
P1
S2.3 (SIM.) L4x4x3/8
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
A
14' - 4 3/16"
H
H
7 5/8"
(@ CATWALK)
S2.2
W/ 2" TOPPING SLAB
1
PLANKS THIS AREA TO BE DESIGNED
S2.2
SL-2 W12X14 (9)
W12X14 (9)
W16X26 W21X44
W12X14 (8)
W10X12
W8x10
C10X15.3
P1
W10X12
W10X12
W10X12
OPEN
P1
W10X12
C10X15.3
5' - 2 7/16"
W24X55
3' - 11 7/8"
P
RAMP LANDING
W8x10
EXISTING FRAMING TO REMAIN
. 4' WIDEx8" H.C. PLANKS W/ 2" TOPPING SLAB
RAMP DOWN
A S2.3 3' - 5" 5' - 5 1/8"
P
Q
S2.2
S2.2
EXISTING FLOOR AT ELEV. 10'-3"+/- AF.F. (VERIFY)
L6x3 1/2x5/16 (OR BENT PL.) ROLLED TO RADIUS OF ARCH.
TYPICAL SECTION X-X THRU REINFORCED CONCRETE LINTEL
7 1
6
5
BEND 1'-6"
6' - 3 3/16"
14' - 2 5/16"
FIN. 2nd FL.
X 3#4
3
ED
RE
*
* No. 19126 PROFESSIONAL
N
EN
TE
GIN E E R
S R S A US
Not Valid Unless Signed
11
SIU H. D C R A AR E SE
2
1
#3 TIES @ 10" O.C.
COORD. W/ ARCHITECTURAL DRAWINGS
24"x10" CONC. COLUMN 8#5 (4 EACH FACE)
49' - 6"
CONSTRUCTION ADDENDUM #1 04-11-2016 CONSTRUCTION ADDENDUM #2 04-22-2016
MJA - WHSIV - GJH DRAWN BY
2'-0"
DETAIL @ ARCHED WINDOW OPENINGS 13' - 11 3/4"
G
RG E OG I S TER I A
ISSUED FOR:
S.3
4 9/16" 6' - 7 3/4"
17' - 1 5/8"
BEND 12" EACH END 2#4
2" CL .
2'-0"
21' - 3 1/2"
WHERE REINFORCED CMU SHEDULED OVER, PROVIDE DOWELS SAME SIZE AND SPAC'G AS VERTICAL REINF. OVER X 3#6
12 12
2
C10X15.3
C12X20.7
C12X20.7
P
P
LAND'G
RAMP DOWN
10
9' - 3 13/16"
C10X15.3
W10X12
W16X26 (13) c=3/4"
W24X55
3. "
W12X19
W12X14 (9) W16X26 W10X12
P1
W12X14 (12)
W10X12
UP
W10X12
S2.3
DECK SPAN
B
W10X12
2
S.5 10.1
4
W10X12 W24X84
P1
W16X26 (13) c=3/4"
W16X26 (13) c=3/4"
W16X26 (13) c=3/4"
W24X55
W14X22
= 14'-0" = 13'-5 3/4"
SL-2
1' - 10 1/8"
W10X12
T/S TOS
6"
DECK SPAN
W12X26
1
9
W12X19
W12X14 (9)
8" CMU
5/8"∅ EXPANSION BOLT @ 24" O.C. W/ MINIMUM 4" EMBEDMENT
8
W12X14 (8)
W12X14 (8)
4" BRICK-SEE ARCH.
HU W.
W14X26
W10X12 (7)
W16X26 (13) c=3/4"
S2.3
W16X26 (13) c=3/4"
C
W24X55
W16X26 (13) c=3/4"
W16X26
5
W10X12
W12X14 (8)
W10X12 (7)
S2.2
W12X14
W12X14 (8)
W10X12
DECK SPAN
S2.3
W14X22
W10X12 (7)
W14X22
W14X26
3 1/4" L.W.. CONC. FILL OVER 3"x18 GA. COMPOSITE STEEL DECK L
1
W12X14 (8)
F
S2.3
3
W12X19
2
W10X12
W24X55
W14X22
W10X12 (7)
C
S2.2
3' - 11 3/16"
W12X14 (9)
R
7" 8' - 9 1/16"
W14X22
W16X26
W10X12
W10X12
W12X14
W12X14 (9)
DN
W10X12
1" E.J. IN FLOOR
W10X12
W10X12 (7)
W10X12
W12X14
W16X26
W10X12
W14X22 (-9 7/8")
PLANKS W/ 2" TOPPING SLAB
W14X22 (7)
4'-0" WIDE x 8 " HOLLOW CORE
S2.3
W10X12
S2.3
S1.3
W10X12
E
1" EXPANSION JOINT AT FACE OF EXISTING WALL
A
10"
4"
1
3' - 3 11/16"
N
D
W10X12
10
W10X12
6" METAL STUD WALL AT (MAX.) 6'-0" O.C.
D
1'-2"
1
1
7' - 3 13/16"
B
CL W14X22
A
FOR ADDITIONAL DL= 100 PSF, SEE R/S2.2
SEE DETAILS THIS SHEET FOR CONCRETE ARCH.
9' - 9 11/16"
EAST VICTORY LANE BELOW
CL
9
M
2ND FLOOR FRAMING PLAN
S2.2
10' - 6"
SL-1
(SIM.)
S.5
10.3
W/ 2" TOPPING SLAB
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
S2.2
SCALE: 1/4" = 1'-0"
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
D D
B
RADIUSSEE ARCH.
CONT. L6x4x3/8 ANGLE
S2.2
1' - 2"
CONT. L6x4 ANGLE
11' - 9 7/16"
1'-0" (MIN.)
CONT. C6x10.8 CHANNEL
CONT. C6x10.8 CHANNEL
H
SPRINGLINESEE ARCH.
H
2"
H
2" CL.
H
W12x40
6' - 4"
H
1'-4"
H
LOWER LEVEL FRAMING PLAN AT STAIR 06
LAP 1'-8" TYP.
