Isolating switching amplifier 2-channel IM1-22EX-R/24VDC

The 2-channel isolating switching amplifier IM1-22EX-R/24VDC is equipped with intrinsically safe input circuits. Sensors according to EN 60947-5-6 (NAMUR) can be connected to the device or potential-free contactors. The output circuits feature 2 relays, each with one NO contact.

Six front panel switches are available to set the output mode separately for each channel (NO/NC mode), as well as to enable/disable wire-break (WB) and short-circuit (SC) monitoring separately. When using mechanical contacts, wire-break and short-circuit monitoring must be switched off or the contact must be wired with resistors (II) (see circuit diagram).



ATEX, FM



Installation in zone 2



Adjustable output mode (NO/NC)



Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable)

The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and 2 below light yellow to indicate the switching status of the corresponding output. In the event of an input circuit error, the associated 2-color LED turns red, provided the input circuit monitoring function is activated. Thereupon the corresponding output relay drops out.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/24VDC

Dimensions

Type code Ident no.

IM1-22EX-R/24VDC 7541210

Flammability class acc. to UL 94

V-0

Nominal voltage Operating voltage range Power loss, typical

24 VDC 10…30 VDC ð 0.99 W

NAMUR No-load voltage Short-circuit current Input resistance Cable resistance Switch-on threshold: Switch-off threshold: Wire breakage threshold Short-circuit threshold

EN 60947-5-6 8 VDC 8 mA 1 kò ð 50 ò 1.55 mA 1.75 mA ð 0.1 mA ï 6 mA

Output circuits (digital) Relay switching voltage Switching current per output Switching capacity per output Switching frequency Contact quality

2 x relays (NO) ð 250 VAC/120 VDC ð2A ð 500 VA/60 W ð 10 Hz AgNi, 3µ Au

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

PTB 00 ATEX 2033 II (1) G, II (1) D [Ex ia Ga] IIC; [Ex ia Da] IIIC terminal connection 1…6 ð 9.6 V ð 21.4 mA ð 26 mW linear Ci negligibly small, Li negligibly small Ex ia Lo [mH] 1 Co [µF] 1,1 (2 Klemmen) Co [µF] 1,1 (3 Klemmen oder mehr

Output relay – Electrical lifetime

IIC 5 0,84

1 6,2

IIIC 5 4,4

0,8

6,2

4,3

MTTF

400 years acc. to SN 29500 (Ed. 99) 40 °C

State/ Fault

2 x yellow / red

Mechanical Data Protection class Storage temperature Relative humidity Dimensions Weight Mounting instruction Housing material Electrical connection Terminal cross-section Tightening torque

IP20 -40…+80°C ð 95 % 104 x 18 x 110 mm 145 g For mounting on DIN rail or mounting panel polycarbonate/ABS 4 x 3-pole removable terminal blocks, reverse polarity protected, screw connection 1 x 2.5 mm / 2 x 1.5 mm 0.5 Nm 2

2

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/24VDC

Accessories Type code

Ident no.

Description

IM-CC-3X2BU/2BK

6900475

Cage clamp terminals for IM modules ( Ex-devices with 18

Dimension drawing

mm overall width); includes: 2 pcs. 3-pin blue terminals and 2 pcs. 3-pin black terminals.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/K51

The 2-channel isolating switching amplifier IM1-22EX-R/K51 is equipped with intrinsically safe input circuits. Sensors according to EN 60947-5-6 (NAMUR) or potential-free contact transmitters can be connected to the device. The output circuits feature 2 relays, each with one NO contact.

You can set each channel separately to work/ closed current, i.e. NO/NC mode and multiply signals via 3 switches at the front. The switching state of channel 1 is thereby transmitted to the outputs 1 and 2. You can also set the output mode separately for each channel. The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and 2 below light yellow to indicate the output switching status. In the event of an input circuit error, the associated 2-color LED turns red, provided the input circuit monitoring function is activated. Thereupon the correspondent output relay drops out.



ATEX, IECEx, CSA, FM, UL, NEPSI, -KOSHA, GOST



Installation in zone 2



2 relay outputs (NO)



Adjustable current flow (NO/NC)



Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable)



Test voltage 4.0 kV



Complete galvanic isolation

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/K51 Type code Ident no.

