2013 5:02 PM

National Fire Protection Association Report 1 of 71 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Second Revision No. 16-NF...
Author: Ethelbert Cobb
81 downloads 2 Views 487KB Size
National Fire Protection Association Report

1 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 16-NFPA 30B-2013 [ Global Comment ]

In Tables 6.3.2.7(a) through 6.3.2.7(l), make the following changes: (1) Under column heading "Response / Nominal Temperature Rating, in each row indicating ESFR sprinklers, change “QR” to “FR”. (2) Add “FR = Fast Response” to legend at bottom of every table.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 21:37:05 EDT 2013

Committee Statement Committee Statement:

The revisions implemented by Second Revision No. 16 reflect current terminology used in NFPA 13.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

2 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 17-NFPA 30B-2013 [ Global Comment ]

In Chapter 7, wherever the phrase “Level 2 and level 3 aerosol products” appears, replace with the phrase “aerosol cooking spray products, Level 2 aerosol products, and Level 3 aerosol products”.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 21:48:49 EDT 2013

Committee Statement Committee Statement:

This Second Revision reflects the fact that the fire behavior of aerosol cooking spray products is the same as that of Level 2 and Level 3 aerosol products.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

3 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 5-NFPA 30B-2013 [ Section No. 1.7 ]

1.7* Classification of Aerosol Products in Metal Containers of Capacity Less Than or Equal Not More Than to 1000 ml (33.8 fl oz) and in Plastic or Glass Containers of Capacity Less Than or Equal to Not More Than 118 ml (4 fl oz). See Annex E . 1.7.1 Aerosol products shall be classified by means of the calculation of their chemical or theoretical heats of combustion and shall be designated Level 1, Level 2, or Level 3 in accordance with 1.7.2 through 1.7.5.2 and Table 1.7.1 . Table 1.7.1 Aerosol Classification If the chemical heat of combustion is

Aerosol Classification Level

>



0

20 kJ/g (8,600 Btu/lb)

1

20 kJ/g (8,600 Btu/lb)

30 kJ/g (13,000 Btu/lb)

2

30 kJ/g (13,000 Btu/lb)



3

1.7.1.1 In lieu of classification by means of the chemical heats of combustion, aerosol products shall be permitted to be classified by means of data obtained from properly conducted full-scale fire tests that utilize a 12-pallet test array. Exception: This shall not apply to aerosol cooking spray products. (See 1.7.5.) 1.7.1.2 The fire tests shall be conducted at an approved testing laboratory. (See Annex C for information on the 12-pallet test array.) 1.7.2 Level 1 Aerosol Products. Level 1 aerosol products are shall be defined as those products with a total chemical heat of combustion that is less than or equal to 20 kJ/g (8600 Btu/lb). 1.7.3 Level 2 Aerosol Products. Level 2 aerosol products are shall be defined as those products with a total chemical heat of combustion that is greater than 20 kJ/g (8600 Btu/lb), but less than or equal to 30 kJ/g (13,000 Btu/lb). 1.7.4 Level 3 Aerosol Products. Level 3 aerosol products are shall be defined as those products with a total chemical heat of combustion that is greater than 30 kJ/g (13,000 Btu/lb). 1.7.5 Aerosol Cooking Spray Products. Aerosol cooking spray products are those aerosol products designed to deliver a vegetable oil or a solid or nonflammable liquid to reduce sticking on cooking and baking surfaces, or to be applied to food, or both. These products have a chemical heat of combustion that is greater than 20 kJ/g (8600 BTU/lb) and contain not more than 18 percent by weight of flammable propellant. 1.7.5.1 If the aerosol cooking spray product has a chemical heat of combustion that does not exceed 20 kJ/g (8600 Btu/lb), it shall be considered a Level 1 aerosol product. 1.7.5.2 If the aerosol cooking spray product contains more than 18 percent by weight of flammable propellant, it shall be classified in accordance with its chemical heat of combustion, as set forth in Table 1.7.1.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address:

12/6/2013 5:02 PM

National Fire Protection Association Report

4 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

City: State: Zip: Submittal Date:

Thu Oct 10 16:54:16 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 5 incorporates classification schemes for aerosol cooking spray products and for aerosol products in plastic containers of greater than 118 ml capacity. These concepts were put forward by means of Committee Input No. 19 at the First Draft stage. No negative or adverse comments were received.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

5 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 6-NFPA 30B-2013 [ Section No. 1.8 ]

1.8 Classification of Aerosol Products in Plastic Containers Larger Than 118ml (4 fl oz) and Smaller Than 1000 ml (33.8 oz) . Storage and display of aerosol products in plastic containers larger than 118 ml (4 fl oz) are covered in Section 6.4 . 1.8.1 Plastic Aerosol 1 Products. Plastic aerosol 1 products shall be defined as those that meet one of the following criteria: (1) The base product has no fire point when tested in accordance with ASTM D 92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester , and the propellant is nonflammable . (2) The base product does not exhibit sustained combustion when tested in accordance with 49 CFR 173, Appendix H, “Method of Testing for Sustained Combustibility," or the UN Recommendations on the Transport of Dangerous Goods , and the propellant is nonflammable. (3) * The base product contains not more than 20 percent by volume (15.8 percent by weight) of ethanol or propanol, or mixtures thereof in an aqueous mix, and the propellant is nonflammable. (4) * The base product contains not more than 4 percent by weight of an emulsified liquefied flammable gas propellant within an aqueous base, said propellant to remain emulsified for the life of the product. Where such propellant is not permanently emulsified then the propellant shall be nonflammable. 1.8.2 Plastic Aerosol X Products. Plastic aerosol X products shall be defined as those products that do not meet any of the criteria provided in 1.8.1.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:22:13 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 6 deletes former Section 1.8 entirely because the information to which it directed the user is no longer in Section 6.4. The information has been revised and incorporated into new Section 1.8, as shown in Second Revision No. 5.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

6 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 7-NFPA 30B-2013 [ Section No. 1.9 ]

1.9 Marking of Packages of Aerosol Products. 1.9.1 Manufacturers of aerosol products shall ensure that all cartons or packages of aerosol products are identified on at least one exterior side with the classification of the aerosol products contained therein, in accordance with Section 1.7 and Section 1.8 . 1.9.2 Cartons or packages containing aerosol products in metal containers or glass and plastic containers 118 ml (4 fl oz) or less shall be clearly marked as follows: Level _____ Aerosols 1.9.3 Cartons or packages containing aerosol cooking spray products in metal containers shall be clearly marked as follows: Aerosol Cooking Spray 1.9.4 Cartons or packages containing aerosol products in plastic containers greater than 118 ml (4 fl oz) shall be clearly marked on the exterior of the carton as follows: Plastic Aerosol Container 1 (or X)

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:25:04 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 7 adds the necessary provisions for marking of cartons of aerosol cooking spray products and for aerosol products in plastic containers. These concepts were put forward by means of Committee Input No. 19 at the First Draft stage. No negative or adverse comments were received.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

7 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 40-NFPA 30B-2013 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2012 2015 edition. NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 edition. NFPA 30, Flammable and Combustible Liquids Code, 2012 2015 edition. NFPA 68, Standard on Explosion Protection by Deflagration Venting, 2007 2013 edition. ® NFPA 72 , National Fire Alarm and Signaling Code, 2013 edition. NFPA 77, Recommended Practice on Static Electricity, ® ® NFPA 5000 , Building Construction and Safety Code , 2012 2015 edition.

Submitter Information Verification Submitter Full Name: Robert Benedetti Organization:

National Fire Protection Assoc

Street Address: City: State: Zip: Submittal Date:

Tue Nov 05 13:03:40 EST 2013

Committee Statement Committee Statement: This Second Revision updates the adoption dates of citations to extract text publications. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

8 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 1-NFPA 30B-2013 [ Section No. 3.3.2 ]

3.3.2* Aerosol Container. A pressurized metal can or plastic container, up to a maximum size of 1000 ml (33.8 fl oz), or a pressurized glass, container stone, or metal bottle , up to a maximum size of 118 ml (4 fl oz), that is designed and intended to dispense its contents an aerosol .

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Sep 19 13:56:56 EDT 2013

Committee Statement Committee The original definition was identical to that in NFPA 5000, except for the units being inverted. The Statement: NFPA 5000 definition reads as follows: A metal can or plastic container, up to a maximum size of 33.8 fl oz (1000 ml), or a glass or plastic bottle, up to a maximum size of 118 ml (4 fl oz), that is designed and intended to dispense an aerosol. The technical committee should return to the original definition for uniformity of concepts and terms. If the committee wants to be unique it should add some qualifier (such as "for the purposes of manufacture and storage of aerosol products" or draft a public input or comment to NFPA 5000 for them to change. This comment is being made on behalf of the NFPA Glossary Committee on Terminology, set up for the purpose of obtaining uniformity in definitions throughout the NFPA system. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

9 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 9-NFPA 30B-2013 [ New Section after 3.4.4 ]

3.4.5 Maximum Allowable Operating Pressure (MAOP). The maximum pressure to which a system can be subjected without exceeding the pressure rating of any of its component parts.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:45:35 EDT 2013

Committee Statement Committee Statement:

This definition is necessary for the proper understanding of Section 5.13 and relates to amendments made to that section via Second Revision No. 24.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

10 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 10-NFPA 30B-2013 [ Section No. 3.4.5 ]

3.4.6 Propellant Charging Pump (Charging Pump). A pump used to boost the liquid propellant to the pressure required by the propellant filler, usually 2070 kPa to 8280 kPa (300 psi to 1200 psi). Tank farm transfer pumps normally supply the suction side of the propellant charging pump at pressures of 100 to 690 kPa (15 to 100 psi) above the propellant's vapor pressure.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:48:46 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 10 deletes material that will be reintroduced as a stand-alone definition by Second Revision No. 11.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

11 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 11-NFPA 30B-2013 [ New Section after 3.4.11 ]

3.4.13 Tank Farm Transfer Pump. A pump used to transfer liquid propellant from storage tanks to the suction side of the propellant charging pump.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:52:28 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 11 provides a stand-alone definition for "Tank Farm Transfer Pump", which has heretofore been described as part of the definition of “Propellant Charging Pump” (formerly Subsection 3.4.5). The Technical Committee determined that this text should be a self-standing definition.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

12 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 13-NFPA 30B-2013 [ New Section after 3.4.12 ]

3.4.15 Under-the-Cup (UTC) Propellant Filler. A machine that evacuates the aerosol container, fills propellant under the loose valve cup, and crimps the valve cup in place in sequence on one machine.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 18:01:52 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 13 adds a definition that relates to applicability of Subsection 5.13.2 to this type of propellant filler. See Second Revision No. 23.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

13 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 38-NFPA 30B-2013 [ Section No. 5.4.4 [Excluding any Sub-Sections] ] Aerosol product container test baths and button tippers shall be enclosed and provided with mechanical exhaust ventilation.

