Ultrasonic Motion Detector 752/225CU

Installation Instructions

22555 F1453-02 752-225CU Instruction.indd 1

23/02/2011 3:19:27 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

Table of Contents 1.0 Introduction .....................................................................................................3 2.0 How it Works ....................................................................................................3 2.1 Ultrasonic Detection...................................................................................3 3.0 Identification of Parts .....................................................................................4 3.1 Detector .....................................................................................................4 3.2 Power Supply .............................................................................................4 4.0 Location............................................................................................................5 5.0 Detection Pattern .............................................................................................5 6.0 Mounting Procedure ........................................................................................6 7.0 Wiring Diagram ................................................................................................6 8.0 Commissioning................................................................................................7 9.0 Logic Bypass Function ...................................................................................7 10.0 Technical Specifications .................................................................................8 11.0 Troubleshooting...............................................................................................9 12.0 Notes......................................................................................................... 10-11 13.0 Warranty ........................................................................................................12

© Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 2

23/02/2011 3:19:27 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

1.0 Introduction The Clipsal 752/225CU Motion Sensor uses ultrasonic technology to perform the ultimate task of sensing.

2.0 How it Works 2.1.Ultrasonic Detection The 752/225CU consists of a transmitter and receiver transducer to provide total volumetric sensing with no blind spots. The sensor operates on 24V d.c. and is designed to work with the 752PR power and relay switching module (supplied). When someone enters a room in which the sensor controls the lighting, the lights are turned on automatically, and in this manner the load can be controlled. The signal derived activates an adjustable timer (30 seconds to 30 minutes), which in turn activates an electrical relay in the power pack, turning the lights on. If no movement or presence is detected for the time selected the relay de-energises, turning the lights and load off. The 752PR device has a C-Bus auxiliary unit connection terminal, which is to be connected only to a C-Bus L5504AUX or C-Bus bus coupler unit.

© Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 3

3 of 12

23/02/2011 3:19:27 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

3.0 Identification of Parts 3.1 Detector

(To 752PR Power Supply) 752LD 1m Lead

Back Mounting Plate Time Delay Adjustment (refer to Time Delay Table)

Sensitivity Adjustment (for ultrasonic

84mm Mounting Centres

6 Way Connectors Detail

Adjustment Access Cover

detection)

Ultrasonic Sensors

3.2 Power Supply Cover

Cut out to suit load cable PCB Fixing Screws

Incoming Mains Supply Cable

Load Output Terminals

752LD Lead Connector for 752LD (lead to sensor) Output for connection to C-Bus bus coupler or auxiliary unit

Base 4 of 12

22555 F1453-02 752-225CU Instruction.indd 4

© Clipsal Australia Pty Ltd

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

4.0 Location The best position to mount the sensor is on the ceiling in the centre of the room. It has a nominal coverage of 15m x 15m (225m2) with 360° coverage.

B

A

Plan of Room (example) Best position

Plan of Room (example) Incorrect positions

Note: Do not mount close to objects which can change temperatures rapidly e.g. air-conditioning vents, heater flues.

5.0 Detection Pattern Maximum detection pattern 1/2 Step Walking Detection

12m

Motion at Desk Coverage

Sensor

14m

Detection patterns are based on standard 3m ceilings and tile floors. In large carpeted areas, a higher sensitivity may be required to overcome the absorbtion of the ultrasonic waves by the carpet. © Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 5

5 of 12

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

6.0 Mounting Procedure 1. Fit power supply in ceiling space within 1m of sensor position. (Fit surface mount socket or similar for supply from lighting circuit.) a. Fix base of power supply to beam. b. Fix PCB to base using screws provided. c. Fit 752LD (1m lead) to connector on PCB at extra low voltage end. d. Fit load cables to terminals on PCB, stripped to length as shown. e. Cut out cover as required to suit load cables.

20mm

9mm

f. Screw cover to base. 2. Fit sensor to ceiling in (a predetermined) position. a. Fix mounting flange to ceiling. b. Cut hole for 752LD lead cable (Ø20mm hole). c. Fit 752LD lead to sensor. d. Fix sensor to mounting flange and secure using side fixing screws.

7.0 Wiring Diagram Hard wired incoming mains

AEN

752PR Module Mains Side

SW A E N

Switched Active

Extra Low Voltage Side Control A B

752LD LEAD 6 Way Cable (1m)

Output for connection to C-Bus auxiliary unit L5504AUX or bus coupler

752/225CU Sensor Head LIGHTING LOAD

Warning It is recommended that this product should be hard wired as per the wiring diagram. When connecting multiple 752PR modules to control the same load, 3 pin plugs or similar must not be used, as this can result in the plugtop pins becoming ‘live’ under certain conditions. For safety reasons, it is recommended to always shut down power to all relevant circuits before undertaking any installation or maintenance of this product. 6 of 12

22555 F1453-02 752-225CU Instruction.indd 6

© Clipsal Australia Pty Ltd

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

8.0 Commissioning Once power has been installed, determine which sensitivity setting and time delay best suits the application.

Time Delay Tables Example of timer settings in minutes

Approximate Sensitivity Adjustment

Stock Room

=# 15

18m²

Room =#1

Hallways

=# 10

37m²

Room =#2

Restroom

=#7

56m²

Room =#3

Office

=#8

75m²

Room =#4

Classroom

=#9

93m²

Room =#5

110m²

Room =#6

140m²

Room =#7

Note: When making adjustments do not attempt to force adjustment screw past limits.

9.0 Logic Bypass Function Note: When logic key or paper clip is inserted into the slot lights will always be on. There is no shock hazard present when using a logic key or a paper clip. This bypass function is for emergency use only.

© Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 7

7 of 12

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

10.0 Technical Specifications Model

752/225CU Ultrasonic Motion Detector.

Time Delay Adjustment

Variable from approximately 30 seconds to 30 minutes.

Coverage

360° (walking) = 14m x 14m, (motion at desk) = 12m x 12m (Note: mounted in classroom with 3m ceiling height).

Room Size Adjustment

Sensitivity adjustment for ultrasonic detection.

Bypass Override Function

Logic key or paper clip. Only for emergency use.

Walk Test Indicator

Red LED = Ultrasonic.

Ambient Ranges

Operating Temperature = (0°C to 50°C) Humidity - 0-95% RH non-condensing.

Colour

White

Enclosure

High-impact U.L. approved material with base to comply with all flammability rating standards.

Description

Diameter: 125mm, Body Depth: 43mm, Weight 200g.

752 Power Supply and Switched Module (752PR) Operating Voltage Range

192V a.c. min.- 265V a.c. max.

Rated Nominal Voltage

240V a.c.

Operating Frequency

50Hz

Output Power

7VA max. @ 240V

Unfiltered d.c. Voltage Output @ 240V a.c. Input (no load)

24V max.

Continuous d.c. Load Current Allowed

100mA max.

Switched Active Contact Rating (N.O.)

240V a.c. 10AX max. suitable for fluorescent, inductive and incandescent loads.

C-Bus Output Connection

Compatible with C-Bus bus coupler or auxiliary unit.

Operating Temperature Range

0°C min. - 50°C max.

Number of 752 Series Motion Detectors allowed to connect

One

8 of 12

22555 F1453-02 752-225CU Instruction.indd 8

© Clipsal Australia Pty Ltd

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

11.0 Troubleshooting Problem

The power is restored and the red and LED does not blink when making motion.

Solution A

Adjust sensitivity and set level to a higher setting as required by observing red LED.

Solution B

Remove sensor and measure if 24V d.c. is present between red and black leads. If no voltage is present, check power connection and power/switch pack. If voltage is present, replace sensor with new one and send defective sensor to Clipsal Australia Pty Ltd.

Problem

Lights are on continuously and do not shut off when no one is present.

Solution

Re-check all your connections then disconnect sensor while power is still on. If lights remain on, this indicates that there is a short in the 752LD Lead connecting the sensor and the power/switch module. Solution to this problem is to replace the 752LD Lead. Check also for external causes such as excessive turbulence (hanging mobiles, etc).

Problem

Lights will not switch on even after sensor is disconnected and red and blue wires are shorted.

Solution

This could indicate a broken wire in the 752LD Lead. Next, disconnect the 752LD Lead at the power/switch module and short the pins where the red and blue wires connect. If lights still do not switch on, replace power/switch module after checking if all connections were made correctly.

Problem

LED blinks but lights will not switch on.

Solution

Check if sensor is working when bypassing all electronics. This can be done by inserting the key provided with each unit. If lights switch on, replace defective sensor.

Problem

After all connections are verified, lights stay on when no one is present, and from time to time LED blinks.

Solution

Turn sensitivity adjustment to a lower setting.

© Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 9

9 of 12

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

12.0 Notes

10 of 12

22555 F1453-02 752-225CU Instruction.indd 10

© Clipsal Australia Pty Ltd

23/02/2011 3:19:29 PM

752/225CU

Ultrasonic Motion Detector Installation Instructions

12.0 Notes

© Clipsal Australia Pty Ltd

22555 F1453-02 752-225CU Instruction.indd 11

11 of 12

23/02/2011 3:19:29 PM

13.0 Warranty 1) The benefits conferred herein are in addition to, and in no way shall be deemed to derogate; either expressly or by implication, any or all other rights and remedies in respect to Clipsal Product, which the consumer has under the Commonwealth Trade Practices Act or any other similar State or Territory Laws. 2) The warrantor is Clipsal Australia Pty Ltd of 33-37 Port Wakefield Road, Gepps Cross, SA 5094. With registered offices in all Australian States. 3) This Clipsal Product is guaranteed against faulty workmanship and materials for a period of two (2) years from the date of installation. 4) Clipsal Australia Pty Ltd reserves the right, at its discretion, to either repair free of parts and labour charges, replace or offer refund in respect to any article found to be faulty due to materials, parts or workmanship. 5) This warranty is expressly subject to the Clipsal Product being installed, wired, tested, operated and used in accordance with the manufacturer’s instructions. 6) All costs of a claim shall be met by Clipsal Australia Pty Ltd, however should the product that is the subject of the claim be found to be in good working order, all such costs shall be met by the claimant. 7) When making a claim, the consumer shall forward the Clipsal Product to the nearest office of Clipsal Australia Pty Ltd with adequate particulars of the defect within 28 days of the fault occurring. The product should be returned securely packed, complete with details of the date and place of purchase, description of load, and circumstances of malfunction. For all warranty enquiries, contact your local Clipsal sales representative. The address and contact number of your nearest Clipsal Australia office can be found at http://www.clipsal.com/locations

Clipsal Australia Pty Ltd A member of Schneider Electric

Contact us: clipsal.com/feedback National Customer Care Enquiries:

Tel 1300 2025 25 Fax 1300 2025 56 F1453/02

10339261

22555 F1453-02 752-225CU Instruction.indd 12

clipsal.com Clipsal Australia Pty Ltd reserves the right to change specifications, modify designs and discontinue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifications and other information in this catalogue are correct, no warranty is given in respect thereof and the company shall not be liable for any error therein. © Clipsal Australia Pty Ltd. The identified trademarks and copyrights are the property of Clipsal Australia Pty Ltd unless otherwise noted. CLIPCOM 22555 February 2011

23/02/2011 3:19:29 PM