H
POST P1 INDICATES HSS4x4x 1_4 OVER LOWER BEAM
1'-0"
H
A
A
2'-0"
H
S2.2
26' - 1 7/8"
H
C
EXISTING FLOOR AT ELEV. 10'-3"+/- A.F.F.(VERIFY) 21'-3 1/2"
10.4 17' - 5 3/4"
H
H
6' - 2 3/4"
7 5/8"
S2.2
H
W14X22
B
H
W12X14
14' - 8 9/16"
H 6' - 2 3/4"
H
W10X12
1' - 7 5/8"
W16X26
S1.2
S2.2
7 5/8"
P1
F
6'-9 3/4" H
2
S2.3
B
W/ 2" TOPPING SLAB
H INDICATES L31/2x31/2x3/8 HANGERS FROM L3x3x1/4 @ 4'-0" O.C. ROOF OVER @ 1" BAR GRATING (MAX.) 6'-0" O.C.
B
III
° 00 .0 3° 90 .34 70
15' - 0 13/16"
1
F
S2.2
C12x20.7 STRINGER
OPEN
H 5' - 2 3/16"
W16X26
3
W/ 2" TOPPING SLAB
ELEVATOR
19.657 °
P1
S1.2
.
4'-0" x 8 " H.C. PLANKS
B
W10X12 (-2")
J OPEN S2.2
1
W10X12 (-2")
8'-0 3/16"
75' - 6 1/8"
25' - 2 1/2"
W16X40 W8x31
W/ 2" TOPPING SLAB
S1.2
5'-10"
OPEN
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
F
3 1/2"
B
W/ 2" TOPPING SLAB
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
S2.2
TOS = 10'-0" A.F.F.
1' - 2" 21' - 9 3/4"
S2.2
H
G
SCALE: 1/8" = 1'-0"
S1.2 7 5/8"
S2.2
E
RAMP LOW FRAMING PLAN
W/ 2" TOPPING SLAB
S2.2
4'-0" WIDE x 8 " HOLLOW CORE PLANKS
S2.2
7 5/8"
H
D 7 5/8"
7° .65 9 10
H
7' - 0 5/16" +/-
Y,
1' - 2"
E
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
7 5/8"
H INDICATES L31/2x31/2x3/8 HANGERS FROM ROOF OVER @ (MAX.) 6'-0" O.C.
26' - 9 9/16"
W/ 2" TOPPING SLAB
SAVANNAH, GEORGIA
W/ 2" TOPPING SLAB
BLESSED SACRAMENT SCHOOL- PHASE I
W/ 2" TOPPING SLAB
OPEN
W12x40
OPEN
18' - 5 5/8"
4'-0" WIDE x 8 " H.C. CORE PLANKS
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
H
W10X12
H
(VERIFY)
10"
H
EXISTING FLOOR AT ELEV. 10'-3"+/-
S2.2
1'-4" (MIN.) ADJUST TOP TO CMU COARSING
H
E
VARIES
H
W14X26
C12x20.7 STRINGER
H
1
S2.3
A
S2.2
W14X26
GEORGIA
J
CONT. C6x10.8 CHANNEL
S2.2
W14X26
W18X50
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
CONT. L6x4 ANGLE
S2.2
1' - 2"
S2.2
1" BAR GRATING
B
4' - 8"
D
L3x3x1/4 @ 4'-0" O.C. 4'-0"
W8x31
D
3 1/2" (TYPICAL)
19' - 8 1/2"
W18X35
A
S2.2 1' - 2"
S2.2
3
1' - 6"
6"
S2.2
3 1/2" (TYPICAL)
161' - 11 15/16"
B
P
HSS4x4x3/8 HANGER TO W24 OVER
5 5/8"
S.1
(NOT TO SCALE)
WHSIII CHECKED BY
WHS III APPROVED BY
03/24/2016
PHASE 1 A
B
C
D
E
F
G
G.8
S.4
PROJECT DATE
10114
G.9
PROJECT NUMBER
SECOND FLOOR FRAMNG PLAN
SHEET NUMBER:
NORTH
SCALE: 1/8"=1'-0"
EXISTING PHASE 2
KEY PLAN
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
S2.1 Copyright (c) 2008 All Rights Reserved.
1'-2" 8" REINF. CMUSEE SCHEDULE
1'-4"
2" TOPPING SLAB
10" CONT L8x6x3/8
EMBED PLATE 6"x 1_2"x6" W/ 4-1_2"DIA.x5" HEADED ANCHORS @ 24" O.C.
J S2.2
SECTION
1'-2"
2"
3"
3 1/2" BEARING
SECTION
N S2.2 8" CMU
8" CMU REINF. WITH #5 AT 24" O.C. IN CENTERLINE OF GROUT FILLED CELLS
5 5_ " 8
4'-0"
4'-0"
1'-2"
+14'-0" A.F.F. 6" CMU BREAK CORNER OF SLAB AND EMBED #4 X 4" X 4" X 1'-0" AT 4'-0" O.C.
8" PRECAST HOLLOWCORE SLAB
4" CMU
GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER
BEARING PAD BY SLAB MFR.
EXISTING CONCRETE BEAM
3~8" BEARING
BEARING PAD BY SLAB MFR.-TYP. 8" REINF. CMU SEE SCHEDULE
14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
8" REINF. CMUSEE SCHEDULE
W14x26 3"
+14'-0" A.F.F.
W14
+10'-9"
PC C12x20.7
C6x8.2 C12x20.7 STRINGER-TYP
EXISTING CONC. WALL
G S2.2
L S2.2
SECTION
EXISTING CONCRETE BEAM
SECTION
Q S2.2
G
* No. 19126
HU W.
0'-4"
PROFESSIONAL
T/S 14'-0" A.F.F.
L321x321x38 HANGER @ 6'-0" MAX O.C.
L3x3x 1_4 @ 4'-0" O.C.
C6x10.8
14'-0" A.F.F.
5"
#4 X 1'-0" X 2'-0" IN EACH GROUTED JOINT 3~8" BEARING
L6x4x38(LLV) W/ 34"DIA. ADHESIVE BOLTS @ 32" O.C.