Submitter Information Verification Submitter Full Name: Robert Benedetti Organization:

National Fire Protection Assoc

Street Address: City: State: Zip: Submittal Date:

Fri Oct 18 14:05:48 EDT 2013

Committee Statement Committee Statement:

This Second Revision amends terminology to correlate with new definitions accepted in Chapter 3.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

14 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 14-NFPA 30B-2013 [ Section No. 5.5 ]

5.5 Electrical Equipment. Electrical equipment and wiring in flammable propellant charging and pump rooms shall be suitable for Class I, Division 1 or Class I, Zone 1 locations in accordance with Articles 500, 501, 504, and 505 of NFPA 70, National Electrical Code . 5.5.1 If the vacuum pumps for propellant charging are installed remotely (i.e., not in the charging room), the area within 1.5 m (5 ft) of the extremities of the pumps shall be classified as a Class I, Division 2 or Class I, Zone 2 location. 5.5.2* Electrical equipment and wiring in areas where flammable liquids are handled shall be suitable for the classification of the area, as defined in Chapters 9 through 16 of NFPA 30, Flammable and Combustible Liquids Code . 5.5.3 The area enclosed by the test bath shall be classified as a Class I, Division 1 or Class I, Zone 1 location. 5.5.3* The area enclosed by the button tipper (actuator placer) shall be classified as a Class I, Division 1 or Class I, Zone 1 location. For button tippers (actuator placers) and test baths that handle products containing flammable gases or flammable liquids, the following area classification requirements shall apply: (1) The area enclosed by the button tipper (actuator placer) or test bath shall be classified as a Class I, Division 1 or Class I, Zone 1. (2) The area within 1.5 m (5 ft) in all directions of the button tipper (actuator placer) shall be classified as a Class I, Division 2 or Class I, Zone 2 . 5.5.5 The area within 1.5 m (5 ft) in all directions of the test bath shall be classified as a Class I, Division 2 or Class I, Zone 2 location. 5.5.6 The area within 1.5 m (5 ft) in all directions of the button tipper (actuator placer) shall be classified as a Class I, Division 2 or Class I, Zone 2 location.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 20:31:48 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 14 simplifies the electrical area classification provisions for button tippers and test baths by combining them into a single subsection. This is appropriate, since the requirements are identical. In addition, the provisions are limited in applicability to those products that contain flammable gases or flammable liquids, because electrical area classification is unnecessary where the components of the product do not present a risk of ignition. Additional guidance is given in the Annex to 5.5.3. See Second Revision No. 15.

12/6/2013 5:02 PM

National Fire Protection Association Report

15 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

16 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 23-NFPA 30B-2013 [ Section No. 5.13.2 ]

5.13.2 Crimper Vacuum Pump Discharge Vent Crimper and Under-the-Cup (UTC) Propellant Filler Vacuum Pumps . 5.13.2.1 The discharge vent for the crimper vacuum pump shall terminate at a safe location outside, not less than 3.7 m (12 ft) above adjacent ground level. Vacuum pump discharge piping on any equipment that handles flammable gases or flammable liquids shall meet the requirements of 5.13.3.3.1(A) and 5.13.3.3.1(B). 5.13.2.2 The vent outlet shall be located or arranged so that flammable gas or vapor will not be trapped by eaves or other obstructions and shall be at least 1.5 m (5 ft) from any building openings.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 10:56:59 EDT 2013

Committee Statement Committee Statement:

This Second Revision accomplishes two objectives: (1) It extends applicability of this subsection to under-the-cup (UTC) propellant fillers. (2) It eliminates information that is redundant to what is found in Subsection 5.13.3. See Second Revision No. 24, Subsection 5.13.3. This Second Revision also relates indirectly to First Revision No. 10.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

17 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 24-NFPA 30B-2013 [ Section No. 5.13.3 ]

5.13.3 Propellant Charging Equipment. 5.13.3.1 The propellant pump Propellant charging pumps, tank farm transfer pumps, and all equipment subject to pressure from the pump pumps shall be suitable for the working pressure maximum allowable operating pressure (MAOP) of the system. 5.13.3.1.1* Pump discharge pressures shall not be limited, provided they do not exceed the working pressure MAOP of the system. 5.13.3.1.2 Propellant heater heat exchangers, piping, pumps, and valves shall have a working pressure rating that meets the pressure of the application. 5.13.3.1.3 Propellant heaters shall use hot water only for the heat exchanger that heats the propellant. 5.13.2.1.3.1 A separate steam or hot water heat exchanger shall be used to heat the water that is used to heat the propellant. 5.13.3.2 High-pressure propellant booster pumps equipped with backpressure regulating valves and bypass return lines shall be provided with an automatic shutdown device in the return line. 5.13.3.2.1 The shutdown device shall be set so that the high-pressure pump shuts down if the pressure in the propellant bypass return piping (downstream of the backpressure regulating valve) reaches a minimum gauge pressure of 345 kPa (50 psi) below the set pressure of the hydrostatic relief valves installed in the propellant bypass return piping. 5.13.3.3 Flammable Liquefied Gas Propellant Pumps. 5.13.3.3.1 Propellant pumps and associated components, such as bypass regulator bonnet vents, safety relief valves, hydrostatic relief valves, and manual vent valves on any equipment that handles flammable gases or flammable liquids and are located within a building shall meet the requirements of 5.13.3.3.1(A) through 5.13.3.3.1(E) (A) The discharge vent shall terminate at a safe location outside the building and at least 3 m (10 ft) away from any air intake. (B) The discharge vent shall terminate at least 3 m (10 ft) above the roof and at least 1 m (3 ft) above the highest point of any building within 7.6 m (25 ft). (C) When flammable liquefied gas propellant charging equipment and piping are being vented, liquid shall not be discharged directly to atmosphere. Expansion chambers, knock-out pots, or equivalent devices shall be used so that only gas or vapor is released. (D) Discharge vent manifolds shall serve a single propellant charging room or pump room. (E) Discharge vents, where installed, shall be designed so as not to inhibit the operation of any safety relief device. 5.13.3.3.2* If located inside a building, the propellant pump shall be located either in the propellant charging room or in a separate pump room that is provided with ventilation meeting the requirements of Section 5.4. 5.13.3.3.3

12/6/2013 5:02 PM

National Fire Protection Association Report

18 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

If located outside, the propellant pump shall be located at least 7.6 m (25 ft) from any of the following: (1) Any opening in the adjacent wall of the production building (2) Walls or buildings other than those of the production facility or the propellant charging room (3) Any area subject to vehicular travel (4) Any other sources of ignition 5.13.3.3.3.1 The propellant charging pump shall be placed on a finished noncombustible hard surface. 5.13.3.3.3.2 A clearance of at least 3 m (10 ft) in all directions shall be maintained from vegetation or other combustible materials. (B) The discharge vent shall terminate at a safe location outside and at least 3 m (10 ft) away from any air intake. (C) The discharge vent shall terminate at least 3 m (10 ft) above the roof and at least 1 m (3 ft) above the highest point of any building within 7.6 m (25 ft). (D) When venting liquefied flammable gas propellant charging equipment and piping, liquid shall not be discharged directly to the atmosphere. Expansion chamber , knock-out pots, or equivalent devices shall be utilized so that only vapor is released. (E) Discharge vent manifolds shall service a single propellant charging or pump room. Discharge vents, where installed, shall be designed so as not to inhibit proper operation of safety relief devices. 5.13.3.3.4 Pressure-containing metal parts and components shall be constructed of the following materials: (1) Steel (2) Stainless steel (3) Ductile (nodular) iron (ASTM A 395 or A 536, grades 60-40-18 or 65-45-12) (4) Malleable iron (ASTM A 47) (5) High-strength gray iron (ASTM A 48, Class 40B) (6) Brass (7) Other material equivalent to one of items (1) through (6) 5.13.3.3.4.1 Pressure-containing parts, plungers, or pistons shall not be constructed of ceramic materials. 5.13.3.4 Propellant Heaters. 5.13.3.4.1 If located inside a building, the propellant pump and propellant heater shall be located either in the propellant charging room or in a separate pump room having suitable ventilation, as described in Section 5.4 . 5.13.3.4.2 If located outside, propellant heaters shall meet the requirements of 5.13.3.3.3. 5.13.3.4.3 Propellant heater components, such as heat exchangers, piping, hoses, pumps, and valves, shall be suitable for the MAOP of the system. 5.13.3.4.4 Propellant heaters shall use only hot water or another nonhazardous liquid medium, such as glycol/water mixtures, for the heat exchanger that heats the propellant. 5.13.3.4.5

12/6/2013 5:02 PM

National Fire Protection Association Report

19 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

A separate heating system shall be used to heat the liquid medium that heats the propellant. 5.13.3.4.5.1 This system shall use steam, hot water, or an electric immersion heater that is rated for the propellant being heated and is suitable for the hazard rating of the location. 5.13.3.4 High pressure propellant booster pumps equipped with backpressure regulating valves and return lines shall be provided with an automatic shutdown device in the return line. 5.13.3.4.1* The shutdown device shall be set so that the high pressure pump shuts down if the pressure in the propellant bypass return piping (downstream of the backpressure regulating valve) reaches a minimum gauge pressure of 345 kPa (50 psi) below the set pressure of hydrostatic relief valves installed in the propellant bypass return piping.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 11:06:44 EDT 2013

Committee Statement Committee Statement:

This Second Revision is the product of a task group effort to consolidate changes that have been made over the years to Subsections 5.13.3 and 5.13.4 into a more coherent and readable format. The subject provisions have been organized into a section on propellant charging equipment for all applications, then a section covering propellant charging equipment for flammable propellants, then the section on propellant heaters. Existing text has been retained to the extent possible.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

20 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 25-NFPA 30B-2013 [ Section No. 5.13.4 ]

5.13.4 Flammable Liquid Propellant Pump and Propellant Heater. 5.13.4.1 If located inside a building, the propellant pump and propellant heater shall be located either in the propellant charging room or in a separate pump room having suitable ventilation, as described in Section 5.4 . 5.13.4.2 If located outside, the propellant charging pump and propellant heater shall be located at least 7.6 m (25 ft) from the following: Any opening in the adjacent wall of the production facility Walls or buildings other than the production facility or propellant charging room Any area subject to vehicular travel Other sources of ignition (A) The propellant charging pump and propellant heater shall be placed on a finished noncombustible hard surface. (B) A clearance of a minimum 3 m (10 ft) shall be required in all directions to vegetation or other combustible materials. 5.13.4.3 Pressure-containing metal parts shall be constructed of the following materials: (1) Steel (2) Stainless steel (3) Ductile (nodular) iron (ASTM A 395 or A 536, grade 60-40-18 or 65-45-12) (4) Malleable iron (ASTM A 47) (5) Higher-strength grey iron (ASTM A 48, Class 40B) (6) Brass (7) Other materials equivalent to (1) through (6) 5.13.4.4 Pressure-containing parts, plungers, or pistons shall not be constructed of ceramic materials. 5.13.4.5 Bypass regulator bonnet vents, safety relief valves, and hydrostatic relief valves on equipment located within buildings shall be vented to a safe location outside. Discharge vents shall terminate at least 3 m (10 ft) above the roof and at least 1 m (3 ft) above the highest point of any building within 7.6 m (25 ft).

