485 Serial Communication Modules for Q Series

JAN 2003 New Product RELEASE Mitsubishi PLC No. 194E QJ71C24N, QJ71C24N-R2, QJ71C24N-R4 Serial Communication Modules GX Configurator-SC Version2 ...
Author: Alison Stevens
2 downloads 0 Views 562KB Size
JAN 2003

New Product RELEASE

Mitsubishi PLC

No. 194E

QJ71C24N, QJ71C24N-R2, QJ71C24N-R4

Serial Communication Modules GX Configurator-SC Version2 Introducing New 2-channel RS-422/485 Serial Communication Modules for Q Series GX Configurator-SC Version 2 makes the modules easier to use.

New Q series serial communication modules

Transmission speed of up to 230,400 bps is available! Supporting circuit trace and communication test for GX Configurator-SC Version 2!

D100

S-READV(FB2) S:IN_ST_NO O_END:B

( M100

)

D101

S:IN_READ_ADR

O_END_NG:B

( M101

)

D102

S:IN_ELEM_NUM

O_ERR_CD:W

D110

X100 B:I_START M1 B:I_REQ_SEND

New product lineup

Supports Protocol FB

QJ71C2

QJ71C2

4N-R4

CH1

RUN NEU. SD RD

ERR. NEU. SD RD

QJ71C2

4N

RUN NEU. SD RD

CH1 CH2

4N-R2

ERR. NEU. SD RD

CH1 CH2

RUN NEU. SD RD

ERR. NEU. SD RD

CH2

Enhanced debugging

2 4 6

S E T A B C T X X

1 3 5 7

QJ71C24N-R4

QJ71C24N

QJ71C24N-R2

CH1:RS-422/485 CH2:RS-422/485

CH1:RS-232 CH2:RS-422/485

CH1:RS-232 CH2:RS-232

QJ71C2

QJ71C2

4

CH1

RUN NEU. SD RD

4-R2

ERR. NEU. SD RD

2 4 6

CH1 CH2

RUN NEU. SD RD

ERR. NEU. SD RD

CH2

1 3 5 7

QJ71C24

QJ71C24-R2

GX Configurator -SC Version 2 is

ideal in these features!

Protocol FB Reduces programming steps.

Debugging Is improved by line monitor and communication test.

Features (1) QJ71C24N, QJ71C24N-R2, QJ71C24N-R4 Serial Communication Modules (a) Upto 230,400 bps transmission speed The total speed for 2 channels is now 230,400 bps. *1 Thus, using 2 channels simultaneously enables high-speed communication at a maximum speed of 115,200 bps for each channel. *1 230,400 bps is available only for the CH1 side.

(b) Support for circuit trace and communication test of GX Configurator-SC Version 2 GX Configurator-SC Version 2 together with the QJ71C24N (-R2/R4) allows the circuit trace function to monitor the send/receive data. The communication test function of GX Configurator-SC Version 2 also reduces debugging steps.

(2) GX Configurator-SC Version 2 The GX Configurator-SC Version 2 utility software makes communication control programming and debugging easier for the QJ71C24N (-R2/R4). *2 *2 The QJ71C24 and QJ71C24-R2 are also supported. (See “GX Configurator-SC Version 2 and Functional Range applicable models.”)

(a) Protocol FB function [1] Function blocks (FB) reduce communication control program steps. Without creating complicated sequence programs, equivalent function block programs can be created only by making simple on-screen settings. By incorporating the created function blocks into existing sequence programs, programming steps can be reduced.

GX Configurator-SC Version2

(Including Protocol FB Function)

Set packet information, packet data and PLC information on each screen.

Convert to FB

GX Developer Version8

Paste a function block from the project tree to a program by drag and drop.

[2] Support for function blocks to communicate with controllers manufactured by other companies Controllers manufactured by other companies are supported by providing function blocks preset with the packet information, packet data, and PLC information required for communication. This eliminates the requirement for any additional special settings.

1

(b) Debug function Debugging work at system startup can be simplified by using the debug support function. [Circuit trace] [Status monitor]

Available for QJ71C24N (-R2/R4) only

Checks the module status.

Traces the send/receive packet data on a communication line and the status of the communication signal line.

