415 V network voltage Varpact Classic power factor correction modules

Power factor correction and harmonic filtering Capacitors and banks 50 Hz network 400/415 V network voltage 0 Varpact Classic power factor correcti...
21 downloads 0 Views 408KB Size
Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Classic power factor correction modules

PB101972-68

Varpact power factor correction module form a prewired automatic compensation subassembly designed for fixing in stand­ alone cubicles or inside Main Low Voltage Switchboard.

PB101975-68

Varpact Classic "with cable connection".

Varpact Classic For no polluted network (Gh/Sn S 15 %) Varpact "with cable connection" 400 V (kvar) 12.5 25 30 40 45 50 60 80 90 100 120 6.25 + 12.5 12.5 + 12.5 10 + 20 15 + 15 20 + 20 15 + 30 30 + 30 20 + 40 25 + 50 30 + 60 40 + 40 45 + 45 50 + 50 40 + 80 60 + 60

Step

Reference

Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double Double Double Double Double Double Double Double Double Double Double Double

51775 51776 51777 51778 51779 51780 51781 51719 51782 51783 51784 51785 51786 51787 51788 51789 51790 51791 51792 51793 51794 51795 51729 51796 51797 51798

Weight (kg) 9 10 10 10 12 12 13 14 14.5 14.5 16 10.5 10.5 10.5 10.5 10.7 10.7 13.7 13.7 14.5 14.5 14.5 15.5 16 16 16

Varpact B "with busbar connection"

DB109720

Varpact Classic B "with busbar connection".

187

374

DB109684

Varpact Classic and Classic B dimensions.

(1) Fixing point.

437E3340_Ver2.0.fm/2

400 V (kvar) 12.5 25 30 40 45 50 60 80 90 100 120 6.25 + 12.5 12.5 + 12.5 10 + 20 15 + 15 20 + 20 15 + 30 30 + 30 20 + 40 25 + 50 30 + 60 40 + 40 45 + 45 50 + 50 40 + 80 60 + 60

Step

Reference

Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double Double Double Double Double Double Double Double Double Double Double Double

51950 51951 51952 51953 51954 51977 51978 51967 51979 51980 51981 51982 51983 51984 51985 51986 51987 51988 51989 51990 51991 51992 51970 51993 51994 51995

28 juillet 2006

Weight (kg) 12 13 13 13 15 15 16 17 17.5 17.5 19 13.5 13.5 13.5 13.5 13.7 13.7 16.7 16.7 17.5 17.5 17.5 18.5 19 19 19

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Classic power factor correction modules Technical data @ @ @ R R @ @ @ R R R R @ @ R R @ @ @

capacitor rated voltage: 415 V, three phase 50 Hz capacitance value tolerance: -5, +10 % insulation level: 0.69 kV withstand 50 Hz, 1 min: 3 kV maximum permissible overcurrent: 30 % max. (400 V) maximum permissible overvoltage: 10 % (8 hours over 24 hours as in IEC 60831) ambient temperature around the capacitor bank (electrical room): maximum temperature: 40 °C average temperature over 24 hours: 35 °C average annual temperature: 25 °C minimum temperature: -5 °C busbar withstand Isc : 35 kA losses: with cable connection: S 1.9 W/kvar (maximum current) with busbar connection: S 2,3 W/kvar (maximum current) degree of protection: front face direct contact protection device colour: RAL 7016 standards: IEC 60439-1, EN 60439-1, IEC 61921. Ref.

Accessories Connection module With fixing kit (600, 650, 700, 800 wide cubicle) Fastening crosspieces Set of 2 crosspieces Extension pieces For Prisma Plus cubicle W = 650 mm For universal cubicle W = 700 mm For universal cubicle W = 800 mm Circuit breaker protection Additionnal circuit breaker 60/63 A protection kit Additionnal circuit breaker 100 A protection kit Additionnal circuit breaker 160 A protection kit Additionnal circuit breaker 250 A protection kit

52800 51670 51635 51637 51639 Maximum reactive power Until 30 kvar From 31 to 50 kvar From 51 to 80 kvar From 81 to 120 kvar

51626 51627 51628 51629

Installation @ horizontal fixing in functional and universal cubicles, 400 and 500 mm deep R in cubicle W = 600 mm using fastening crosspieces R in cubicle W = 650, 700 and 800 mm using fastening crosspieces and extension pieces @ vertical fastening every 300 mm (maximum 5 modules) directly to cubicle uprights using sliding crosspieces or to intermediate upright support @ control circuit power supply: 230 V, 50 Hz.

28 juillet 2006

437E3340_Ver2.0.fm/3

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Comfort power factor correction modules

PB101972-68

Varpact power factor correction module form a prewired automatic compensation subassembly designed for fixing in stand­ alone cubicles or inside Main Low Voltage Switchboard.

Varpact Comfort "with cable connection".