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip:

12/6/2013 5:02 PM

National Fire Protection Association Report

21 of 71

Submittal Date:

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Wed Oct 16 12:15:08 EDT 2013

Committee Statement Committee Statement:

This Second Revision deletes Subsection 5.13.4 entirely. The text has been incorporated into the rewrite of Subsection 5.13.3, as shown in Second Revision No. 24.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

22 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 39-NFPA 30B-2013 [ Section No. 5.14 ]

5.14* Shrink-Wrapping of Aerosol Products. 5.14.1 Where heat shrink-wrapping in tunnel equipment greater than 1.8 m (6 ft) in length of individual packages of 5 five or more aerosol containers products or palletized aerosol products are is performed, the heat shrink-wrap tunnel and equipment shall be provided with the following: (1) Equipment failure detection and notification (2) Automatic product evacuation and notification upon loss of power (3) Automatic fire suppression and notification 5.14.2 Where heat shrink-wrapping in tunnel equipment of 1.8 m (6 ft) or less in length of individual packages of 4 four or fewer aerosol containers products is performed, an automatic product evacuation system and alarm shall be provided that activates upon loss of power.

Submitter Information Verification Submitter Full Name: Robert Benedetti Organization:

National Fire Protection Assoc

Street Address: City: State: Zip: Submittal Date:

Fri Oct 18 14:06:57 EDT 2013

Committee Statement Committee Statement:

This Second Revision amends terminology to correlate with new definitions accepted in Chapter 3.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

23 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 4-NFPA 30B-2013 [ Section No. 5.15.1 ]

5.15.1 Aerosol product laboratories shall be considered as that handle flammable gases shall meet the requirements for Class A laboratory units and, as such, shall comply with set forth in NFPA 45, and shall meet the requirements of Section 5.15 . Aerosol product laboratories that do not handle flammable gases shall meet the appropriate requirements of NFPA 45 and shall meet the requirements of Section 5.15 Standard on Fire Protection for Laboratories Using Chemicals .

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Sep 24 14:30:51 EDT 2013

Committee Statement Committee Statement:

This Second Revision amends and expands on First Revision No. 78 to distinguish as NFPA 45 Class A laboratory units those aerosol product laboratories handling flammable gases and/or flammable liquids.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

24 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 31-NFPA 30B-2013 [ Section No. 6.1.1 ]

6.1.1 The protection criteria in this chapter shall apply to the following: (1) Level 1 aerosol products in metal containers not more than 1000 ml (33.8 fl oz) capacity , in accordance with Section 6.2 (2) Level 2 and Level 3 aerosol Aerosol cooking spray products in metal containers up to not more than 1000 ml (33.8 fl oz) capacity, in accordance with Section 6.4 6.3 (3) Level 2 and Level 3 A a erosol products in glass and plastic metal containers up to 118 ml (4 fl oz) not more than 1000 ml (33.8 fl oz) capacity, in accordance with Section 6.3 6.4 (4) Limited-quantity storage of a A erosol products in glass and plastic containers greater not more than 118 ml (4 fl oz) capacity, in accordance with Subs ection 6.3.3 6.4 (5) Aerosol products in plastic containers greater than 118 ml (4 fl oz) capacity, and not more than 1000 ml (33.8 fl oz) capacity, in accordance with Section 6.4 6.5

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 15:23:09 EDT 2013

Committee Statement Committee Statement:

This Second Revision implements amendments promulgated by Tentative Interim Amendment 11-1, as well as concepts set forth under Committee Inputs Nos. 19, 57, and 58. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision. This Second Revision also relates to First Revisions Nos 80, 81, and 87.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

25 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 32-NFPA 30B-2013 [ Section No. 6.1.2 ]

6.1.2 All outer packaging of aerosol products , including cartons, trays, shrouds, or other packaging, of aerosol products shall be identified on at least one side with the classification of the aerosol products in accordance with Section 1.9 and marked as follows with one of the following, whichever is appropriate : (a) Level _____ Aerosols or (b) Aerosol Cooking Spray or (c) Plastic Aerosol 1 (or X)

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 15:29:46 EDT 2013

Committee Statement Committee Statement: This Second Revision effects changes that correlate with Second Revision No. 7. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

26 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 33-NFPA 30B-2013 [ New Section after 6.2.2 ]

6.3 Storage of Aerosol Cooking Spray Products. 6.3.1 General. 6.3.1.1 Aerosol cooking spray products shall be permitted to be stored in a general-purpose warehouse. 6.3.1.2 Aerosol cooking spray products shall be permitted to be stored mixed with other higher hazard aerosols as long as the provided isolation, storage height restrictions, and protection are based on the highest hazard aerosol product present. 6.3.2 Fire Protection.

12/6/2013 5:02 PM

National Fire Protection Association Report

27 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6.3.2.1 Encapsulated storage of cartoned aerosol cooking spray products shall be protected as uncartoned storage. 6.3.2.2 Stretch-wrapping of cartons of aerosol cooking spray products shall be protected as cartoned storage. 6.3.2.3 Wet-pipe automatic sprinkler protection shall be provided in accordance with Table 6.3.2.3(a) or Table 6.3.2.3(b) for cartoned aerosol cooking spray products stored in open frame racks without solid shelves or stored as palletized or solid pile storage. Table 6.3.2.3(a) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (Metric Units) Maximum Ceiling Height

Maximum Storage Height

(m)

(m)

9.1

7.6

Ceiling Sprinkler Protection Criteria Sprinkler Type / Nominal Orifice (L/min/bar 0.5 )

Response / Nominal Temperature Rating

Hose Stream (# sprinklers @ Demand discharge (L/min) pressure)

Water Supply Duration

12 @ 5.2 bar

1

Design

(hr)

ESFR-pendent K = 200

FR / Ordinary

950

Table 6.3.2.3(b) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (English Units) Maximum Ceiling Height

Maximum Storage Height

(ft)

(ft)

30

25

Ceiling Sprinkler Protection Criteria Sprinkler Type / Nominal Orifice (gpm/psi 0.5 )

Response / Nominal Temperature Rating

Hose Stream (# sprinklers @ Demand discharge (gpm) pressure)

Water Supply Duration

12 @ 75 psi

1

Design

(hr)

ESFR-pendent K = 14.0

FR / Ordinary

250

6.3.2.4 Rack storage shall be arranged so that a minimum aisle width of 2.4 m (8 ft) is maintained between rows of racks and between racks and adjacent solid pile or palletized storage. 6.3.2.5 Solid pile and palletized storage shall be arranged so that no storage is more than 7.6 m (25 ft) from an aisle. Aisles shall be not less than 1.2 m (4 ft) wide. 6.3.2.6 Aerosol cooking spray product that is stored uncartoned shall be protected in accordance with Section 6.4 using the criteria for a Level 2 or Level 3 aerosol product, based on the product’s chemical heat of combustion. 6.3.2.7 Protection criteria that are developed based on full-scale fire tests performed at an approved facility shall be considered an acceptable alternative to the protection criteria set forth in Table 6.3.2.3(a) or Table 6.3.2.3(b) . 6.3.2.8 Storage in occupancies other than warehouses or mercantile occupancies, such as in assembly, business, educational, industrial, and institutional occupancies, shall be permitted up to a maximum of 454 kg (1000 lb) net weight. 6.3.2.9 Solid pile, palletized, or rack storage of aerosol cooking spray product shall be permitted in a generalpurpose warehouse that is either unsprinklered or not protected in accordance with this code, up to a maximum of 1135 kg (2500 lb).

Supplemental Information

12/6/2013 5:02 PM

National Fire Protection Association Report

28 of 71

File Name NFPA_30B_A2014_2nd_Draft_-_SR_No._33_AttachmentTables_6.3.2.3a_b_-_DONE.doc

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Description This attachment includes Tables 6.3.2.3(a) and 6.3.2.3(b) for inclcusion in SR No. 33.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 15:34:50 EDT 2013

Committee Statement Committee Statement:

This Second Revision implements amendments promulgated by Tentative Interim Amendment 11-1, as well as concepts set forth under Committee Inputs Nos. 19, 57, and 58. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision. This Second Revision also relates to First Revisions Nos 80, 81, and 87.

Response Message:

12/6/2013 5:02 PM

Maximum Ceiling Height (m)

Table 6.3.2.3(a) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (Metric Units) Maximum Ceiling Sprinkler Protection Criteria Hose Storage Stream Height Demand Sprinkler Type / Response / Design (m) (L/min) Nominal Orifice Nominal (# sprinklers @ (L/min/bar0.5) Temperature discharge Rating pressure)

Water Supply Duration (hr)

9.1

7.6

1

Maximum Ceiling Height (ft)

Table 6.3.2.3(b) Rack, Palletized and Solid Pile Storage of Cartoned Aerosol Cooking Spray Products (English Units) Maximum Ceiling Sprinkler Protection Criteria Hose Storage Stream Height Demand Sprinkler Type / Response / Design (ft) (gpm) Nominal Orifice Nominal (# sprinklers @ (gpm/psi0.5) Temperature discharge Rating pressure)

Water Supply Duration (hr)

30

25

1

ESFR-pendent K = 200

ESFR-pendent K = 14.0

FR / Ordinary

FR / Ordinary

12 @ 5.2 bar

12 @ 75 psi

950

250

National Fire Protection Association Report

29 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 34-NFPA 30B-2013 [ Section No. 6.3.3 ]

6.4.3 Limited-Quantity Storage in Occupancies Other Than Warehouses. 6.4.3.1 Storage of Level 2 and Level 3 aerosol products and aerosol products in plastic containers in a single fire area in occupancies other than warehouses or mercantile occupancies, such as assembly, business, educational, industrial, and institutional occupancies, shall be permitted up to one of the following quantities: (1) A maximum of 454 kg (1000 lb) net weight of Level 2 aerosol products (2) A maximum of 227 kg (500 lb) net weight of Level 3 aerosol products A maximum of 227 kg (500 lb) net weight of aerosol products in plastic containers 6.4.3.2 In no case shall the combined net weight of Level 2 and Level 3 aerosol products and aerosol products in plastic containers exceed 454 kg (1000 lb). 6.4.3.3 These quantities shall be permitted to be doubled if the quantities in excess of those stated in 6.4.3.1 are stored in storage cabinets that meet the requirements of Section 9.5 of NFPA 30, Flammable and Combustible Liquids Code . 6.4.3.4 Where Level 2 and Level 3 aerosol products are stored in quantities greater than those allowed by 6.4.3.1 and 6.4.3.2, such quantities shall be stored in a separate inside storage area meeting the requirements of 6.4.7.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 16:55:57 EDT 2013