PULL

QJ71C24N (-R2/R4)

External device

[Communication test] Available for QJ71C24N (-R2/R4) only

Tests the communication by sending user-specified packet data to the external device.

GX Configurator-SC Version2

Serial Communication Modules Function List (1) Serial communication module basic functions Description

Function Communication QnA compatible 2C/3C/4C frame by MC protocol A compatible 1C frame

Reads/writes the PLC CPU data from/to the external device.

Communication by Non Procedure protocol Sends/receives data using the protocol format of the external device. Communication by bidirectional protocol Connection to PC running GX Developer

Sends/receives data using the message format and transmission control procedure for the bidirectional protocol between the PLC CPU and external device. Performs programming, monitoring and testing of the PLC CPU.

(2) Serial communication module application functions Function Data transmission by PLC CPU monitoring function Data communication by modem function Remote password check Call back

Description* Monitors the PLC CPU, and transmits the monitored information for notification. Performs data communication via a modem with the remote device.

MC

MC

Non Procedure

Prevents illegal access to the QCPU from the remote device.

Non Procedure

Bidirectional

GX Dev

MC

GX Dev

Enables to reconnect (call back) the line from the serial communication

GX Dev

module side after the line is connected from GX Developer.

Data reception by interrupt program

Enables data reception using interrupt programs while receiving another data. Non Procedure Bidirectional

Data communication

Registers the fixed format part of send/receive data as a user frame to

using the user frame

facilitate data communication.

Data communication by ASC -to-binary conversion Sends/receives ASC Data communication by specifying transparent code Mode switching NEW Send/receive data monitoring

data by ASC -to-binary conversion.

Enables to send/receive transmission control data as user data. Enables to switch the communication protocol of the serial communication module by the external device or PLC CPU. Enables to trace communication data. GX Configurator-SC screen displays communication timing waveform of the traced data.

MC

Non Procedure

Non Procedure

Bidirectional

Non Procedure

Bidirectional

MC

Non Procedure

Bidirectional

GX Dev

MC

Non Procedure

Bidirectional

GX Dev

* Protocols for application functions MC : MC protocol, Non Procedure : Non Procedure protocol, Bidirectional : Bidirectional protocol, GX Dev : GX Developer Each interface of the serial communication module operates independently. It is also possible to use two interfaces simultaneously.

2

Serial Communication Modules Performance Specifications

Item CH1 Interface CH2 Communication method Synchronization method

Data format

Access cycle

Error detection

QJ71C24N-R4

RS-422/485-compliance RS-232-compliance RS-232-compliance (D-sub 9P) (D-sub 9P) (2-piece plug-in connector socket block) RS-232-compliance RS-422/485-compliance RS-422/485-compliance (D-sub 9P) (2-piece terminal block) (2-piece plug-in connector socket block) Full duplex communication/half duplex communication Asynchronous method 50 14400

Transmission speed

Specifications QJ71C24N-R2

QJ71C24N

300 19200

600 28800

1200 38400

2400 57600

4800 115200

9600 230400

(bps)

• Transmission speed 230400 bps is available for only CH1. (Not available for CH2) • Total transmission speed of two interfaces is available up to 230400 bps. • Transmission speed of up to 115200 bps for each interface is available when two interface are used simultaneously.

1 Start bit 7/8 Data bit 1(vertical parity) or none Parity bit 1/2 Stop bit Processes one request during installed PLC CPU END processing. MC protocol • Number of scans that must be processed/number of link scans depends on the contents of the request. communication Nonprocedural protocol communication Sends each time a send request is issued. Can receive at any time. Bidirectional protocol communication Parity check For all protocol, select odd/even by the parameter when there is an error. Select by the parameter for MC protocol/Bidirectional protocol. Sum check code Select by the user frame for non-procedure protocol. RS-232

Transmission control

RS-422/485

DTR/DSR (ER/DR) control RS/CS control CD signal control DC1/DC3 (Xon/Xoff) control, DC2/DC4 control • DTR/DSR signal control and DC code control are selected by the user.