IM1-22EX-R/K51 7541238

Flammability class acc. to UL 94

V-0

Nominal voltage Operating voltage Frequency Operating voltage range Power consumption

Universal voltage supply unit 20…250 VAC 40…70 Hz 20…125 VDC ð 3 W

NAMUR No-load voltage Short-circuit current Input resistance Cable resistance Switch-on threshold: Switch-off threshold: Wire breakage threshold Short-circuit threshold

EN 60947-5-6 8.2 VDC 8.2 mA 1 kò ð 50 ò 1.55 mA 1.75 mA ð 0.1 mA ï 6 mA

Output circuits (digital) Relay switching voltage Switching current per output Switching capacity per output Switching frequency Contact quality

2 x relays (NO) ð 250 VAC/120 VDC ð2A ð 500 VA/60 W ð 10 Hz AgNi, 3µ Au

Galvanic isolation Test voltage

4.0 kV

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

Load curve

Output relay – Electrical lifetime

TÜV 04 ATEX 2553 II (1) G, II (1) D [Ex ia Ga] IIC; [Ex ia Da] IIIC terminal connection: 1+4 / 2+5 ð 9.6 V ð 11 mA ð 26 mW linear Li = 65 µH, Ci negligibly small Ex ia Lo [mH] Co [µF]

1

5

IIC 10

2

IIB 10

20

1,1

0,83

0,74

5,2

3,8

3,4

TÜV 06 ATEX 552968 X II 3 G Ex nA nC [ic Gc] IIC/IIB T4 Gc terminal connection: 1+4 / 2+5 ð 9.6 V ð 11 mA ð 26 mW linear Li = 65 µH, Ci negligibly small Ex ic Lo [mH] Co [µF]

IIC

IIB

1

5

10

1

5

10

1.9

1.4

1.2

11

7.5

6.6

MTTF

400 years acc. to SN 29500 (Ed. 99) 40 °C

Indication Operational readiness Switching state Error indication

green yellow red

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/K51 Mechanical Data Protection class Ambient temperature Storage temperature Relative humidity Dimensions Weight Mounting instruction Housing material Electrical connection Terminal cross-section Tightening torque

IP20 -25…+70 °C -40…+80°C ð 95 % 104 x 18 x 110 mm 147 g For mounting on DIN rail or mounting panel polycarbonate/ABS 4 x 3-pole removable terminal blocks, reverse polarity protected, screw connection 1 x 2.5 mm / 2 x 1.5 mm 0.5 Nm 2

2

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/K51

Accessories Type code

Ident no.

Description

IM-CC-3X2BU/2BK

6900475

Cage clamp terminals for IM modules ( Ex-devices with 18

Dimension drawing

mm overall width); includes: 2 pcs. 3-pin blue terminals and 2 pcs. 3-pin black terminals.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R

The 2-channel isolating switching amplifier IM1-22EX-R is equipped with an intrinsically safe input circuit. Sensors according to EN 60947-5-6 (NAMUR) can be connected to the device or potential-free contactors. The output circuits feature 2 relays, each with one NO contact.

Six front panel switches are available to set the output mode separately for each channel (NO/NC mode), as well as to enable/disable wire-break (WB) and short-circuit (SC) monitoring separately. When using mechanical contacts, wire-break and short-circuit monitoring must be switched off or the contact must be wired with resistors (II) (see circuit diagram).



ATEX, IECEx, CSA, FM, UL, NEPSI, -KOSHA, GOST



Installation in zone 2



2 relay outputs (NO)



Adjustable current flow (NO/NC)





Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable) Complete galvanic isolation

The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and 2 below light yellow to indicate the output switching status. In the event of an input circuit error, the associated 2-color LED turns red, provided the input circuit monitoring function is activated. Thereupon the correspondent output relay drops out.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R

Dimensions

Type code Ident no.

IM1-22EX-R 7541231

Flammability class acc. to UL 94

V-0

Nominal voltage Operating voltage Frequency Operating voltage range Power consumption Power loss, typical

Universal voltage supply unit 20…250 VAC 40…70 Hz 20…125 VDC ð 3 W ð 0.98 W

NAMUR No-load voltage Short-circuit current Input resistance Cable resistance Switch-on threshold: Switch-off threshold: Wire breakage threshold Short-circuit threshold

EN 60947-5-6 8.2 VDC 8.2 mA 1 kò ð 50 ò 1.55 mA 1.75 mA ð 0.1 mA ï 6 mA

Output circuits (digital) Relay switching voltage Switching current per output Switching capacity per output Switching frequency Contact quality

2 x relays (NO) ð 250 VAC/120 VDC ð2A ð 500 VA/60 W ð 10 Hz AgNi, 3µ Au

Galvanic isolation Test voltage

2.5 kV

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Rated voltage Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

Approval MTTF

Output relay – Electrical lifetime

TÜV 04 ATEX 2553 II (1) G, II (1) D [Ex ia Ga] IIC; [Ex ia Da] IIIC terminal connection: 1+4 / 2+5 ð 9.6 V ð 11 mA ð 26 mW linear 250 V Li = 65 µH, Ci negligibly small Ex ia Lo [mH] Co [µF]

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

Load curve

1

5

IIC 10

2

IIB 10

20

1,1

0,83

0,74

5,2

3,8

3,4

TÜV 06 ATEX 552968 X II 3 G Ex nA nC [ic Gc] IIC/IIB T4 Gc terminal connection: 1+4 / 2+5 ð 9.6 V ð 11 mA ð 26 mW linear Li = 65 µH, Ci negligibly small Ex ic Lo [mH] Co [µF]