Committee Statement Committee Statement:

The deletions incorporated by this Second Revision reflect the addition of new Section 6.5, in accordance with Second Revision No. 36.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

30 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 35-NFPA 30B-2013 [ Section No. 6.3.4 ]

6.4.4 Limited-Quantity Storage in General-Purpose Warehouses. 6.4.4.1 Subject to the approval of the AHJ, solid pile, palletized, or rack storage of Level 2 and Level 3 aerosol products and aerosol products in plastic containers shall be permitted in a general-purpose warehouse that is either unsprinklered or not protected in accordance with this code, up to one of the following quantities: (1) A maximum of 1135 kg (2500 lb) net weight of Level 2 aerosol products (2) A maximum of 454 kg (1000 lb) net weight of Level 3 aerosol products A maximum of 454 kg (1000 lb) net weight of aerosol products in plastic containers 6.4.4.2 In no case shall the combined net weight of Level 2 and Level 3 aerosol products and aerosol products in plastic containers exceed 1135 kg (2500 lb). 6.4.4.3 Subject to the approval of the authority having jurisdiction AHJ , solid pile or palletized storage of Level 2 and Level 3 aerosol products shall be permitted in a general-purpose warehouse that is protected throughout by an automatic sprinkler system up to a maximum total quantity of 5,450 5450 kg (12,000 lb) combined net weight of Level 2 and Level 3 aerosol products, subject to the following: (1) The sprinkler system over the aerosol product storage area and for a distance of 6 m (20 ft) beyond shall be designed in accordance with Table 6.4.2.7(a) through Table 6.4.2.7(d). (2) Storage of flammable and combustible liquids shall be separated from the aerosol products storage area by at least 8 m (25 ft). 6.4.4.4 Subject to the approval of the AHJ, rack storage of Level 2 and Level 3 aerosol products shall be permitted in a general-purpose warehouse that is protected throughout by an automatic sprinkler system up to a maximum total quantity of 10,900 kg (24,000 lb) combined net weight of Level 2 and Level 3 aerosol products, subject to the following: (1) The sprinkler system in the Level 2 and Level 3 aerosol products storage area shall be designed in accordance with Table 6.4.2.7(e) through Table 6.4.2.7(l) . The ceiling sprinkler system design shall extend for 6 m (20 ft) beyond the aerosol products storage area. (2) Storage of aerosol products shall be separated from storage of flammable and combustible liquids by at least 8 m (25 ft).

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 16:59:49 EDT 2013

Committee Statement Committee Statement:

The deletions incorporated by this Second Revision reflect the addition of new Section 6.5, in accordance with Second Revision No. 36.

12/6/2013 5:02 PM

National Fire Protection Association Report

31 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

32 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 36-NFPA 30B-2013 [ Section No. 6.4 ]

6.5 Aerosol Products in Plastic Containers Greater Than 118 ml (4 fl.oz.) and Not More Than 1000 ml (33.8 oz) . 6.5.1 Fire Protection — Plastic Aerosol 1 Products. Aerosol products in plastic containers larger than 118 ml (4 fl oz) shall be considered equivalent to Class III commodities, as defined in NFPA 13 , Standard for the Installation of Sprinkler Systems , where any of the following conditions are met: The base product has no fire point when tested in accordance with ASTM D 92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester , and the propellant is nonflammable. The base product does not exhibit sustained combustion when tested in accordance with “Method of Testing for Sustained Combustibility," Title 49, Code of Federal Regulations, Part 173, Appendix H, or the UN Recommendations on the Transport of Dangerous Goods , and the propellant is nonflammable. * The base product contains up to 20% by volume (15.8% by weight) of ethanol or propanol or mixtures thereof in an aqueous mix and the propellant is nonflammable. * The base product contains 4% by weight or less of an emulsified flammable liquefied gas propellant within an aqueous base, said propellant to remain emulsified for the life of the product. Where such propellant is not permanently emulsified then the propellant shall be nonflammable. 6.5.1.1 Plastic aerosol 1 products shall be permitted to be stored in a general-purpose warehouse without isolation. 6.5.1.2* Plastic aerosol 1 products shall be considered equivalent to Class III commodities, as defined in NFPA 13 6.5.1.3 In cases where the storage of plastic aerosol 1 products is required to be protected, they shall be protected in accordance with the requirements of NFPA 13. 6.5.2 Fire Protection — Plastic Aerosol X Products. 6.5.2.1 Storage of plastic aerosol X products in occupancies other than warehouses or mercantile occupancies, such as in assembly, business, educational, industrial, and institutional occupancies, shall be permitted up to a maximum of 45 kg (100 lb) net weight. 6.5.2.2 Solid pile, palletized, or rack storage of plastic aerosol X products shall be permitted in a generalpurpose warehouse or an aerosol warehouse regardless of protection level up to a maximum of 115 kg (250 lb).

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 21:14:14 EDT 2013

12/6/2013 5:02 PM

National Fire Protection Association Report

33 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Committee Statement Committee Statement:

This Second Revision implements amendments promulgated by Tentative Interim Amendment 11-1, as well as concepts set forth under Committee Inputs Nos. 19, 57, and 58. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision. This Second Revision also relates to First Revisions Nos 80, 81, and 87.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

34 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 27-NFPA 30B-2013 [ Section No. 7.1 ]

7.2 Sales Display Areas — Aerosol Storage Not Exceeding 2.4 m (8 ft) High. 7.2.1 Level 1 aerosol products and plastic aerosol 1 products in sales display areas shall not be limited. 7.2.2 When located in sales display areas, aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be removed from combustible cartons, or the cartons shall be display-cut, when located in sales display areas . 7.2.2.1 Cartoned display of Level 2 and Level 3 aerosol products shall be permitted, provided the area is protected in accordance with by one of the following: (1) In accordance with Table 6.3.2.3(a) or Table 6.3.2.3(b) , or (2) In accordance with Table 6.4.2.7(a) through Table 6.4.2.7(l) , or (3) In accordance with the maximum quantity of cartoned display complies with 7.2.3.1 Table 6.3.2.7(a) through Table 6.3.2.7(l) or the maximum quantity of cartoned display complies with 7.1.3.1 . 7.2.2.2 Cartoned display of Level 2 and Level 3 aerosol products shall be permitted, provided the area is protected in accordance with Table 6.4.2.7(a) through Table 6.4.2.7(l) or the maximum quantity of cartoned display complies with 7.2.3.1 . 7.2.3 Aerosol cooking spray products and Level 2 and Level 3 aerosol products in sales display areas shall not exceed the maximum quantities given in 7.2.3.1 and 7.2.3.2 according to the protection provided. 7.2.3.1 In sales display areas that are nonsprinklered or whose sprinkler system does not meet the requirements of 7.2.3.2, the total aggregate quantity of aerosol cooking spray products and Level 2 and Level 3 aerosol 2 2 products and aerosol products in plastic containers shall not exceed 9.8 kg/m (2 lb/ft ) of total sales display area, up to the quantities specified in Table 7.2.3.1 . Table 7.2.3.1 Maximum Quantity per Floor of Aerosol Cooking Spray Products, Level 2 and Level 3 Aerosol Products and Aerosol Products in Plastic Containers Max. Maximum Net Weight per Floor Floor

kg

Basement

lb Not Permitted

Ground

1135

2500

Upper

227

500

7.2.3.1.1 No single 3 m × 3 m (10 ft × 10 ft) section of sales display area shall contain an aggregate quantity of more than 454 kg (1000 lb) net weight of aerosol cooking spray products and Level 2 and Level 3 aerosol products and aerosol products in plastic containers . 7.2.3.2 In sales display areas that are sprinklered in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems , for at least O o rdinary H h azard (Group 2) occupancies, the total aggregate quantity 2 of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall not exceed 9.8 kg/m 2 (2 lb/ft ) of total sales display area.

12/6/2013 5:02 PM

National Fire Protection Association Report

35 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7.2.3.2.1 No single 3 m × 3 m (10 ft × 10 ft) section of sales display area shall contain an aggregate quantity of more than 454 kg (1000 lb) net weight of aerosol cooking spray products and Level 2 and Level 3 aerosol products. 7.2.4 Aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be securely stacked to not more than 1.8 m (6 ft) high from base to top of the storage array unless on fixed shelving. 7.2.4.1 Shelving shall be of stable construction, and storage shall not exceed 2.4 m (8 ft) in height.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 13:35:16 EDT 2013

Committee Statement Committee This Second Revision adds a new Section 7.1 to address and establish quantity limitations on Statement: so-called plastic aerosol X products in mercantile occupancies. Plastic aerosol X products are those whose characteristics are such that they do not meet any of the criteria established in (new) Section 1.8 of NFPA 30B. This Second Revision also establishes storage criteria for aerosol cooking spray products and for plastic aerosol 1 products, in accordance with Committee Inputs Nos. 19 and 58 and testing done subsequent thereof. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

36 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 28-NFPA 30B-2013 [ Section No. 7.2 ]

7.3 Sales Display Areas — Aerosol Storage Exceeding 2.4 m (8 ft) High. 7.3.1 Storage and display of Level 1 aerosol products and plastic aerosol 1 products in sales display areas shall not be limited. 7.3.2 Uncartoned or display-cut (case-cut) aerosol cooking spray products and Level 2 and Level 3 aerosol products that are stored for display no more than 1.8 m (6 ft) above the floor shall be permitted where protection is installed in accordance with 7.3.3, based on the highest level of aerosol product in the array and the packaging method of the storage above 1.8 m (6 ft). 7.3.3 Protection. 7.3.3.1 The storage and display of aerosol cooking spray products in metal containers only shall be protected in accordance with Table 6.3.2.3(a) or Table 6.3.2.3(b) or shall be protected in accordance with Table 6.4.2.7(a) through Table 6.4.2.7(l) The storage and display of Level 2 and Level 3 aerosol products in metal containers only shall be protected in accordance with Table 6.4.2.7(a) through Table 6.4.2.7(l) , whichever is applicable. 7.3.3.1.1 Where in-rack sprinklers are required by Table 6.4.2.7(e) through Table 6.4.2.7(l) and where the aerosol cooking spray products and Level 2 and Level 3 aerosol products are stored for display below the 1.8 m (6 ft) level, the first tier of in-rack sprinklers shall be installed above the display, but no not more than 1.8 m (6 ft) above the floor level. 7.3.3.2 Noncombustible draft curtains shall extend down a minimum of 0.61 m (2 ft) from the ceiling and shall be installed at the interface between ordinary and high-temperature sprinklers. 7.3.4 Storage and display of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall not 2 2 exceed 4,540 4540 kg (10,000 lb) net weight within any 2,323 2323 m (25,000 ft ) of sales display area. 7.3.4.1 Aerosol cooking spray products and Level 2 and Level 3 aerosol product display areas shall be separated from each other by a minimum of 7.6 m (25 ft). 7.3.5 The area of the design for the required ceiling sprinkler system shall extend 6 m (20 ft) beyond the area devoted to storage of aerosol cooking spray products and Level 2 and Level 3 aerosol products. product display and storage area . 7.3.6 Storage and display of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be separated from the storage of flammable and combustible liquids by a minimum distance of 7.6 m (25 ft) or by a segregating wall or noncombustible barrier. 7.3.6.1 Where aerosol cooking spray products and Level 2 and Level 3 aerosol products are stored within 7.6 m (25 ft) of flammable and combustible liquids, the area beneath the noncombustible barrier shall be liquidtight at the floor to prevent spilled liquids from flowing beneath the aerosol products. 7.3.7 The sales display area shall meet the requirements for mercantile occupancies in NFPA 101, Life Safety Code .