Varpact Comfort For polluted network (15 % < Gh/Sn S 25 %) Varpact "with cable connection" 400 V (kvar) 15 20 25 30 35 45 60 70 90 15 + 15 15 + 30 15 + 45 30 + 30 30 + 60 45 + 45

Step

Reference

Single Single Single Single Single Single Single Single Single Double Double Double Double Double Double

51801 51803 51805 51807 51809 51811 51813 51816 51817 51818 51819 51820 51821 51822 51823

Weight (kg) 9 10 10 10 12 12 13 14.5 15 10 12.7 13.7 14.5 16.5 16.5

Varpact B "with busbar connection" PB101975-68

400 V (kvar) 15 20 25 30 35 45 60 70 90 15 + 15 15 + 30 15 + 45 30 + 30 30 + 60 45 + 45

DB109720

Varpact Comfort B "with busbar connection".

Step

Reference

Single Single Single Single Single Single Single Single Single Double Double Double Double Double Double

51740 51741 51742 51743 51744 51745 51746 51747 51748 51749 51750 51751 51752 51753 51754

187

374

DB109684

Varpact Comfort and Comfort B dimensions.

(1) Fixing point.

437E3340_Ver2.0.fm/4

28 juillet 2006

Weight (kg) 12 13 13 13 15 15 16 17.5 18 13 15.7 16.7 17.5 19.5 19.5

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Comfort power factor correction modules Technical data @ @ @ R R @ @ @ R R R R @ @ R R @ @ @

capacitor rated voltage: 480 V, three-phase 50 Hz capacitance value tolerance: -5, +10 % insulation level: 0.69 kV withstand 50 Hz, 1 min: 3 kV maximum permissible overcurrent: 50 % max. (400 V) maximum permissible overvoltage: 10 % (8 hours over 24 hours as in IEC 60831) ambient temperature around the capacitor bank (electrical room): maximum temperature: 40 °C average temperature over 24 hours: 35 °C average annual temperature: 25 °C minimum temperature: -5 °C busbar withstand Isc : 35 kA losses: with cable connection: S 2 W/kvar (maximum current) with busbar connection: S 2,4 W/kvar (maximum current) degree of protection: front face direct contact protection device colour: RAL 7016 standards: IEC 60439-1, EN 60439-1, IEC 61921. Ref.

Accessories Connection module With fixing kit (600, 650, 700, 800 wide cubicle) Fastening crosspieces Set of 2 crosspieces Extension pieces For Prisma Plus cubicle W = 650 mm For universal cubicle W = 700 mm For universal cubicle W = 800 mm Circuit breaker protection Additionnal circuit breaker 60/63 A protection kit Additionnal circuit breaker 100 A protection kit Additionnal circuit breaker 160 A protection kit Additionnal circuit breaker 250 A protection kit

52800 51670 51635 51637 51639 Maximum reactive power Until 30 kvar From 31 to 50 kvar From 51 to 80 kvar From 81 to 120 kvar

51626 51627 51628 51629

Installation @ horizontal fixing in functional and universal cubicles, 400 and 500 mm deep R in cubicle W = 600 mm using fastening crosspieces R in cubicle W = 650, 700 and 800 mm using fastening crosspieces and extension pieces @ vertical fastening every 300 mm (maximum 5 modules) directly to cubicle uprights using sliding crosspieces or to intermediate upright support @ control circuit power supply: 230 V, 50 Hz.

28 juillet 2006

437E3340_Ver2.0.fm/5

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Harmony power factor correction modules

PB101983-68

Varpact power factor correction module form a prewired automatic compensation subassembly designed for fixing in stand­ alone cubicles or inside Main Low Voltage Switchboard.

Varpact Harmony For highly polluted network (25 % < Gh/Sn S 50 %) Varpact "with cable connection" Tuning order 2.7 (135 Hz)

3.8 (190 Hz)

4.3 (215 Hz)

Varpact Harmony "with cable connection".

400 V (kvar) 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50

Step

Reference

Double Double Double Single Single Single Double Double Double Single Single Single Double Double Double Single Single Single

51916 51917 51918 51919 51920 51921 51925 51926 51927 51928 51929 51930 51934 51935 51936 51937 51938 51939

Step

Reference

Double Double Double Single Single Single Double Double Double Single Single Single Double Double Double Single Single Single

51757 51759 51761 51763 51765 51767 51653 51654 51655 51656 51657 51658 51501 51503 51505 51509 51511 51512

Weight (kg) 23 31.5 38.5 23.5 35.5 46.5 21.5 30 37 22 34 45 21.5 30 37 22 34 45

Varpact B "with busbar connection" PB101982-68

Tuning order 2.7 (135 Hz)

3.8 (190 Hz)

Varpact Harmony B "with busbar connection".

DB110596

DB110597

4.3 (215 Hz)

400 V (kvar) 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50 6.25 + 6.25 6.25 + 12.5 12.5 + 12.5 12.5 25 50

Varpact Harmony dimensions.