SECTION
D S2.2
SECTION
H S2.2
4'-4"
8"
8"
#3@8"O.C. IN CENTERLINE-TYP
FACE OF 4" CMU BETWEEN W16 FLANGES W24x68
4'-4"
#3@8"O.C.BEND 8" AT TOP
8"
1
8" #3@8"O.C.BEND 8" AT TOP 8" CMU
BEND 12"
#3@12"O.C.
2" TOPPING SLAB
2
CONSTRUCTION ADDENDUM #1 04-11-2016 CONSTRUCTION ADDENDUM #2 04-22-2016
MJA- WHSIV - GJH DRAWN BY
WHSIII
2ND FLOOR
CHECKED BY
CONT. STEEL PLATE: 1'-5"x1/2"
1 0'-0 _" 2
S R S A US
BEND 12"
BEND 8"
GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER BEARING PAD BY SLAB MFR. 14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
4'-4"
6"
GALV. CORR. BRICK TIES @ 16" O.C.
L4x4x1/4 CONT.
GIN E E R
ISSUED FOR:
WT STIFFENER (CUT FROM W12x14) @ 48" O.C.
SEE ARCH.
STEEL RAILINGSEE ARCH
4"
1" GALV STEEL GRATING
4'-4"
1/2"∅x6" HEADED STUDS @ 24" O.C. IN GROUTED CMU.
4" BRICKSEE ARCH.
8"
12" REINF CMU- SEE SCHEDULE
17'-4" #5x3"x1'-6" DOWELS WELDED TO W16 TOP FLANGE @ EACH VERTICALLY REINF. CELL OVER
6"
4" CMU
EN
TE
Not Valid Unless Signed
6"
SEE PLAN
8" CMU REINF. WITH #5 AT 48" O.C. IN CENTERLINE OF GROUT FILLED CELLS
8" PRECAST HOLLOWCORE SLAB
2"±
1'-6"
2" HIGH CMU
LAP 2'-6" MIN.
N
2"± TOPPING SLAB
ED
RE
*
(SEE E/S2.2 FOR CONTINUATION) 1'-2"
RG E OG I S TER I A III
EXISTING 2ND FLOOR FRAMING
L4x4x 3_8 W/ 2- 3_4"DIA. EXP BOLTS
Y,
3 1/2" BEARING
SECTION
W12x14
CLOSURE PLATE
3 1/2" BEARING
C S2.2
1 1_2" CONCRETE FILL ON 12GA METAL PANS-TYP
1 _" 4
W16x40 3 1/2" BEARING
61/4"
3"
W10
2"
W10x12 OR W12x14- SEE PLAN
[email protected]"=3'-9"
3"
8"
16" TYP.
3'-3"+/-
2"±
2"± GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER
CLOSURE PLATE
3 L1x1x __ EACH 16 STRINGER
BEARING PAD BY SLAB MFR.-TYP.
#4 X 3'-0" X 1'-0" IN EACH GROUTED JOINT(4'-0")
1 _" 4
3"
SECTIONS
7T@11"=6'-5"
3"
14'-0" A.F.F.
EXPANSION JOINT COVER- SEE ARCH
+10'-3" A.F.F. VERIFY
SECTION
P S2.2
SECTION
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
W8x31
A
4"
GROUTED CORES WHERE REQUIRED BY SLAB 3 1/2" MANUFACTURER BEARING
4'-0"
4"
BEARING PAD BY SLAB MFR.-TYP.
W14x26
2
6"x18 GA METAL STUD WALL @ 6'-0" MAX O.C.
8"
#4 X 2'-0" X 4" IN EACH GROUTED JOINT
1" E.J.
341" LW CONC. OVER 3" COMP. STEEL DECK
T/S 14'-0" A.F.F.
8"
2"±
2"±
T/S 14'-0" A.F.F.
T/S 14'-0" A.F.F.
8"
T/S 14'-0" A.F.F.
K S2.2
SECTION
BREAK CORNER OF SLAB AND EMBED #4 X 8" X 1'-6" AT EACH GROUTED JOINT
8" PRECAST HOLLOWCORE PLANKS
BREAK CORNER OF SLAB AND EMBED #4 X 8" X 1'-6" AT EACH GROUTED JOINT
8" PRECAST HOLLOWCORE PLANKS
F S2.2
#4x8" DOWELS AT 4" O.C. BEND 3" AND WELD TO BEAM
2"± TOPPING SLAB
2"± TOPPING SLAB
5 5_ " 8
W14x26 3'-9"
CONT HSS4x4x 3_8
61/4"
SECTION
#4x8" DOWELS AT 4" O.C. BEND 3" AND WELD TO BEAM
TOPPING SLAB CONTROL JOINT
L3x3x 3/8 BRACE @ 5'-0" O.C.
W18x50
8" REINF. WALLSEE SCHEDULE
B S2.2
TYP. 1/4
L3x3x 3_8 BRACES AT 36" MAX ON CENTER
L3x3x 3/8 BRACE @ 5'-0" O.C.
14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
SECTION
CONT PLATE 3 _"x7 5 _" 8 8
2"
3 1/2" BEARING
14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
BEARING PAD BY SLAB MFR.
VARIES W/ RAMP
8" 3 1/2" BEARING
GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER
#4 X 1'-0" X 2'-0" IN EACH GROUTED JOINT
3 1/2" BEARING
+10'-3"
L21/2x21/2x1/4 FRAMES @ 24" O.C.
W24x84
2"
6"
8"
#4 X 1'-0" X 2'-0" IN EACH GROUTED JOINT
L21/2x21/2x1/4 FRAMES @ 24" O.C.
T/S 14'-0" A.F.F.
T/S 14'-0" A.F.F.
1#5 CONT.
21/2" THICK CONCRETE FILL OVER 9/16" STEEL FORM DECK
VARIES W/ RAMP
2"±
6" CMU
W16 BEYONDSEE PLAN
2"
8" PRECAST HOLLOWCORE SLAB
2" HIGH CMU
T/S 14'-0" A.F.F.
8"
FORMED CAST IN PLACE CONCRETE
T/S 14'-0" A.F.F.
2"±
2" HIGH CMU
2"± TOPPING SLAB
BREAK CORNER OF SLAB AND EMBED #4 X 8" X 8" X 1'-0" AT 4'-0" O.C.