IIC

IIB

1

5

10

1

5

10

1.9

1.4

1.2

11

7.5

6.6

SIL 2 acc. to EXIDA FMEDA 400 years acc. to SN 29500 (Ed. 99) 40 °C

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R Indication Operational readiness Switching state Error indication Mechanical Data Protection class Ambient temperature Storage temperature Relative humidity Dimensions Weight Mounting instruction Housing material Electrical connection Terminal cross-section Tightening torque

green yellow red

IP20 -25…+70 °C -40…+80°C ð 95 % 104 x 18 x 110 mm 154 g For mounting on DIN rail or mounting panel polycarbonate/ABS 4 x 3-pole removable terminal blocks, reverse polarity protected, screw connection 1 x 2.5 mm / 2 x 1.5 mm 0.5 Nm 2

2

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R

Accessories Type code

Ident no.

Description

IM-CC-3X2BU/2BK

6900475

Cage clamp terminals for IM modules ( Ex-devices with 18

Dimension drawing

mm overall width); includes: 2 pcs. 3-pin blue terminals and 2 pcs. 3-pin black terminals.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/230VAC

The 2-channel isolating switching amplifier IM1-22EX-R/230VAC is equipped with intrinsically safe input circuits. Sensors according to EN 60947-5-6 (NAMUR) or potential-free contact makers can be connected to the device. The output circuits feature 2 relays, each with one NO contact.

Six front panel switches are available to set the output mode separately for each channel (NO/NC mode), as well as to enable/disable wire-break (WB) and short-circuit (SC) monitoring separately. When using mechanical contacts, wire-break and short-circuit monitoring must be switched off or the contacts must be wired to resistors (II) (see circuit diagram).



ATEX



Installation in zone 2



Adjustable output mode (NO/NC)



Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable)

The Pwr LED lights green to indicate operational readiness. The 2-color LEDs 1 and 2 below light yellow to indicate the switching status of the corresponding output. The same LEDs turn red in the event of an input circuit error, provided the input circuit monitoring function is switched on. Thereupon the associated output relay drops out.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/230VAC

Type code Ident no.

IM1-22EX-R/230VAC 7541211

Flammability class acc. to UL 94

V-0

Nominal voltage Operating voltage Frequency Power consumption

230 VAC 196…253 VAC 48…62 Hz ð 2 VA

NAMUR No-load voltage Short-circuit current Input resistance Cable resistance Switch-on threshold: Switch-off threshold: Wire breakage threshold Short-circuit threshold

EN 60947-5-6 8 VDC 8 mA 1 kò ð 50 ò 1.55 mA 1.75 mA ð 0.1 mA ï 6 mA

Output circuits (digital) Relay switching voltage Switching current per output Switching capacity per output Switching frequency Contact quality

2 x relays (NO) ð 250 VAC/120 VDC ð2A ð 500 VA/60 W ð 10 Hz AgNi, 3µ Au

Ex approval acc. to conformity certificate Application area Protection type Max. values: Max.output voltage Uo Max. output current Io Max. output power Po Characteristic Internal inductance/capacitance Li/Ci External inductance/capacitance Lo/Co

PTB 00 ATEX 2033 II (1) G, II (1) D [Ex ia Ga] IIC; [Ex ia Da] IIIC terminal connection 1…6 ð 9.6 V ð 21.4 mA ð 26 mW linear Ci negligibly small, Li negligibly small Ex ia Lo [mH] 1 Co [µF] 1,1 (2 Klemmen) Co [µF] 1,1 (3 Klemmen oder mehr

Output relay – Electrical lifetime

IIC 5 0,84

1 6,2

IIIC 5 4,4

0,8

6,2

4,3

MTTF

400 years acc. to SN 29500 (Ed. 99) 40 °C

State/ Fault

2 x yellow / red

Mechanical Data Protection class Ambient temperature Storage temperature Relative humidity Dimensions Weight Mounting instruction Housing material Electrical connection Terminal cross-section Tightening torque

IP20 -25…+70 °C -40…+80°C ð 95 % 104 x 18 x 110 mm 148 g For mounting on DIN rail or mounting panel polycarbonate/ABS 4 x 3-pole removable terminal blocks, reverse polarity protected, screw connection 1 x 2.5 mm / 2 x 1.5 mm 0.5 Nm 2

2

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Isolating switching amplifier 2-channel IM1-22EX-R/230VAC

Accessories Type code

Ident no.

Description

IM-CC-3X2BU/2BK

6900475

Cage clamp terminals for IM modules ( Ex-devices with 18

Dimension drawing

mm overall width); includes: 2 pcs. 3-pin blue terminals and 2 pcs. 3-pin black terminals.