Line RS-232 configuration(*1) RS-422/485 Max. transmission RS-232 distance RS-422/485 (overall distance) Max. number of writes for flash ROM Number of occupied I/O points

1:1 1:1, 1:n, n:1, m:n 15 m (49.2 ft.) 1200 m (4592.4 ft.) (overall distance)

1:1 – 15 m (49.2 ft.) –

– 1:1, 1:n, n:1, m:n – 1200 m (4592.4 ft.) (overall distance)

100,000 writes to the same area 32 points per slot (I/O assignment: Intelli: 32 points) 7/0. 127 nP HRV-SV Outside diameter 8.5mm (0.33in.) or more RS-232 (Oki Electric Cable Co., Ltd. n:number of pairs) Recommended SPEV (SB)-MPC-0.2 x 3P Outside diameter approx. 6.5mm (0.26 in.) (Mitsubishi Cable Industries, LTD.) cable RS-422/485 (*2) SPEV(SB)-0.2 x 3P Outside diameter approx. 7.5mm (0.3 in.) (Mitsubishi Cable Industries, LTD.) Applicable connector for external wiring – 9 pin D-sub (male) screw type 0.31A 5V DC internal current consumption 0.39A 0.26A External dimensions 98(3.86in.)(H) x 27.4(1.08in.)(W) x 90(3.54in.)(D)[mm] Weight 0.20kg (0.44lb)

*1 Indicates possible combinations when connecting the PLC CPU and external devices (external device side: PLC CPU side). The total number of n and m+n is up to 32 stations. *2 Recommended cables SPEV (SB)-MPC-0.2 x 3P and SPEV (SB)-0.2 x 3P have the same electrical characteristics, but their external dimensions and internal wire colors are different.

3

External Dimensions (1) QJ71C24N R2+10

QJ71C24N RUN NEU. SD RD

CH1

ERR. NEU. SD RD

CH2

98(3.86)

CH1 RS-232

R2 (*2) SDA

1

SG SDB

3

(FG)

RDA

R1 (*1)

90(3.54)

5

(FG)

r1 (*3)

RDB

6 7

CH2 RS-422 /485

4.5(0.18)

27.4(1.08)

(Unit:mm(in))

*1 R1 (Bend radius near terminal block) : Cable diameter x 4 *2 R2 (Bend radius near connector) : Cable diameter x 4 *3 r1 (Bend radius near crimping terminal) : Connectable to the degree with no excessive bending of the cable

(2) QJ71C24N-R2 QJ71C24N-R2 RUN NEU. SD RD

CH1

ERR. NEU. SD RD

CH2

98(3.86)

R2+10

CH1 RS-232

R2 (*4) CH2 RS-232

QJ71C24N-R2

90(3.54) *4 R2 (Bend radius near connector)

4.5(0.18)

27.4(1.08)

(Unit:mm(in))

: Cable diameter x 4

(3) QJ71C24N-R4 QJ71C24N-R4 CH1

RUN NEU. SD RD

ERR. NEU. CH2 SD RD

CH1 RS-422/485 SDA

r2 (*6)

RDA RDB SG (FG) CH2 RS-422/485

98(3.86)

SDB

R3 (*5)

SDA SDB RDA RDB SG (FG)

QJ71C24N-R4

90(3.54)

11.5

27.4(1.08)

(0.45) *5 R3 (Bend radius near the plug-in socket block) *6 r2 (Bend radius near the wire connector)

: cable diameter x 4 : Connectable to the degree with no excessive bending of the cable

4

(Unit:mm(in))

GX Configurator-SC Version 2 Function List (1) Protocol FB function

NEW

Function Module setting Packet configuration setting Packet data information setting Sequence information setting Sequence FB conversion

(2) Debug function

Description Initial settings of the module. Sets the packet configuration of the external device. Sets the details for each configuration element of data to be transmitted/received. Sets communication sequence information for the serial communication module. Creates a protocol FB.

NEW

Function

Description Monitors send/receive packet data and traces the status of communication signal line. Performs a communication test from the serial communication module to the external device. Monitors the error status, communication signal line, etc. of the serial communication module.

Circuit trace Communication test Status monitor

(3) Intelligent function utility Function

Description Stores the operation status, error code etc., of the serial communication module into the internal device memory of the PLC CPU. Performs various settings for data communication with the external device. Performs the monitoring/testing of various setting values stored in buffer memory.