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

12/6/2013 5:02 PM

National Fire Protection Association Report

37 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 14:26:11 EDT 2013

Committee Statement Committee Statement:

This Second Revision establishes storage criteria for aerosol cooking spray products and for plastic aerosol 1 products, in accordance with Committee Inputs Nos. 19 and 58 and testing done subsequent thereof. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

38 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 29-NFPA 30B-2013 [ Section No. 7.3 ]

7.4 Back Stock Storage Areas. 7.4.1 Where back stock areas are separated from sales display areas by construction having a minimum 1-hour fire resistance rating, storage of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall meet the requirements of Chapter 6. 7.4.2 Where back stock areas are not separated from sales display areas by construction having a minimum 1-hour fire resistance rating, the quantity of aerosol cooking spray products and Level 2 and Level 3 aerosol products in back stock areas shall be included in the total allowable quantities specified in 7.2.3 or 7.3.4. 7.4.2.1 Protection shall be provided in accordance with 7.3.3 . 7.4.3 An additional quantity of aerosol cooking spray products and Level 2 and Level 3 aerosol products, up to a maximum of 227 kg (500 lb) net weight, shall be permitted in back stock areas where the additional quantities are stored in flammable liquid storage cabinets that meet the requirements of Section 9.5 of NFPA 30. , Flammable and Combustible Liquids Code . 7.4.4 Storage of aerosol cooking spray products and Level 2 and Level 3 aerosol products in separate, inside flammable liquids storage rooms shall meet the requirements of 6.4.7 .

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 14:33:34 EDT 2013

Committee Statement Committee Statement:

This Second Revision establishes storage criteria for aerosol cooking spray products, in accordance with Committee Inputs Nos. 19 and 58 and testing done subsequent thereof. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

39 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 30-NFPA 30B-2013 [ Section No. 7.4 ]

7.5 Special Protection Design.

12/6/2013 5:02 PM

National Fire Protection Association Report

40 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7.5.1

12/6/2013 5:02 PM

National Fire Protection Association Report

41 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Section 7.5 prescribes a special protection design methodology for the storage and display of aerosol cooking spray products and Level 2 and Level 3 aerosol products in double-row racks. Protection shall be in accordance with Table 7.5.1 , Figure 7.5.1, and 7.3.3.2, 7.3.4, and Section 7.5. Table 7.5.1 Protection of Single, Double-Row Display/Rack Storage of Aerosol Cooking Spray Products and Level 2 and Level 3 Aerosol Products with In-Rack Sprinklers Ceiling Maximum Maximum Storage Ceiling Height Height

9.1 m (30 ft)

Sprinkler Type and Arrangement

Clearance Storage to Sprinklers

Ceiling Design

In-Rack Sprinkler Type and Arrangement

Quick-response, ordinary temperature, K=160 ( K ≥ = 11.2 orifice size pendent sprinklers, ESFR maximum 127 K=360 (K = mm (50 in.) on 12 25.2), center spacing sprinklers 4.8 m (16 O o rdinary Up to 4.6 m located 2.4 m (8 @103 T t emperature, (15 ft) ft) ft) above floor at kPa ( 15 2 each rack face 9.3 m (100 psi) and in 2) ft maximum longitudinal flue spacing space, if a double- row rack. A barrier shall be located directly over level of in-rack sprinklers. ESFR K=200 (K = 14) O o rdinary T t emperature, 2 9.3 m (100 2) ft maximum spacing

In-Rack

Duration

Design

(hr)

212 L/min ( 56 gpm) per sprinkler minimum based on operation of hydraulically most remote 12 sprinklers

2

12 sprinklers @ 345 kPa ( 50 psi)

Note: Minimum 0.7 bar (10 psi) for in-rack sprinkler design pressure. Figure 7.5.1 Special Protection for Aerosol Cooking Spray Products and Level 2 and Level 3 Aerosol Products in Double-Row Racks.

12/6/2013 5:02 PM

National Fire Protection Association Report

43 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7.5.2 Storage and display of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be in cartons. 7.5.2.1 Containers of aerosol cooking spray products and Level 2 and Level 3 aerosol products that are stored or displayed no more than 2.4 m (8 ft) above the floor shall be permitted to be uncartoned or in display-cut cartons. 7.5.3 Storage and display of aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be on open racks or wire mesh shelves. 7.5.4 Rack storage shall be arranged so that a minimum aisle width of 2.3 m (7.5 ft) is maintained between rows of rack and adjacent solid piled or palletized storage. 7.5.5 Nominal 76 mm (3 in.) transverse flue spaces at rack uprights and nominal 152 mm (6 in.) longitudinal flue spaces shall be provided. 7.5.6 Horizontal barriers of plywood [minimum 10 mm (3⁄8 in.) thickness] or sheet metal (minimum 22 gauge) and in-rack sprinklers shall be installed in accordance with Table 7.5.1 and Figure 7.5.1.

12/6/2013 5:02 PM

National Fire Protection Association Report

44 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7.5.6.1 For double-row racks with aerosol product storage on only one side, the horizontal barrier shall extend over the longitudinal flue space in accordance with Plan View 2 of Figure 7.5.1. 7.5.7 Ordinary combustibles (Class Classes I, II, III, and IV, commodities and plastic commodities) shall be permitted to be stored adjacent to aerosol cooking spray products and Level 2 and Level 3 aerosol products, provided that the ordinary combustibles are protected in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems . 7.5.8 Flammable and combustible liquids (NFPA 30 Classes IB, IC, II, IIIA, and IIIB) in one-gallon 3.8L (1 gal) metal relieving and nonrelieving style containers and five-gallon 19L (5 gal) metal relieving style containers shall be permitted to be stored adjacent to aerosol cooking spray products and Level 2 and Level 3 aerosol products (see Figure 7.5.1 ), provided that the sprinkler protection for the flammable and combustible liquids is in accordance with Chapter 16 of NFPA 30. , Flammable and Combustible Liquids Code . 7.5.9 The ordinary-temperature design criteria correspond to ordinary-temperature-rated sprinklers and shall be used for sprinklers with ordinary- and intermediate-temperature classification.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 14:38:05 EDT 2013

Committee Statement Committee Statement:

This Second Revision also establishes storage criteria for aerosol cooking spray products and for plastic aerosol 1 products, in accordance with Committee Inputs Nos. 19 and 58 and testing done subsequent thereof. Changes in accordance with Global Second Revision No. 17 have also been incorporated into this Second Revision.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

45 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 8-NFPA 30B-2013 [ New Section after A.1.7 ]

A.1.8.1(3) Fire testing with alcohol and water at this percentage in plastic bottles has been successful. Small-scale burn tests of aerosol products in plastic containers have shown the aerosol with a nonflammable propellant to behave the same as the aerosol with no propellant. A.1.8.1(4) A fire test with a formula of this type using liquefied petroleum gas was successful. An emulsion in an aerosol product is a mixture of two or more liquids, one of which is present as droplets of microscopic or ultramicroscopic size distributed throughout the other. Emulsions are formed from the component liquids either spontaneously or, more often, by mechanical means such as agitation, provided that the liquids that are mixed have no (or a very limited) mutual solubility. Emulsions are stabilized by agents that form films at the surface of the droplets (e.g., soap molecules) or that impart to them a mechanical stability (e.g., colloidal carbon or bentonite). Colloidal distributions or suspension of one or more liquid(s) with another liquid will have a shelf life that varies with the efficiency of the recipe used.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:39:46 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 8 adds annex material necessary for the understanding of Paragraphs 1.8.1(3) and (4), which have been added to the Code via Second Revision No. 5

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

46 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 2-NFPA 30B-2013 [ Section No. A.3.3.3 ]

A.3.3.3 Aerosol Propellant. The flammable propellant is generally a hydrocarbon gas, such as butane, isobutane, propane, and various blends of these gases. Systems that generate a propellant gas are included in this definition . Examples of flammable liquefied gas propellants include hydrocarbon propellants (e.g. butane, isobutane, and propane), dimethyl ether, hydrofluorocarbon 152a, and various blends of these gases. Examples of nonflammable liquefied gas propellants include hydrofluorocarbon 134a and hydroflouroolefin 1234ze. Examples of nonflammable compressed or soluble gas propellants may include carbon dioxide (CO ), 2 nitrous oxide (N O), nitrogen (N ), or and compressed air. Systems that generate a propellant gas are 2 2 included in this definition. Note Extreme care should be taken when switching between nitrous oxide (N O) and flammable 2 propellants. Mixtures of nitrous oxide and flammable propellants are potentially explosive. The propellants should be supplied to the filling machine with separate piping systems. The filling apparatus and any associated piping must be cleaned per CGA G-4.1, Cleaning Equipment for Oxygen Service, before switching to nitrous oxide.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Sep 24 11:43:55 EDT 2013

Committee Statement Committee Statement:

The first sentence is redundant with the text added at the First Draft. The subject matter of the deleted second sentence is covered later in the paragraph.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

47 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 12-NFPA 30B-2013 [ New Section after A.3.4.7 ]

A.3.4.12 Tank Farm Transfer Pump. Normal pump pressure is 100 kPa to 690 kPa (15 psi to 100 psi) above the propellant’s vapor pressure.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Thu Oct 10 17:57:44 EDT 2013

Committee Statement Committee Statement:

Second Revision No. 12 adds annex text related to the new definition of Tank Farm Transfer Pump added via Second Revision No. 11.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

48 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 15-NFPA 30B-2013 [ New Section after A.5.5.2 ]

A.5.5.3 For aerosol products that contain no flammable propellant or base product components, enclosures should be provided to protect operators in case an aerosol container ruptures.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 20:46:29 EDT 2013

Committee Statement Committee Statement: This Second Revision addresses an issue of operator safety. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

49 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 26-NFPA 30B-2013 [ Section No. A.5.13.3.3.1 ]