8"
LAP 2'-6" MIN.
8" PRECAST HOLLOWCORE PLANKS
21/2" THICK CONCRETE FILL OVER 9/16" STEEL FORM DECK
CONT. L2 1/2x21/2x1/4
2"± TOPPING SLAB
2"±
4" BRICKSEE ARCH.
2"±
2"± TOPPING SLAB
LAP 2'-6" MIN.
LAP 2'-6" MIN.
2" HIGH CMU
61/4"
CONT. L2 1/2x21/2x1/4
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
E S2.2
11/2"
W8x31
GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER
SAVANNAH, GEORGIA
SECTION
SEE A/S2.2
BLESSED SACRAMENT SCHOOL- PHASE I
A S2.2
11/2"
BEARING PAD BY SLAB MFR.-TYP.
8" REINF. CMUSEE SCHEDULE
8" REINF. CMUSEE SCHEDULE
GEORGIA
T/S 14'-0"+/A.F.F.
8" GROUTED CORES WHERE REQUIRED BY SLAB MANUFACTURER BEARING PAD BY SLAB MFR.-TYP.
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
2'-2"
#4@16"O.C.
2#4
6" 14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
3~8" BEARING
SECTION
2#4
CONT #4
#4 X 4'-0" CENTERED IN EACH GROUTED JOINT
3 1/2" BEARING
3 1/2" BEARING
BEARING PAD BY SLAB MFR.
14" DEEP CMU BOND BEAM REINF. W/ 2#5 CONT.
#3 STIRRUPS @ 8" O.C.
T/S 14'-0" A.F.F.
8" 1#5 CONT.
#4x1'-0"x2'-0" DOWELS AT 4'-0" O.C.
1'-6"
T/S 14 '-0" A.F.F.
8"
FORMED CAST IN PLACE CONCRETE
2#6 TOP AND BOTTOM
8" PRECAST HOLLOWCORE PLANKS
T/S 14'-0" A.F.F.
8"
2"±
T/S 14'-0" A.F.F.
2"±
8" PRECAST HOLLOWCORE SLAB
TOPPING SLAB CONTROL JOINT 2"± TOPPING SLAB
8" PRECAST HOLLOWCORE PLANKS
2"±
LAP 2'-6" MIN.
2" HIGH CMU
2" HIGH CMU
2"± TOPPING SLAB
2"± TOPPING SLAB
2"±
BREAK CORNER OF SLAB AND EMBED #4 X 8" X 8" X 1'-0" AT 4'-0" O.C.
4" BRICKSEE ARCH.
FACE OF 4" BRICK
LAP 2'-6"
LAP 2'-6" MIN.
1'-2"
WHSIII APPROVED BY
03/24/2016 0'-10"
2#4
8" PCHC
STYROFOAM BILLETS
~C
SECTION (SPECIAL LINTEL SL-1)
PROJECT DATE
3#4@12"O.C.
10114 PROJECT NUMBER
M S2.2 SECTION
R S2.2
SHEET NUMBER:
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
S2.2 Copyright (c) 2008 All Rights Reserved.
CONT W/ 5 8"DIA. A307 BOLTS @ 32"O.C.
61/4" 3"
FIN 2ND FL
4" BRICK VENEERSEE ARCH.
CONT BENT PLATE 641"x41"x4"(LLV) ANCHOR BOLTS AT 32" O.C.
4-3/4"∅ HS BOLTS 1 _" 2
STIFFENER PLATE EACH SIDE OF WF
C12x20.7 STRINGER EACH SIDE
3"
8" REINF. CMU-SEE SCHEDULE
1 4"
CLOSURE PLATE
EXISTING 2ND FL. +10'-3"+/- A.F.F.
1 2"DIA.x6" 5 L6x6x16
2'-0 5/8"
3 4"
CONT W/ DIAMETER x 8"x2" ANCHOR BOLTS AT 16" O.C.
1'-8 13/16"
3" BEND- WELD TO PLATE
CONT PLATE 21"x13" 7 5/8"
CONT BENT PLATE 38"x6" 2-C8x11.5
(STAIRWELL)
5'-10"
1/ " 2
1 W16x26
A S2.3
SECTION
W24x55
SECTION
D S2.3 SEE PLAN
SECTION
A 3'-5"
5'-5 1/8"
4" METAL STUDS- SEE ARCH
1/4" CLOSURE PLATE
2 0.7 x2 2 C1
GYPBOARD FINISHSEE ARCH
61/4"
SEE L/S2.2
F S2.3
4" METAL STUDSSEE ARCH
61/4"
6" 4" CMU PIER TYPE P3 AT CORNER
W10x12 W10x12
W10x12
W10x12 21/2"
21/2"
C12x20.7 STAIR STRINGER
L4x4x1/4x0'-4" W/ 5/8"∅x10"x2" ANCHOR BOLT IN SLOTTED HOLES
3'-9"
16" TYP.
3"
10 TREADS @ 11" = 9'-2"
STAIR STRUCTURESEE A/S2.3
EXTEND C12x20.7 OUTSIDE STRINGERS TO WALL
C12x20.7
3" CONC. FILL ON 12 GA. PLATE REINF. WITH 6x6x10/10 WWF
0.7 x2 2 C1
3" PC C12 CLOSURE AT INTERIOR STRINGER 3" 1/4" CLOSURE PLATE
14'-0"
2'-0 5/8"
HEADED ANCHORS @ 16"O.C.
W16x26
11 RISERS @ 7" = 6'-5"
C12x20.7
9'-4" A.F.F.
3'-1 5/16"
4"
C6x8.2
TOS 10'-6" A.F.F.
W16x26
W14x22
6"
C6x8.2 POST ON INSIDE FACE OF EACH STRINGER CONT L4x4x3/8 W/ 3 4"DIA. EXPANSION BOLTS @ 24" O.C.
E S2.3
SECTION
3"
EXISTING CONCRETE BEAM 6x6x10/10 WWF
1'-2"
W14x22
61/4"
2"
PC C12x20.7
CONT. L3x3x1/4
WT4x5
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
2"
[email protected]"=3'-9"
FIN 2ND FLR +14'-0" A.F.F.