437E3340_Ver2.0.fm/6

28 juillet 2006

Weight (kg) 26 34.5 41.5 26.5 38.5 49.5 24.5 33 40 25 37 48 24.5 33 40 25 37 48

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Varpact Harmony power factor correction modules Technical data @ @ @ @ R R @

capacitor rated voltage: 480 V, three-phase 50 Hz

tuning order: 2.7 (135 Hz) - 3.8 (190 Hz) - 4.3 (215 Hz)

capacitance value tolerance: -5, +10 %

insulation level:

0.69 kV

withstand 50 Hz, 1 min : 3 kV

maximum permissible overloads:

Tuning order Overcurrent (max) Overvoltage

@ R R R R @ @ @ @ @

2.7 (135 Hz) 3.8 (190 Hz) 4.3 (215 Hz) 12 % under 400 V 19 % under 400 V 30 % under 400 V 10 % (8 hours over 24 hours as in IEC 60831)

ambient temperature around the capacitor bank (electrical room): maximum temperature: 40 °C average temperature over 24 hours: 35 °C average annual temperature: 25 °C minimum temperature: -5 °C busbar withstand Isc : 35 kA losses: S 8 W/kvar degree of protection: front face direct contact protection device colour: RAL 7016 standard: IEC 60439-1, EN 60439-1, IEC 61921.

Accessories

Ref.

Connection module With fixing kit (600, 650, 700, 800 wide cubicle)

52800

Installation @ horizontal fixing in functional and universal cubicles, 400 and 500 mm deep, fixing in cubicle W = 650, 700 and 800 mm using fastening crosspieces supplied @ vertical fixing every 300 mm (maximum 5 modules) directly to cubicle uprights using sliding crosspieces or to intermediate upright support @ control circuit power supply: 230 V, 50 Hz.

28 juillet 2006

437E3340_Ver2.0.fm/7

Power factor correction

and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage Accessories for Varpact power factor correction modules

E72598

Connection module

Connection module IP00

PB100067-68

a: cubicle L = 600 b: cubicle L = 650 or 700 c: cubicle L = 800

(Ref. 52800) It is used to connect: @ the power and control cables for the power factor correction module contactors (maximum five power factor correction modules) @ the cubicle supply cables. It is supplied with: @ 4 crosspieces @ 2 extension pieces O 3 power connection bars (800 A max.), marked L1, L2, L3 P Voltage transformer supplying the contactor coils 400/230 V, 250 VA Q Control circuit safety fuses R Contactor control distribution terminal block S sliding crosspieces for mounting in cubicles 400 and 500 mm deep T Extension pieces for mounting in cubicles 650, 700 or 800 mm wide U Power factor correction module connection: 5 holes Ø10 per phase V Customer's incoming cable connection: 2 x M12 bolts per phase. To make it easier to connect the supply cables, we recommended that the connection module be installed at least 20 cm from the ground.

Fastening crosspieces for Varpact Classic and Comfort (Ref. 51670) Specially designed horizontal crosspieces allow easy installation of the power factor correction modules in all types of functional and universal cubicles 400 ou 500 mm deep. The crosspieces automatically ensure that the module is positioned correctly at the right depth and maintain a distance of 55 mm between the modules. The crosspieces are sold in pairs and must be ordered separately.

2 fastening crosspieces (ref. 51670)

PB100068-68

Extension pieces for cubicles W = 700 and W = 800 with Varpact Classic and Comfort (Ref. 51637 and 51639) They are used to extend the power factor correction modules for use in cubicles

700 and 800 mm wide.

The extension pieces are supplied with the 4 screws required to attach

them to the module.

Extension pieces for Prisma Plus cubicle W = 650 with Varpact Classic and Comfort (Ref. 51635) It allows the module to be attached directly to the Prisma Plus cubicle uprights.

The extension piece is supplied with the 4 screws required to attach it to the module.

Extension pieces for cubicles

W = 650 (ref. 51635)

W = 700 (ref. 51637)

W = 800 (ref. 51639)

437E3340_Ver2.0.fm/8

28 juillet 2006

0

Power factor correction and harmonic filtering

Capacitors and banks 50 Hz network 400/415 V network voltage

0

Accessories for Varpact power factor correction modules

PB100072-68

Circuit breaker kit for Varpact Classic and Comfort (Ref. 51626, 51627, 51628 and 51629) It allows to ensure individual and visible circuit breaking of each capacitor steps.

Retrofit kit

(Ref. 51617, 51619, 51621 and 51633)

Set of pieces using for installation and connection of Varpact in functionnal and universal existing cubicles. It is necessary to choose a Varpact module and to order separately associated retrofit kit. Retrofit kit Ref. 51617 51619 On request 51633

PB100071-68

Circuit breaker kit

For P400 power factor correction module For P400 DR power factor correction module For L600 power factor correction module For Rectimat 2 capacitor bank in cubicle standard and H type

Retrofit kit

28 juillet 2006

437E3340_Ver2.0.fm/9