Auto refresh setting System setting Monitor/test

GX Configurator-SC Version 2 and Functional Range applicable models Model

Circuit trace

Debug support function Communication Communication test Status monitor timing waveform

Intelligent function utility

QJ71C24N, QJ71C24N-R2, QJ71C24N-R4 QJ71C24, QJ71C24-R2

GX Configurator-SC Version 2 Operating Environment Item

Peripheral device

Installation (Add-in) destination *1 Personal Computer CPU Required memory For installation Available hard disk space For operation Display resolution

Operating system

Add-in to GX Developer Version 8 or later *2 IBM-PC/AT compatible personal computer installed with applicable OS. See the following table "Operation Systems and Performance Required for PCs." 65 MB or more 20 MB or more 800 x 600 pixels or higher *3 Microsoft® Windows®95 Operating System (English version) Microsoft® Windows®98 Operating System (English version) Microsoft® Windows®Millennium Edition Operating System (English version) Microsoft® Windows NT® Workstation Operating System Version 4.0 (English version) Microsoft® Windows®2000 Professional Operating System (English version) Microsoft® Windows®XP Professional Operating System (English version) Microsoft® Windows®XP Home Edition Operating System (English version)

* 1 Install GX Configurator-SC to GX Developer Version 8 or later of the same language. However, when using only the intelligent function utility, it can be added into GX Developer Version 4 or later. Using the Japanese version of GX Developer together with the English version of GX Configurator-SC, or using the English version of GX Developer together with the Japanese version of GX Configurator-SC is not allowed. * 2 GX Configurator-SC is not applicable to GX Developer Version 3 or earlier. * 3 When Windows® XP Professional or Windows® XP Home Edition is used, large font sizes are not supported.

Operation Systems and Performance Required for PCs Performance required for Personal Computer CPU Required memory

Operating Software Windows®95 (Service pack 1 or more) Windows®98 Windows®Me Windows NT® Workstation 4.0 (Service pack 3 or more) Windows®2000 Professional Windows®XP Professional “XP Compatible Mode” and “Simplified Windows®XP Home Edition User Switching” are not supported.

5

Pentium®133MHz or higher Pentium®133MHz or higher Pentium®150MHz or higher Pentium®133MHz or higher Pentium®133MHz or higher Pentium®300MHz or higher Pentium®300MHz or higher

32MB or more 32MB or more 32MB or more 32MB or more 64MB or more 128MB or more 128MB or more

Product List (1) Serial Communication Modules Product name

Model QJ71C24N QJ71C24N-R2 QJ71C24N-R4

QJ71C24N serial communication module QJ71C24N-R2 serial communication module QJ71C24N-R4 serial communication module

(2) GX Configurator-SC Version 2 (a) Single license products Product name

Model

GX Configurator-SC Version2 (English Version) Single license product

SW2D5C-QSCU-E

Remarks CD-ROM (SW2D5C-QSCU-E) x 1 Including manual (English version) License agreement x1 Software license agreement x1 Software registration form x1

(b) Volume license products You can specify 2+ volume license. Please contact your local Mitsubishi service or representative for details. Product name GX Configurator-SC Version2 (English Version) Volume license product

Model

Remarks

SW2D5C-QSCU-EA

CD-ROM (SW2D5C-QSCU-E) x 1 Including manual (English version) License agreement x1 Software license agreement x1 Software registration form x n *1

*1 ”n” is the same as the number of licenses.

(c) Additional license products Product name

Model

GX Configurator-SC Version2 (English Version) Additional license product

SW2D5C-QSCU-EAZ

*1 ”n” is the same as the number of licenses.

6

Remarks License agreement Software license agreement Software registration form

x1 x1 x n *1

Manual Manual name Serial Communication Module User's Manual (Hardware) Q Corresponding Serial Communication Module User's Manual (Basic) Q Corresponding Serial Communication Module User's Manual (Application) Q Corresponding MELSEC Communication Protocol Reference Manual GX Configurator-SC Version2 Operating Manual (Protocol FB support function)

Manual supply status

IB/SH No. (following version or later manual)

Model code

Included with product

IB-0800008-D

13JQ31

Sold separately *1

SH-080006-F

13JL86

Sold separately

SH-080007-D

13JL87

Sold separately

SH-080008-D

13JF89

Sold separately *1

SH-080393E-A

13JU46

*1 This product includes the manual data in PDF format on the CD containing the software package. (Acrobat Reader, the software needed to view PDF format document on a personal computer is also included on the CD-ROM.) The printed material is available separately.