GEORGIA
3 4"DIA.x8"x2x
W12x26
9 3" CONC FILL OVER 16 "x 26GA STEEL FORM DECK
8" REINF. CMU-SEE SCHEDULE
W10x12
SEE Q/S2.2
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
CLOSURE PLATE
3
+14'-0" A.F.F.
1'-2"
1 4"
ANCHOR BOLTS AT 32" O.C.
61/4"
3"
3 _ "∅x8"x2x 4
SAVANNAH, GEORGIA
1
ANCHOR BOLTS AT 32" O.C.
L6x4x38(LLV)
BLESSED SACRAMENT SCHOOL- PHASE I
7T@11"=6'-5"
4" BRICK VENEERSEE ARCH.
3'-0"± 3 _"∅x8"x2x 4
6"
THREADED ANCHOR W/ NUT AT BOTTOM SET IN 6" DRILLED HOLES FILLED W/ EPOXY ADHESIVE
6"
3 4"DIA
10
EXISTING 16"x16" CONCRETE ROOF BEAM
2
W16x26
3"
C12x20.7 RETURN
MC 12 x1 0.6
L1x1x3/16 SUPPORTS TYPICAL
HSS COLUMNSEE SCHEDULE
B S2.3
SECTION
L3x3x1/4 WITH 5/8"Ø HILTI KWIK BOLT (OR APPROVED EQUAL) WITH MINIMUM 2 1/4" EMBEDMENT 1/4" CLOSURE PLATE
12 TREADS @ 11" = 11'-0"
SECTION
G S2.3
A 2 FIELD DETERMINE EXPANSION JOINT COVER- SEE ARCH
1" E.J.
31_4" LW CONC. OVER 3" COMP. STEEL DECK
TIMBER BLOCKINGSEE ARCH.
1 _" 2
STIFFENER PLATE BETWEEN BEAM FLANGES
7 5/8"
23'-3 1/2"
7 5/8"
2'-8" CONT L3x3x1/4WELD TO JOISTS
5 CONT L6x3x16 (SLV)WELD TO JOISTS
4 1/2" 5'-3 5/8"
DN. WT
1'-0 3/4"
WT SR
12'-5 1/4"
WT
7 5/8"
EXISTING CONC. WALL
5'-3 7/8"
HSS6x6-SEE SCHEDULE
S2.3
EN
TE
GIN E E R
S R S A US
ISSUED FOR: 18" DEEP ROOF JOIST W21 STEEL BEAM-SEE PLAN
11
2
NEW ROOFING SYSTEM-SEE ARCH.
DN. G
PROFESSIONAL
Not Valid Unless Signed
S
+10'-3"
*
N
WT
CAP PLATE 5 1_2"x1_2"x12" WITH 4-3/4"∅ HS BOLTS
ED
RE
No. 19126
6" METAL STUD WALL-SEE ARCH.
FIELD DETERMINE
6"x18 GA METAL STUD WALL @ 6'-0" MAX O.C.
RG E OG I S TER I A
*
11 TOS 32'-2 16 " AFF
W14
3'-9"+/-
3"
G
7'-11"
S
W12
9'-2"
S
16" TYP.
5'-10"
HU W.
W16
4 1/2" 7 5/8"
61/4"
+14'-0" A.F.F.
III
6"
SECTIONS
1 1/2" CONC. FILL ON 12 GA. METAL PANS-SEE ARCH. DETAILS FOR NOSING
L2x2x1/4 AT EACH MC12 STRINGER
Y,
TOS 10'-6"
MC 12 x1 0.6
11 RISERS @ 7" = 7'-7"
TS6x3x1/4" BTW. OUTSIDE STRINGERS
2" TYP.
POST P1
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
8" CMU EXISTING 2ND FL. +10'-3"+/- A.F.F.
CONSTRUCTION ADDENDUM #1 04-11-2016 CONSTRUCTION ADDENDUM #2 04-22-2016
WT
MJA - WHSIV - GJH
EXISTING PRECAST CONCRETE TEES
S EXISTING 2ND FLOOR FRAMING
DRAWN BY
4 1/2"
WHSIII
SECTION
C S2.3
STAIR FRAMING LEGEND: S C12x20.7 STRINGER SR C12x20.7 STRINGER RETURN WT WT4x5 C8 C8x11.5 T TS6x6x3/8
CHECKED BY
WHSIII
STAIR 04 FRAMING PLAN
APPROVED BY
SCALE: 1/4"=1'-0"
03/24/2016 PROJECT DATE
2
10114 PROJECT NUMBER
PRELIMINARY SECTION
H S2.3
NOT FOR CONSTRUCTION USE
2
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
SHEET NUMBER:
S2.3 Copyright (c) 2008 All Rights Reserved.
S.1
S.2 36' - 0 3/8"
2' - 0 1/8"
3' - 6 11/16" 3' - 4"
EQ.
EQ.
3' - 4"2' - 8 3/8" 4' - 0 1/4"
3' - 3 3/4" 8 SPACES @ 5'-0" = 40'-0"
5 SPACES @ 6'-0" = 30'-0"
A
GEORGIA
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
S3.2 10K1
26KCS4
10K1 10K1
7 5/8"
RAC-2
1
RAC-3
26KCS4
10K1 10K1 1 EF-2 10K1 10K1 RAC-1
10K1
H
26KCS4 ERV-1
1
S3.2
10K1 10K1
26KCS4
TOS = 28'-3" A.F.F. 36LH11
36LH11
36LH11
36LH11
36LH11
36LH11
36LH11
W8x24 HOIST . BEAM
7 5/8" 10K1
22K9
ELEVATOR
8' - 5 5/8"
2
1
22K9
10K1
6"
6"
S3.2
26KCS4 RAC-4
2
10K1 10K1
EDGE OF DECK
K
26KCS4
S3.2 26KCS4 2
T 2'-5 3/4" . 4'-4 1/4" .