A.5.13.3.3.2 This can be accomplished by the installation of a high- pressure shutdown switch, or a safety relief valve installed in the propellant bypass return line ( [ set at a minimum gauge pressure of 345 kPa (50 psi) below the setting of the hydrostatic relief valves) ] , and vented into a vent pipe equipped with a flow switch, or sensor.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 12:18:42 EDT 2013

Committee Statement Committee Statement:

This Second Revision is strictly to change the identification of the annex text from A.5.13.3.3.1 to A.5.13.3.2.1, in accordance with Second Revision No. 24.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

50 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 18-NFPA 30B-2013 [ Section No. A.5.14 ]

12/6/2013 5:02 PM

National Fire Protection Association Report

51 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

A.5.14

12/6/2013 5:02 PM

National Fire Protection Association Report

52 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

The principal concern in the event of a shrink-wrap tunnel failure is the risk of aerosol container failure and subsequent fire. In the event of a container failure, significant ejection speeds, sympathetic failures of adjacent containers, and hot surfaces present serious potential exposures. In turn, ignition of flammable solvent or propellant vapor can result, . T with t he consequence of this is that an explosion can further augment the original ejection force. This can be a significant hazard to operators in the vicinity. Newly installed shrink-wrapping machines should be equipped with numerous safety features and . E e quipment suppliers should be advised of these such features prior to placing orders. The high fire risk associated with shrink-wrap tunnels should be considered when determining their location. Shrink-wrap acts as a very good insulator, which can facilitate overheating during its passage through the tunnel. Some containers can act as very efficient heat sinks, resulting in fast heating of the containers if the film fails. This can also be exacerbated by the use of high proportions of substances with low specific heats in the formulations. Automatic film failure detection, which switches off the heater and stops the machine in-feed, is necessary. The following list is offers further guidance: (1) The shrink-wrap machine design should ensure that containers are prevented from being trapped in the heating tunnel by internal obstructions. (2) An alarm should be activated in the event of unplanned stoppage. (3) The shrink-wrap machine should have a secondary means of keeping the tunnel conveyer moving in the event of power failure. (4) In the event of conveyor power failure, standby power is recommended in place of a back- up air motor. This cuts in to energize the conveyor if any phase drops more than 10 percent. The in-feed gate and heaters should also automatically switch off and the operator should be alerted by a suitable alarm. If an air motor system is installed, a dedicated air receiver should be connected via metal pipework. This receiver should store enough air to evacuate any “packs” in the tunnel and be constantly fed by the compressor via a non- return valve. An air pressure switch should be installed to interlock with the shrink-wrapper control system. Neither of these back-up systems backup system will be of any use if the belt itself or transmission is broken, so a motion detector should also be installed to confirm belt movement and initiate the above shutdown described if the belt stops during production. (5) Operator protection training should include the use of appropriate personal protective equipment (PPE) in the event containers or collations must be removed manually during a breakdown or unplanned stoppage. (6) Automatically operated fire suppression systems should be installed in accordance with applicable NFPA codes and standards. Portable fire extinguishers should be provided and located in accordance with NFPA 10. , Standard for Portable Fire Extinguishers . (7) There should be a half-hour 30–minute fire-resistant partition or other equivalent means to prevent the spread of fire between the shrink-wrapping machine and the remainder of the aerosol product filling line. (8) Access to and escape routes from the shrink-wrapping machine should be kept clear at all times. (9) Supplies of packaging materials should be stored or staged in defined areas away from the shrinkwrapping machine. (10) There should be an automatic device to detect film failure and prevent new collations from being allowed to enter the heating tunnel in the event of a film failure. (11) A pusher rod with a flat plate on the end, that is specifically designed for the shape of the heating tunnel or equivalent system, should be provided. This The rod will allow operators to rapidly clear the heating tunnel of all collations and containers in the event of a total conveyer failure. (12) A suitable means of ensuring that trapped aerosol containers can be rapidly removed from the tunnel (because either the conveyor has stopped or they have caught on some obstruction) is essential. The inside of the tunnel should be designed with sloping sides to prevent loose aerosol products containers from being retained under the heaters. The design of such a system needs to provide for the protection of operators removing aerosol products containers trapped in the heating tunnel, as because a fully pressurized aerosol container that fails — as well as and its contents — can be ejected with considerable force. Therefore, a remote-operated or automatic mechanism or system could might be preferable. The above procedure described should only be carried out only if aerosol products containers have remained in the tunnel for a short time and the operator is aware

12/6/2013 5:02 PM

National Fire Protection Association Report

53 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

that it is within a safe period. (13) The operator should be provided with the necessary PPE and be trained in its proper use, the proper use of the pusher rod, and the risks involved. (14) A switch should be installed to allow the power supply to the tunnel heat to be turned off in the event of an emergency. (15) The tunnel heater power switch should be provided with automatic shutdown systems that are manually reset. (16) An emergency air blower or other means of rapidly cooling the tunnel should be installed according to the specification provided by the equipment supplier, unless an automatic fire suppression system is provided. (17) Detectors should be installed to count collations in and out of the heating tunnel to activate heater power cutouts and alarms and to stop in-feed gates in the event of a tunnel blockage. (18) Heated surfaces can ignite burst containers, so attention container stability must be provided to ensure container stability ensured , especially when wrapping containers are being unwrapped without trays. If there is a likelihood of unstable containers in this area, appropriate sensors should be installed to inhibit the in-feed gate until the containers are removed. Installing gaseous or dry chemical automatic protection into the shrink-wrapper tunnel is an effective way to directly reach the source of fire. Such systems can be activated by the operator from a safe location, or installed to automatically activate by optical flame detectors located at each end of the tunnel. In addition to the tunnel, the discharge nozzles should also cover the film sealing area. (19) The fire suppression system should be connected to the building fire alarm system. (20) Where conveyers feed shrink-wrapped collations to further automatic equipment downstream from the shrink-wrapping machine, there should be an out-feed light curtain or similar device to detect back- up from the downstream equipment and to stop the in-feed gate until there is no longer a backup. (21) There should be a device installed to detect excess temperatures in the heating tunnel, producing an alarm, cutting power to the heaters, starting the air blowers (if installed), and stopping the in-feed gate. (22) The excess temperature detector should be calibrated at regular specified intervals and the results recorded. (23) A tunnel temperature indicator should be installed for operator information and maintenance purposes showing low, normal, and high/excess bands. (24) The temperature indicator should be calibrated at regular specified intervals and the results recorded. (25) All electrical resets on shrink-wrappers should be manually operated only. (26) Safeguarding should be provided to prevent injury to operators from ejecting ejected containers and contact with hot surfaces.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 21:57:17 EDT 2013

Committee Statement Committee

This Second Revision implements changes in terminology that are consistent with changes

12/6/2013 5:02 PM

National Fire Protection Association Report

54 of 71

Statement:

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

made at the First Draft stage.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

55 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 37-NFPA 30B-2013 [ New Section after A.6.4.1(4) ]

A.6.5.1.2 The maximum quantity of storage of plastic aerosol X products is limited to what is provided in 6.5.1.2 because no demonstrated protection criteria are available.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Wed Oct 16 21:26:58 EDT 2013

Committee Statement Committee Statement: This Second Revision adds companion annex text to Second Revision No. 36. Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

56 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 19-NFPA 30B-2013 [ Chapter B [Title Only] ]

Mechanism of Fire Growth in Aerosol Containers Products

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 22:04:47 EDT 2013

Committee Statement Committee Statement:

This Second Revision implements a change that is consistent with amendments to definitions made at the First Draft stage.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

57 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 20-NFPA 30B-2013 [ Section No. B.1 ]

12/6/2013 5:02 PM

National Fire Protection Association Report

58 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

B.1 Introduction.

12/6/2013 5:02 PM

National Fire Protection Association Report

59 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

The automatic fire protection alternatives given in Chapter 6 of this code are derived from more than a dozen aerosol product fire tests conducted by a major insurance company in the late 1970s and early 1980s [see Table B.1(a) and Table B.1(b) ], and more than 50 small-, medium-, and large-scale tests sponsored by the aerosol products industry in the 1980s [see Table B.1(c) through Table B.1(g) ]. This aerosol products fire research represents a significant body of knowledge regarding aerosol fire development and control for various types of aerosol products in metal containers in various storage and protection scenarios. A complete and detailed history of these aerosol product storage research efforts can be obtained on request from the Chemical Specialities Manufacturers Association, Inc., in the form of a series of articles entitled “An Industry Responds: A Technical History of the CSMA Aerosol Warehouse Storage Fire Protection Research Program.” Send requests to the attention of the Director of Scientific Affairs, Chemical Specialities Manufacturers Association, Inc., 1913 I Street N.W., Washington, DC 20006. Aerosol product warehouse storage fires, using standard fire test igniters, begin as cardboard fires. The fire grows up the flue, burning off the aerosol carton faces, and there is usually a flame 1.5 m to 3.0 m (5 ft to 10 ft) above the top of the array before the first aerosol container ruptures and aerosol products become involved in the fire. Depending on the type of aerosol product, the first container rupture tends to occur at 30 seconds to 60 seconds after ignition in rack storage arrays and 90 seconds to 120 seconds in palletized storage arrays. When aerosol containers begin to rupture, some of the heat from the fuel added by the aerosol product goes quickly to the ceiling, while some is absorbed into other aerosol products, bringing them closer to, or exceeding, their burst pressure. Early application of adequate densities of sprinkler water is the most effective way to control or suppress an aerosol product fire, avoiding a chain reaction that can lead to loss of control. For this reason, early suppression fast response ( ESFR) sprinkler protection is especially effective for aerosol products. Table B.1(a) Spray Sprinkler Tests Test No. 1

2

3

4

5

6

7

Alcohol

Alcohol

Toluene

Alcohol

Toluene

Alcohol

Toluene

8

24

8

12

12

8

1

Rack

Rack

Rack

Palletized

Palletized

2×2×2

Palletized

13

16

43

4

92

64

36

Time of Operation of First Sprinkler, in min:sec

1:52

2:06

2:19

3:05

3:03

1:26

9:23

No. of In-Rack Sprinklers Operated

5

6

5









1292

1334

1493

938

2216

1789

1905

(700)

(723)

(812)

(503)

(1213)

(976)

(1040)

3:19

5:41

3:48

3:09

4:54

4:26

9:58









2:16

3:32

0:52

642

815

973

378

1439



626

(339)

(435)

(503)

(192)

(782)



(330)

Aisle Jump

No

No

Yes

No

Yes





Fire Controlled

Yes

Yes

No

Yes

No

No

No

Type of Aerosol Base Product No. of Pallet Loads Storage Configuration No. of Ceiling Sprinklers Operated

Maximum Near-Ceiling Gas Temperature, in °F (°C) Time of Maximum Gas Temperature, in min:sec Time Above 1000°F (538°C) Maximum Near-Ceiling Steel Temperature, in °F (°C)