Microsoft, Windows, Windows NT are registered trademarks of Microsoft Corporation in the United States and other countries. Adobe and Acrobat are registered trademarks of Adobe Systems Incorporated. Pentium and Celeron are trademarks of Intel Corporation in the United States and other countries. Other company names and product names used in this document are the trademarks or registered trademarks of their respective owners. VS-VIEW Copyright(C)2001 ComponentOne LLC VS-FlexGrid Pro Copyright(C)2000 VideoSoft Corporation SPREAD Copyright(C)1996 FarPoint Technologies,Inc.

Country/Region Sales office

Tel/Fax

U.S.A

Mitsubishi Electric Automation Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061

Tel : +1-847-478-2100 Fax : +1-847-478-0328

Brazil

MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Av. Rio Branco, 123-15 ,and S/1507, Rio de Janeiro, RJ CEP 20040-005, Brazil

Tel : +55-21-221-8343 Fax : +55-21-221-9388

Taiwan

Germany

Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8 D-40880 Ratingen, GERMANY

Tel : +49-2102-486-0 Fax : +49-2102-486-717

U.K

Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Herts., AL10 8XB,UK

Tel : +44-1707-276100 Fax : +44-1707-278695

Italy

Mitsubishi Electric Europe B.V. Italian Branch Centro Dir. Colleoni, Pal. Perseo - Ingr.2 Via Paracelso 12, 20041 Agrate B., Milano, Italy

Tel : +39-039-60531 Fax : +39-039-6053312

Spain

Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rubi 76-80 08190-Sant Cugat del Valles, Barcelona, Spain

Tel : +34-935-653135 Fax : +34-935-891579

China

South Africa Circuit Breaker Industries LTD. Private Bag 2016, Isando 1600, Johannesburg, South Africa

Tel : +27-11-928-2000 Fax : +27-11-392-2354

Hong Kong

Tel : +852-2887-8870 Fax : +852-2887-7984

Ryoden Automation Ltd. 10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong

Ryoden International Shanghai Ltd. 3F Block5 Building Automation Instrumentation Plaza 103 Cao Bao Rd. Shanghai 200233 China

Tel : +86-21-6475-3228 Fax : +86-21-6484-6996

Setsuyo Enterprise Co., Ltd.

Tel : +886-2-2299-2499

6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan

Fax : +886-2-2299-2509

Korea

HAN NEUNG TECHNO CO., LTD. 1F Dong Seo Game Channel Bldg., 660-11,Deungchon-dong Kangsec-ku, Seoul, Korea

Tel : +82-2-3660-9552 Fax : +82-2-3664-8372

Singapore

Mitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02, Mitsubishi Electric Bulding Singapore 159943

Tel : +65-473-2480 Fax : +65-476-7439

Thailand

F. A. Tech Co.,Ltd. 898/28,29,30 S.V.City Building, Office Tower 2, Floor 17-18 Rama 3 Road, Bangkpongpang, Yannawa, Bangkok 10120

Tel : +66-2-682-6522 Fax : +66-2-682-6020

Indonesia

P.T. Autoteknindo SUMBER MAKMUR Jl. Muara Karang Selatan Blok a Utara No.1 Kav. No.11 Kawasan Industri/Pergudangan Jakarta-Utara 14440

Tel : +62-21-663-0833 Fax : +62-21-663-0832

India

Messung Systems Put,Ltd. Tel : +91-20-7128927 Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026,India Fax : +91-20-7128108

Australia

Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia

Tel : +61-2-9684-7777 Fax : +61-2-9684-7245

ELECTRIC CORPORATION HEAD OFFICE: 1-8-12,OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212,JAPAN NAGOYA WORKS: 1-14,YADA-MINAMI 5,HIGASHI-KU,NAGOYA,JAPAN

Specifications subject to change without notice. Printed in Japan on recycled paper.

0301(MEE)