L
4 EQ. SPACES = 16'-10"+/-
S
10K1
2
7 SPACES @ 5'-0" = 35'-0"
S3.2
S3.2
2
S3.2
2
W21X57 (-2 1/2")
H S2.3 2
14K6
SLOPE SLOPE 4:12 4:12
14K6
14K6
2
L
2
S3.2
10 L S3.2
14K6
S3.2 CUT OUT EXISTING CONCRETE BEAM CORRIDOR OPENING
S3.2
14K6
P
S3.2
S.5
14K6
S3.2
S3.2
N
0"
Q W12x40 ABOVE EXISTING ROOF
J
RIDGE
(SIM.)
Q
W18x40 (-6")
HSS3x3x1/4 OUTRIGGERS @ 4'-0" O.C. EACH END OF ROOF
W27x102 RIGID FRAME (-3")
R
SLOPE SLOPE 4:12 4:12
S3.2
14K6
18K7
18K7
18K7
18K7
18K7
18K7
18K7
18K7
U
W W14X22 PO 10 ST x33
EAST VICTORY LANE
FLAT ROOF
14K6
9 2
8
W16X26 (-6")
7"
EXISTING BLDG.
7 M K
S3.2
S3.2
G
RG E OG I S TER I A ED
RE
*
* No. 19126 EN
TE
GIN E E R
III
HU W.
PROFESSIONAL
N
S R S A US
Not Valid Unless Signed
EQ.
EQ.
ISSUED FOR:
6"
CONSTRUCTION ADDENDUM #1 04-11-2016
10K1
11
2
11' - 8"
10K1
CL
TOS = 32'-2 3/16" A.F.F.
2
W W14X22 CO 10 LU x33 M N
GENERAL CONTRACTOR SHALL PROVIDE TO THE JOIST MANUFACTURER THE LOCATIONS AND LOADS IMPARTED TO THE ROOF JOISTS FROM THE WEIGHT OF THE BASKETBALL GOALS AND ACCESSORIES. JOIST SIZES AND DESIGNATIONS SHOWN ON THE ROOF FRAMING PLAN DO NOT INCLUDE THE LOADS/WEIGHTS DUE TO THE BASKETBALL GOAL AND ACCESSORIES. JOIST MANUFACTURER SHALL INCLUDED WEIGHTS FURNISHED BY THE GENERAL CONTRACTOR IN THE DESIGN OF THE JOISTS. GENERAL CONTRACTOR SHALL COORDINATE THE ATTACHMENT/SUPPORT METHOD/ ETC. OF THE BASKETBALL EQUIPMENT BASED ON THE JOIST LOCATIONS SHOWN ON THE FRAMING PLAN. BASKETBALL EQUIPMENT CONFIGURATION SHOWN ON THE CONTRACT DRAWINGS IS SCHEMATIC. COORDINATE WITH ARCHITECTURAL DRAWINGS AND INCLUDE ALL ATTACHMENT METHODS TO THE JOISTS IN THE EQUIPMENT SUBMITTALS.
35' - 0 5/16"
S3.2
10K1
3.
S3.2
W24X68
2.
E
0"
W14x22
1.
E
35' - 0 5/16"
BASKETBALL EQUIPMENT LOADS :
W24x55
2
10K1
10.3 WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
10K1
3'-2"+/-
S3.2
15' - 4 7/8"
EF-4
10.4 10' - 6"
W27x84 (-6") (CAMBER 1 3/4")
1
14' - 0 11/16"
10K1 10K1
S3.2
1
10K1 10K1
SUPPORT W27 ON CMU WALL
M
1
3' - 11 3/16" 7' - 3 13/16"
G
5' - 11 3/4"
26KCS4
1
1' - 5 1/2"
10K1 7 5/8"
10K1 10K1 RAC-5
2
3' - 6 5/8"
7 5/8"
Y,
36LH11
36LH11
36LH11
36LH11
36LH11
36LH11
36LH11
1' - 6"
59' - 3 1/8"
10K1 36LH11
69' - 1 1/2"
36LH11
6"
1
S3.2
36LH11
26KCS4
1
D
36LH11
2
10K1
ROOF FRAMING PLAN
S3.2
26K10
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
10K1
SAVANNAH, GEORGIA
12K 1
(3) 2.5K
10' - 0"
S3.2
1' - 1 5/8"
BLESSED SACRAMENT SCHOOL- PHASE I
S3.2
B
EF-1 1
13 SPACES @ 5'-0" = 65'-0"
C
W12X26 (-2 1/2")
B
TOS = 29'-1 1/2" A.F.F.
7 5/8"
W12X26 (-2 1/2")
6"
10 SPACES @ 5'-0" = 50'-0"
W12X26
26K10
S1.2
10K1
12KCS1
12KCS1
12KCS1
12KCS1
26K10
W24X76 (-5")
F
26K10
W8X24 (-2 1/2")
1
26K10
W8X24 (-2 1/2")
EF-3
12KCS1
TOS = 28'-3" A.F.F.
12KCS1
12KCS1
12KCS1
12KCS1
W16X26
12KCS2
12KCS2
12KCS2
17' - 2 1/2"
12KCS2
12KCS2
12KCS2
W16X26
12KCS1
12KCS1
S2.2
19' - 6 7/8"
12KCS1
12KCS1
12KCS1
12KCS1
B
CONSTRUCTION ADDENDUM #2 04-22-2016
MJA - WHSIV - GJH
PHASE 1
DRAWN BY
WHSIII CHECKED BY NORTH
WHSIII APPROVED BY
F
ROOF FRAMNG PLAN
S.4
EXISTING
03/24/2016
PHASE 2
PROJECT DATE
KEY PLAN
PROJECT NUMBER
10114
SCALE: 1/8"=1'-0"
SHEET NUMBER:
SAUSSY ENGINEERING 400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
S3.1 Copyright (c) 2008 All Rights Reserved.
8"
3 CONT 3 1_2x__ x31_2 BENT PLATE 16
CONT. 8" DEEP BOND BEAM
HSS4x4x 1_4
CONT W/ CONT1_4" STEEL PLATE
HSS3x2x1/4 CUT-IN BETWEEN OUTRIGGERS HSS3x3x1/4 OUTRIGGERS @ 4'-0" O.C. ON SLOPE
5 CONT. L6x3 21x16 (LLV) W/ 34" DIA. A307 THRU BOLTS @ 32" O.C.
4'-0"
4"
" 4'-0
CONT. L5x5x 41 W/ 34" DIA. A307 THRU BOLTS @ 24" O.C.