All Tests

12/6/2013 5:02 PM

National Fire Protection Association Report

60 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1

2

3

4

5

6

7

Table B.1(b) Spray Sprinkler Tests Test No. 1

2

3

4

5

9

10

0.6 (24)

0.3 (12)

Toluene Toluene Toluene Toluene Paint Alcohol Perfume Deodorant Toluene

Butane

Ceiling Sprinkler Density, in 0.6 2 2 0.6 (24) 0.6 (24) 0.6 (24) 0.3 (12) (24) gpm/ft (L/min·m ) Type of Aerosol Base Product

6 0.3 (12)

7

8

0.3 (12) 0.3 (12)

No. of Pallets

8

12

24

24

10

1

1

1

24

1

Storage Configuration (r = rack,

r

p

r

r

p







p (2 high)



12

4

5

5

18

4

0

3

44



1:37

2:33

3:37

2:15

2:35

4:21



4:13

2:07



6



5

1













1527 (830)

1177 (636)

790 (421)

2162 1410 1343 697 372 165 (74) 520 (271) (189 1183 (765) (728) (369) (1183 189 ) )

Time of Maximum Gas Temperature, in min:sec

3:32

2:34

3:32

2:17

4:02

4:27

4:50

3:57

4:03

6:13

Time Above 1000°F (538°C)

2:28

0:04

0:28

0:44

0:06







4:56



835 (446)

417 (214)

213 (101)

1557 375 323 170 243 100 (38) 177 (80) (117 847 (191) (162) (77) (847 117 ) )

Aisle Jump

Yes

No

Yes

No

Yes







Yes



Fire Controlled

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

p = palletized, 3 × 4 × 1 high) No. of Ceiling Sprinklers Operated Time of Operation of First Sprinkler, in min:sec No. of In-Rack Sprinklers Operated Maximum Near-Ceiling Gas Temperature, in °F (°C)

Maximum Near-Ceiling Steel Temperature, in °F (°C)

All Tests Test Location

Factory Mutual Test Center, West Glocester, Rhode Island; 30 ft (9 m) high test site.

Ignition

Two cellucotton rolls — 3 in. diam × 3 in. long (7.5 cm × 7.5 cm) each soaked in 4 oz (118 ml) of gasoline. 17

⁄32 in. (13.5 mm) large orifice, 286°F (141°C); 10 ft × 10 ft (2.5 m× 2.5 m) spacing [Tests Protection/Ceiling 1–3, 5, and 9]. 1⁄2 in. (12.7 mm) standard orifice, 286°F (141°C); 10 ft × 10 ft (2.5 m × 2.5 m) spacing [Tests 4, 6–8, and 10].

12/6/2013 5:02 PM

National Fire Protection Association Report

61 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1 Protection/In-Rack

2

3

4

5

6

7

8

9

10

Three 1⁄2 in. (12.7 mm) orifice, 165°F (74°C) rated, upright sprinklers per tier; 30 psi (207 kPa) discharge pressure.

Table B.1(c) Tests on Product and Packaging Changes Data Summary Series 1 Test No. 1

2

3

4

5

6

Paint

Paint

Paint

Paint

Paint

Paint

Rim-vent-

Fire retardant

release cans

cartons

4

33

Maximum Ceiling Temperature, in °F

1010

Time of First Can Rupture

Type of Aerosol Base Product

Shrink-

Methylene

wrapped

chloride

pallets

solvent

4

30

28

5

2141

980

1525

1881

1220

1:31

1:20

1:56

1:25

1:18

1:36

1st First Sprinkler Activation

2:15

1:40

2:40

2:13

1:45

1:55

Final Sprinkler Activation

2:22

5:09

4:12

5:22

4:55

3:06

Est. Estimated Product Damage

60%

70%

40%

80%

70%

75%

Increased fire intensity after 3 min required test to be aborted at 4:30

Fire controlled by five sprinklers in 9–10 min

Packaging Variable



Metal overcaps

Test Results Sprinklers Operated

Comments

Fire built rapidly out

Fire controlled Increased fire by four intensity after 4 of control, sprinklers in min required reaching 6 min, after test to be maximum slow fire aborted at 5:20 in 9–10 min intensity at 6 development min Fire controlled by four sprinklers

All Tests Test Location

20 ft ceiling (tests conducted on 40 ft × 40 ft metal platform).

Ignition

2 Two -pallet array spaced 1 ft apart with ignition between pallets by two half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Protection

Standard orifice sprinklers with 286°F (141°C) links installed 10 ft apart; 29 psi constant 2 water pressure delivering 0.3 gpm/ft .

2 2 2 2 For SI units, 1 ft = 0.3048 m; 1 ft = 0.0929 m ; 1 gpm/ft = 40.743 L/min· m ; 1 psi = 6.895 kPa; 1 gpm = 3.785 L/min. Table B.1(d) Intermediate-Scale Tests Data Summary Series 2 Test No.

Type of Aerosol Base Product Pallet Configuration Sprinkler

1

2

3

4

5

6

Hair spray

Hair spray

Air freshener

Furniture polish

Laundry pre-wash

Toluene/A-70

2×2×2

2×2×3

1×2×1

1×2×1

1×2×1

1×2×1

1

⁄2 in.

17

⁄32 in.

1

⁄2 in.

1

⁄2 in.

1

⁄2 in.

1

⁄2 in.

12/6/2013 5:02 PM

National Fire Protection Association Report

62 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1

2

3

4

5

6

160

160

280

280

280

280

Water Pressure, in psi

30

30

30

30

30

30

Water Density, in 2 gpm/ft

0.3

0.43

0.3

0.3

0.3

0.3

33

23

1

3

3

16

1761

1475

659

603

653

1855

Time of First Can Rupture

1:48

1:50

1:45

1:54

1:51

1:50

1st First Sprinkler Activation

2:02

2:05

3:05

6:08

4:17

2:16

Final Sprinkler Activation

6:36

4:50



6:10

4:20

4:48

50%

75%

20%

50%

75%

65%

Link Temperature, in °F

Test Results Sprinklers Operated Maximum Ceiling Temperature, in °F

Est Estimated . Product Damage

Comments

Poor control; intense fire for 15 min

Fire easily Intensity of fire controlled required test to in 5 min be aborted at by single 8:20 sprinkler

Fire

Fire

controlled

reasonably well controlled

in 9 min

after slow fire build-up in 10–12 min

Intense fire for 8–10 min before any control established

All Tests Test Location

20 ft ceiling (tests conducted on 40 ft × 40 ft metal platform).

Ignition

Ignition by two half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Protection

Sprinklers installed on 10 ft grid.

2 2 2 2 For SI units, 1 ft = 0.3048 m; 1 ft = 0.0929 m ; 1 gpm/ft = 40.743 L/min· m ; 1 psi = 6.895 kPa; 1 gpm = 3.785 L/min. Table B.1(e) Control Mode Specific Application (CMSA) Sprinkler Tests — Intermediate-Scale Data Summary Series 3 Test No.

Type of Aerosol Base Product Pallet Configuration Sprinklers Link Temperature,

1

2

3

4

5

6

Hair spray

Hair spray

Hair spray

Paint

Furniture polish

Paint

2×2×3

2×2×3

2×2×3

2×2×3

0.64 in.

0.64 in.

0.64 in.

0.64 in.

0.64 in.

160

160

160

160

160

17

⁄32 in.

160

2×2×3 2×2×2

7 Paint (RVR/MeCl)

*

1×2×1 1

⁄2 in.

280

in °F

12/6/2013 5:02 PM

National Fire Protection Association Report

63 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1

2

3

4

5

6

7

Water Pressure, in psi

56

50

25

75

50

75

30

Water Density, in 2 gpm/ft

0.6

0.8

0.56

0.96

0.8

0.96

0.3

4

4

18

4

4

4

36

Maximum Ceiling Temperature, in °F

1080

1645

1439

1350

1068

1111

2163

Time of First Can Rupture

1:48

1:45

1:46

1:35

1:56

1:47

1:20

1st First Sprinkler Activation

1:56

1:54

1:53

1:43

2:27

2:01

1:47

Final Sprinkler Activation

2:00

2:01

4:52

1:47

2:28

2:08

3:24

Est Estimated . Product Damage

20%

20%

50%

40%

20%

20%

90%

Inadequate control led to 18 sprinkler activations; potential for fire spread

Fire marginally controlled, but potential for fire spread

Test Results Sprinklers Operated

Comments

Fire controlled in Fire fully 6–8 min and suppressed suppressed in 10 min by 15 min

Fire Very intense controlled Fire well fire; test controlled aborted at in 5–7 in 4–5 min 3:20 min

All Tests Test Location

20 ft ceiling (tests conducted on 40 ft × 40 ft metal platform).

Ignition

Ignition by two half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Protection

Sprinklers installed on 10 ft grid.

2 2 2 2 For SI units, 1 ft = 0.3048 m; 1 ft = 0.0929 m ; 1 gpm/ft = 40.743 L/min · m ; 1 psi = 6.895 kPa; 1 gpm = 3.785 L/min; 160°F = 71°C; 280°F = 138°C. * Rim-vent release container; methylene chloride solvent. Table B.1(f) Control Mode Specific Application (CMSA) Sprinkler Tests — Large-Scale and Intermediate-Scale Data Summary Series 4 Test No. 1

2

3

4

5

Paint

Hair spray

Laundry pre-wash

Antiperspirant

Paint

2-High

3-High

2×2×2

2×2×3

2×2×3

Sprinkler

0.64

0.64

0.64

0.64

0.64

Link Temperature, in °F

160

160

160

160

* 160 (150 RTI)

Type of Aerosol Base Product Pallet Configuration

12/6/2013 5:02 PM

National Fire Protection Association Report

64 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1

2

3

4

5

Water Pressure, in psi

75

50

50

75

75

Water Density, in 2 gpm/ft

0.96

0.8

0.8

0.96

0.96

4

7

4

7

4

1158

1337

1116

1520

895

Time of First Can Rupture

1:30

1:33

2:24

1:45

1:34

1st First Sprinkler Activation

1:49

1:44

2:52

1:49

1:43

Final Sprinkler Activation

1:52

3:42

3:09

6:43

1:48





15%

50%

25%

Test Results Sprinklers Operated Maximum Ceiling Temperature, in °F

Est. Estimated Product Damage

Comments

Fire well controlled in 3–4 min; suppressed in 15–20 min. No fire spread.

Fire well controlled in 6–7 min, despite 2 sprinkler malfunctions. No fire spread.

Fire well controlled in 5 Moderate control, min; suppressed fire persisted 25 within 10–15 min. min; probability Fire spread for fire spread. unlikely.

Fire well controlled in 5 min; suppressed in 15–20 min. Fire spread unlikely.

All Tests Test Location

25 ft ceiling (tests conducted on 40 ft × 40 ft metal platform).

Ignition

Ignition by two half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Protection

Sprinklers installed on 10 ft grid.