E S3.2
SECTION
6" A.F.F.
x102 W21
3"
6"
1'-6"
1'-8 1_2"
31'-4" A.F.F. 4" BRICKSEE ARCH.
TIMBER BLOCKINGSEE ARCH.
W18x76
1 2"
THICK STIFFENER PLATE EACH SIDE OF WF
4"
31_2"
CONT L5x5x 41 W/ 58"DIA.x8"x2" ANCHOR BOLTS @ 24" O.C.
9'-2" CONT TO JOISTS
WELD
28'-3" A.F.F.
4"
P S3.2
SECTION
TYP.
2
COORD. W/ PLAN
1'-5 1/2"
SECTION
N S3.2
2
T S3.2
SECTION
1'-2" THICK STEEL CAP PLATE
KNIFE PLATE 10"x8 21"x21" W/3- 34" DIAMETER H.S. BOLTS
1 2"
STIFFENER PLATE EACH SIDE OF W12 WEB
9" TYP.
H S3.2
SECTION
HSS5x5x38" STEEL POST EACH END OF W12.
5 CONT L6x321x16 (SLV)
W12x40
2
SEE J/S2.3 1'-8 1/2" CONT BENT PLATE 3 4"x16 "x4"-VERIFY DIMS WITH ARCH. DETAILS
10" JOIST 36" LONG SPAN JOIST
4
6" METAL STUDSSEE ARCH EXISTING CONCRETE BEAM TO REMAIN
6"
8" REINF CMU- SEE SCHEDULE
BLOCKING-SEE ARCH
EXISTING SINGLE TEE JOISTS
12
EXISTING CONCRETE BEAM TO BE REMOVED
6"
W14x22-TAPER AT ENDS AND WELD TO TOP OF W24
L4x3x41(LLV)x0'-4" EACH ANGLE BRACE
L8x6x1/2-SEE SECTION P/S3.2
CONT L3x3x1/4WELD TO L's
14" JOIST
VARIES WITH HIGH ROOF SLOPE
28'-3" A.F.F.
4"
29'-1 1/2" A.F.F.
ROOF DECK TYPE RD3
CONT L4x4x 41
26" DEEP ROOF JOISTS-SEE PLAN
W27x102
1 2"
30'-0" A.F.F.
L321x321x41-
STUD BRACES @ 16" ON CENTER-SEE ARCH
4" BRICKSEE ARCH.
CENTERLINE OF TOP CHORD PANEL POINT
ROOF DECK TYPE RD3
3" 28'-0" A.F.F.
7"
26" DEEP JOISTSEE PLAN
L8x6x1/2x9" EACH SIDE W/ (3) BEVELED STIFFENER PLATES
EXISTING CONCRETE BEAM TO BE REMOVED ABOVE CORRID0R 2100
5 8"
THICK SPLICE PLATE W/ (12) 3 4 "DIA. H.S. BOLTS
TOS 28'-3" AFF
1 2"
4"
3 CONT. L321x16 x321 BENT PLATE W/ HOLES @ 24" O.C.
ROOF DECK TYPE RD1
C S3.2
2" 5" 2" 4-3/4"DIA. A307 THRU BOLTS THRU EXISTING STEMS
4"
CONT HSS4x4x 41 W/ CONT . 1 4" STEEL PLATE
4
W27 STEEL BEAM-SEE PLAN
4"
STIFFENER PLATES @ 24" O.C.
4"
4
3 16"
7"
SECTION
18" DEEP ROOF JOIST
12
ROOF DECK TYPE-RD1 12
ROOF DECK TYPE-RD1
3"
W12x40 4-1"DIA. A36 HANGER RODS
4"
28'-3" A.F.F.
1 2_" 2
OSB PLYWOOD DECKING
CONT. HSS12x4x 41 1 CONT L3x3x 4WELD TO JOISTS
CONT L6x4x21(LLV) W/ 41" STIFF PLATE @ 24" O.C.
W24x76
3 _" 4
3"
12" DEEP JOIST
SECTION
PRE-ENGINEERED METAL ROOF TRUSSES @ 24" MAX. O.C.
SEE J/S3.2
G S3.2
6" METAL STUD WALL-SEE ARCH.
3"
29'-1 1_2" A.F.F.
5"
CONT BENT PLATE
EXISTING PRECAST SINGLE TEE ROOF JOISTS
1" (MIN.)
3 321x16 x321
M S3.2
5"
2" 4"
1'-2"
CONT L321x321x41- WELD TO JOISTS
36" DEEP LONG SPAN JOIST
SECTION
5 6x321x16 (LLV)-
11 TOS 32'-2 16 " AFF
6"
10" JOIST W/ 5" DEEP SEATS EACH END
CONT WELD TO JOISTS
CONT L3x3x1/4WELD TO JOISTS
5 CONT L6x3x16 (SLV)WELD TO JOISTS
2" (MIN.)
ROOF DECK TYPE RD3
2
1'-6"
L4x4x 21 EACH SIDE W/ 14- 43 "DIA. H.S. BOLTS
12" REINF CMUSEE SCHEDULE 1 4_" 2
S S3.2
SECTION
W8x31
5 CONT. L6x321x16 (LLV) W/ 34" DIA. A307 THRU BOLTS @ 32" O.C.
B S3.2
GEORGIA
36" LONG SPAN JOIST
L4x4x 38 EACH SIDE W/ 14- 43 "DIA. H.S. BOLTS
F S3.2
SECTION
8" REINF CMU- SEE SCHEDULE
SECTION
12
THICK CAP PLATE
29'-1 1_2" A.F.F.
12" JOISTSEE PLAN
6"
29'-1 1_2"
1 5 _" 2
28'-3" A.F.F.
1'-6"
SPLACE PLATE 4"x1"x4'-0" EACH SIDE
2"
7 _" 8
6"
12" REINF CMUSEE SCHEDULE
8" REINFORCED CMU-SEE SCHEDULE FOR REINFORCING SIZE AND SPACING
4
3"
JOIST-SEE PLAN
" 1'-6
.C.
6"
M
4" BRICKSEE ARCH.
ROOF DECK TYPE RD1
36" DEEP LONG SPAN JOIST
12" REINF CMUSEE SCHEDULE
1'-6"
1 1
CONT. L32x32x4- WELD TO JOISTS
XO " MA 0 ' 4
3"
31'- 4" A.F.F.
1 5 CONT. L6x32x16(LLV)WELD TO JOISTS 1
SPLICE PLATE 10"x1"x4'-0" " 6'-0
1 4_" 2 ROOF DECK TYPE RD3
36" DEEP LONG SPAN JOIST
1'-6"
A S3.2
SECTION
29'-1 1_2" A.F.F.
1 5_" 2
4" BRICKSEE ARCH
ROOF DECK TYPE RD3
L S3.2
SECTION
18" DEEP ROOF JOIST
5 8"DIA.x8"x2"
W/ CONT ANCHOR BOLTS @ 24" O.C.
W27x102 RIGID FRAME
28'-8 " A.F.F.
~C OF TOP CHORD L31_2x31_2x3_8 HANGERS @ MAX 6'-0" O.C. PANEL POINT
L5x5x 41
28'-3" A.F.F.
28'-0" A.F.F.
3"
7" CONT 6x3 1_2x3_8(LLV)
8'-10"
29'-1 1_2" A.F.F. 1 5_" 2
14" JOIST
G
D S3.2
W27x84
EXISTING CONCRETE COLUMN
AFTER ALL NEW STEEL OVER ROOF INSTALLED, CUT OUT EXISTING CONCRETE BEAM WHERE IT OCCURS OVER NEW 2ND FLOOR CORRIDOR-SEE ARCH FOR EXACT LIMITS
CONT L4x4x 41
2 14" JOISTSEE PLAN
CONT. 8" DEEP BOND BEAM
4" BRICKSEE ARCH.
CONT. L5x3x1/4(SLV) W/ 5/8"DIA THRUBOLTS @ 32" O.C.
SECTION
U S3.2
2
GIN E E R
S R S A US
CONSTRUCTION ADDENDUM #1 04-11-2016 CONSTRUCTION ADDENDUM #2 04-22-2016
MJA - WHSIV - GJH DRAWN BY
WHSIII CHECKED BY
WHSIII
11 TOS 32'-2 16 " AFF
W18x40
J S3.2
2
W24x68
COORD. WITH PLAN
1'-5 1/2"
SECTION SECTION
Q S3.2
2
TYP.
COORD. W/ PLAN
18" JOIST-SEE PLAN
1'-9"
26" DEEP ROOF JOISTS-SEE PLAN
1
34'-0" AFF
SECTION
STUD BRACES @ 16" ON CENTER-SEE ARCH
PLYWOOD SUBGRADE
EN
TE
ISSUED FOR:
FIELD DETERMINE
TOS 28'-3" AFF
6"
CLAY TILE ROOFINGSEE ARCH
CONT BENT RIDGE PLATE 4"x 1_4"x4"
PROFESSIONAL
Not Valid Unless Signed
TYP.
11_2" STEEL ROOF DECK 12 4
*
N
TOS 28'-3" AFF
L221x221x41@ 24" O.C.
W27 STEEL BEAM-SEE PLAN
ED
RE
No. 19126 HU W.
SECTION
BASE PLATE 11"x 58"x11" W/ 4-3/4" DIAMETER ADHESIVE BOLTS
PLYWOOD SHEATHINGSEE ARCH
RG E OG I S TER I A
*
CONT L6x321x1/4- WELD TO L's 5 8"
SWAINSBORO, ALBANY, ROME, SAVANNAH AND ATHENS
4" BRICKSEE ARCH
11
TOS 32'-2 16" AFF
JAMES W. BUCKLEY & ASSOCIATES INC. -- ARCHITECTS
BENT PLATE W/ HOLES @ 24" O.C.
7"
CONT
3 3 1_2x__ x31_2 16
SECTIONS
3 1/2"
ROOF DECK TYPE RD3
III
CONT HSS12x4x 1_4
CONT. L5x3x1/4(SLV) W/ 5/8"DIA. THRUBOLTS @ 32" O.C.
Y,
4
CONT L3x3x 1_4WELD TO JOISTS
TOS VARIES
SAVANNAH, GEORGIA
12
BLESSED SACRAMENT SCHOOL- PHASE I
STIFFENER PLATES @ 24" O.C.
CONT L4x4x1/4
WARNING: Contractors, subcontractors, vendors and suppliers are advised that the contract documents consist of Architect-reproduced printed, bound and numbered specifications, Architectreproduced printed, bound and numbered blue- or black-line prints, addenda, post-bid addenda, and change orders only. Documents reproduced by parties other than the Architect, whether in hard copy or in electronic format, shall not be considered part of the contract documents and do not supersede the provisions of the contract documents. The contractor, subcontractors, vendors and suppliers are solely responsible for verification that information utilized in bidding, development of shop drawings, and construction of the facility are identical to the contract documents.
3 __ " 16
L4x4x1/4x0'-4" EACH OUTRIGGER
29'-1 1/2" A.F.F.
ROOF DECK TYPE RD1
4'-8"
PRE-ENGINEERED METAL ROOF TRUSSES @ 24" MAX. O.C.
33'-4 " A.F.F.
OSB PLYWOOD DECKING
1'-9"
3 _" 4
12" JOISTSEE PLAN
SEE ARCH
APPROVED BY
K S3.2
03/24/2016 PROJECT DATE
10114 PROJECT NUMBER
18" DEEP ROOF JOIST
1'-2"
SECTION
6"
SHEET NUMBER:
8" REINFORCED CMU-SEE SCHEDULE FOR REINFORCING SIZE AND SPACING
R S3.2
SAUSSY ENGINEERING
2
400 Johnny Mercer Boulevard Suite E P.O. Box 30597 Savannah, Georgia 31410 Phone: (912) 898-8255 Fax: (912) 898-1882 PROJECT NO. 15003
S3.2 Copyright (c) 2008 All Rights Reserved.