2 2 2 2 For SI units, 1 ft = 0.3048 m; 1 ft = 0.0929 m ; 1 gpm/ft = 40.743 L/min · m ; 1 psi = 6.895 kPa; 1 gpm = 3.785 L/min; 160°F = 71°C; 280°F = 138°C. * Response Time Index of 150. Table B.1(g) ESFR Tests Test No.

Aerosol Base Product Aerosol Product Classification

1

2

3

4

5

6

7

8

9

Hair spray

Paint

Paint

Paint

Paint

Paint

Hair spray

Hair spray

Paint

Level 2 Level 3 Rack,

Array Stack Height

Level 3

Level 3 Level 3 Level 3 Level 2 Level 2 Level 3

Rack,

Rack, Rack, Rack, Rack, Rack, Rack, Palletized, 18 ft 10 13 ft 10 15 ft 6 in. 13 ft 7 13 ft 10 13 ft 10 13 ft 10 18 ft 10 13 ft 10 in. in. in. in. in. in. in. in. (4.7 m) (5.7 m) (4.2 m) (4.1 m) (4.2 m) (4.2 m) (4.2 m) (5.7 m) (4.2 m)

12/6/2013 5:02 PM

National Fire Protection Association Report

65 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test No. 1

2

3

4

5

6

7

8

9

11 ft 2 11 ft 2 15 ft 0 15 ft 0 10 ft 0 15 ft 0 6 ft 2 in. 9 ft 6 in. (2.9 4 ft 2 in. in. (3.4 in. (3.4 in. (4.5 in. (4.5 in. (3 in. (4.5 (1.9 m) m) (1.3 m) m) m) m) m) m) m)

Ceiling clearance No. of Sprinklers above Ignition Point

4

4

4

2

1

1

1

2

1

Time of First Sprinkler Operation, in min:sec

1:02

0:42

0:49

0:55

0:35

0:36

0:34

0:56

1:15

Time of Last Sprinkler Operation, in min:sec

1:11

1:06

1:36

6:33

0:35

2:06

0:34

3:44



4

4

4

5

1

61

1

14

1

Peak Temperature,

1045

565

713

1421

256

1447

223

995

200

in °F (°C)

(563)

(296)

(378)

(772)

(124)

(786)

(106)

(535)

(93)

Time of First Container Rupture

1:03

1:01

1:29

0:52

None

0:44

0:46

1:01

0:10

Total Sprinklers Operated

Test Location Tests 1 25 ft ceiling (tests conducted on 40 ft × 40 ft metal platform). through 5 Tests 6 through 9

30 ft ceiling.

Ignition Tests 1, 2, and 4 through 9

Ignition by four half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Test 3

Ignition by two half-igniters (plastic bags containing 4 oz heptane on cotton rolls).

Protection

Sprinklers installed on 10 ft grid.

Note: All of the above tests, except for Test 9, were conducted with 50 psi (3.45 bar) operating pressure. Test 9 used 75 psi (5.2 bar).

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 22:07:32 EDT 2013

Committee Statement Committee Statement:

This Second Revision implements changes that are consistent with amendments to definitions made at the First Draft stage.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

66 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 21-NFPA 30B-2013 [ Section No. C.1 ]

12/6/2013 5:02 PM

National Fire Protection Association Report

67 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

C.1 Data from Various Palletized Aerosol Products in Plastic Containers Fire Tests.

12/6/2013 5:02 PM

National Fire Protection Association Report

68 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Beginning with the first edition of NFPA 30B in 1990, aerosol products in plastic aerosol containers have been limited to a maximum size of 118 ml (4 fl oz) while metal aerosol containers have had a maximum size of 1000 ml (33.8 fl oz). This is based on both the U.S. Department of Transportation (DOT) limitations and the absence of fire research involving aerosol products in plastic containers. The DOT has recently removed the smaller size restriction on aerosol products in plastic aerosol containers. Plastic containers for combustible and flammable liquids have been found to be a greater fire risk than metal containers. The assumption is then that plastic might pose a greater risk than metal when used as containers for aerosol products. The recent removal of the DOT limitation has prompted the beginning of fire research with aerosol products in plastic containers. , and initial Initial tests are now recorded presented in this Annex C. Table C.1(a) is taken from Table 1 of the Underwriters Laboratories Inc. (UL) Research Technical Report, “Palletized Plastic Aerosol Storage Testing Result.” This table summarizes a full-scale test conducted by Underwriters Laboratories UL and sponsored by a manufacturer of aerosol products. This test of aerosols aerosol products in plastic containers on wood pallets was conducted with control mode specific application (CMSA) sprinkler protection. Table C.1(a) Fire Tests of Control Mode Specific Application (CMSA) Sprinkler Protection of Aerosol Products in Plastic Containers Test Number & Date

Test 1

9/29/2009

Test Parameters Storage T t ype

Palletized Aerosol in Plastic Containers plastic containers

Commodity T t ype

Foam Shaving Cream shaving cream ,

Commodity D d escription

Log (No. 9114)

Main T t est A a rray of P p allets

2 wide by 2 long by 3 high

Nominal P p allet S s torage H h eight (ft)[m] [ft (m)]

14 [ ( 4.3] )

Building T t est S s ite C c eiling H h eight (ft)[m] [ft (m)]

25 [ ( 7.6] )

Sprinkler to C c ommodity C c learance (ft)[m] [ft (m)]

Centered Between Four Sprinklers between four sprinkers

Ignition L l ocation Nominal D d eflector to ceiling (in.)[mm] [in(mm)]

7 [ ( 178] ) 155°F standard response (Standard Response 68°C ) [ 68°C ]

Sprinkler T t emperature R r ating Ceiling Sprinklers

Upright K-11.2 CMSA

Sprinkler Spacing (branchline by sprinkler) (ft)[m] [ft (m)] Applied Flowing Pressure (psi)(bar) Applied Sprinkler Density [gpm/ft /min )[mm/min ]

10 ft, 2 in. [ ( 3.1] )

2

10 × 10 [ ( 3.05 × 3.05] ) 50 [ ( 3.4) ]

(gpm/ft

2

mm

0.79 [ ( 32] )

Fire Test Results Length of T t est (min:sec) Number of O o perated C c eiling S s prinklers

32:00 4

Time of F f irst N n oticeable C c ontainer R r upture (min:sec)

0:55

Time of F f lame B b reach at T t op of A a rray (min:sec)

0:59

First C c eiling S s prinkler O o peration (min:sec)

1:23

Last C c eiling S s prinkler O o peration (min:sec)

1:33

Peak G g as T t emperature at G g as A a bove I i gnition ( °F )[ C° ] [°F (°C)]

1242 [ ( 672] )

Maximum 1–m M inute A a verage s S teel T t emperature A a bove I i gnition (°F)[C°] [°F (°C)]

583 [ ( 306] )

12/6/2013 5:02 PM

National Fire Protection Association Report

69 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Test Number & Date

Test 1

9/29/2009

Table C.1(b) is taken from Table E-1 of the Underwriters Laboratories Inc. (UL) Research Technical Report, “Large Drop Sprinkler Protection of Palletized Storage of Aerosols in Plastic Containers on Wood Pallets Testing Result.” This table summarizes a full-scale palletized array test conducted by Underwriters Laboratories UL and sponsored by a manufacturer of aerosol products. This test of aerosol products in plastic containers on wood pallets was conducted with control mode specific application (CMSA) sprinkler protection. Table C.1(b) Fire Tests of Control Mode Specific Application (CMSA) Sprinkler Protection of Palletized Storage of Aerosol Products in Plastic Containers on Wood Pallets Test Number & Date

Test 1

4/29/2008

Test Parameters Storage Type

Palletized

Commodity Type

Aerosol in Plastic Containers plastic containers

Main Test Array of Pallets

*

2 wide × 2 long × 3 high

Nominal Pallet Storage Height (ft)[m] [ft (m)]

10 [3.05]

Ceiling Height (ft)[m] [ft (m)]

30 [9.1]

Sprinkler to Commodity Clearance (ft)[m] [ft (m)]

19 ft, 5 in. [5.9] Centered between

Ignition Location

four sprinklers

Nominal Deflector to Ceiling (in.)[mm] [in. (mm)] Sprinkler Temperature Rating (°F)[°C] [°F (°C)]

7 [178] 155°F Standard Response (Standard Response 68°C ) [68°C] Upright K-11.2

Ceiling Sprinklers

CMSA

Sprinkler Spacing (branchline by sprinkler) (ft)[m] [ft (m)] Applied Flowing Pressure (psi)[bar] [psi (bar)] 2

Applied Sprinkler Density ( [ gpm/ft (mm/min ) [mm/min ]

10 × 10 [3.05 × 3.05] 75 [5.2] 0.97 [39.5]

Fire Test Results Length of Test (min)

32

Number of Operating Sprinklers

4

Time of First Noticeable Container Rupture (min:sec)

1:12

Time of First Sprinkler Operation (min:sec)

1:47

Time of Last Sprinkler Operation (min:sec)

1:49

Peak Gas Temperature at Ceiling Above Ignition (°F)[C°] [°F (°C)]

884 [ ( 473) ]

Maximum 1 Minute Average Gas Temperature (°F)[C°] [°F (°C)]

472 ( [ 244) ]

Peak Steel Temperature at Ceiling Above Ignition (°F)[C°] [°F (°C)]

173 ( [ 78) ]

Maximum 1 Minute Average Steel Beam Temperature (°F)[C°] [°F (°C)]

168 ( [ 75] )

Estimated Product Damage

50%

* Nominal 851 g (30 oz) plastic containers filled with a 35% 35 percent ethanol/65% 65 percent water mixture with propane, butane, and isobutane used as a propellant. The calculated heat of combustion was reported to be 10.85 kJ/g. UL did not verify the ingredients or the heat of combustion of this reported

12/6/2013 5:02 PM

National Fire Protection Association Report

70 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

mixture. This information was provided by the test sponsor. Source: Underwriters Laboratories Inc.

Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization:

[ Not Specified ]

Street Address: City: State: Zip: Submittal Date:

Tue Oct 15 22:10:45 EDT 2013

Committee Statement Committee Statement:

This Second Revision implements changes that are consistent with amendments to definitions made at the First Draft stage.

Response Message:

12/6/2013 5:02 PM

National Fire Protection Association Report

71 of 71

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

Second Revision No. 41-NFPA 30B-2013 [ Section No. J.3 ]

J.3 References for Extracts in Informational Sections. NFPA 30, Flammable and Combustible Liquids Code, 2008 2015 edition.

Submitter Information Verification Submitter Full Name: Robert Benedetti Organization:

National Fire Protection Assoc

Street Address: City: State: Zip: Submittal Date:

Tue Nov 05 13:06:31 EST 2013

Committee Statement Committee Statement: This Second Revision updates the adoption date of citation to extract text publication. Response Message:

12/6/2013 5:02 PM