Please read these instructions carefully as they will enable you to get maximum efficiency and reliability from your new Calorex Dehumidifier.
Technical Manual DH/TTW 75/110 (SD405452 Iss 10) 09/06/09
HEALTH AND SAFETY WARNING As the dehumidifier embodies electrical and rotational equipment, ONLY competent persons should carry out any work on this type of machine (see warranty).
CONTENTS SECTION 1.0 INSTALLATION INSTRUCTIONS/ USER CHECK LIST. ....................................................... 2 SECTION 2.0 CONTROL LAYOUT & LPHW OPERATION. ........................................................................ 4 SECTION 3.0 MACHINE DIMENSIONS ...................................................................................................... 5 SECTION 4.0 DATA SHEET. ....................................................................................................................... 6 SECTION 5.0 WIRING DIAGRAMS ............................................................................................................ 7 SECTION 6.0 REFRIGERATION CIRCUIT .................................................................................................. 9 SECTION 7.0 PERFORMANCE GRAPHS ................................................................................................. 10 SECTION 8.0 SPARE PARTS LISTS ......................................................................................................... 11 SECTION 9.0 OPTIONAL ITEMS, REMOTE CONTROLS. ....................................................................... 19 SECTION 10.0 WARRANTY CONDITIONS ............................................................................................... 21
Page 1
SECTION 1.0 INSTALLATION INSTRUCTIONS/ USER CHECK LIST. HEALTH & SAFETY WARNING. As the Heat Pump contains electrical and rotational equipment , it is recommended that ONLY competent persons carry out any work on this type of machine (see warranty). ISOLATE ELECTRICALLY BEFORE ENTERING MACHINE OR REMOVING PANELS. REMOVE PANEL (4 SCREWS) TO LOCATE MAINS ELECTRICAL TERMINAL BLOCK.
FIG.1
STANDARD MACHINE
1234567890123456789012345678 1234567890123456789012345678 1234567890123456789012345678 SAFETY 1234567890123456789012345678 1234567890123456789012345678 Remove grille from outer cover 1234567890123456789012345678 before removing the cover from 1234567890123456789012345678 1234567890123456789012345678 the machine. 1234567890123456789012345678
OUTER COVER FITTED TO STANDARD MACHINES ONLY
GRILLE
STANDARD & TTW MACHINE
FIXING SCREWS (3) LOCATED BEHIND GRILLE
INSTALLATION - MODEL DH75/110 1. Remove machine from packaging and set on a level surface. Check that machine is level both vertically and horizontally. 2. Remove covers as shown in FIG.1 relative to machine type installed. 3. Electrical supply to unit must be sized according to the data on serial number label paying special attention to I.E.E. regulations latest edition regarding the special conditions governing electrical supply to machines in potentially damp areas (DH75/110 are IP45). 4. The electrical supply should be connected to the terminal block mounted inside the electrical box found in the top corner of the machine, see fig1, 2 & 4. Wires to be connected as follows :- Brown/Red to Live, Blue/Black - to Neutral, and Earth to stud provided. 5. Fan mode switch can be set to cycle fan, then when Hygrostat senses demand, but should be set to continuous to promote good air circulation and reduce condensation. Note that on models fitted with LPHW and or remote Hygrostat the fans will start automatically whenever there is an air heating or dehumidification demand. During defrost the fans will stop. (Fan cycle not recommended for TTW machines with humidistat only). Set Fan Speed switch to ‘High’ for maximum duty, ‘Low’ for minimum sound. 6. Locate drain, 15mm compression fitting, on side of unit and run it away to waste as preferred. A single hole is provided in the side of the unit. The drain is factory fitted to this hole. (In TTW machines there is an alternate position, see drawings). MODELS WITH LPHW FITTED 7. Connect water circuit piping to the 22mm stubs provided on the side of the machine as per diagram. 8. It is recomended that isolation valves are fitted to enable isolation of the machine in the event of service. The Circulating Pump must be sized to take into account the design flow rate of the machine plus the water system resistance (Flow Rate 9.6 L/min Pressure Drop 2.8 m hd). FIG.2
FIG.3 LPHW SCHEMATIC
MAINS IN PORT A TO COIL
PORT B LPHW OUT
BOILER
LPHW CONNECTIONS LOCATED IN CABINET
RADIATORS IF FITTED FLOW METER
LPHW OUT LPHW IN
FLOW BALANCE VALVE
PUMP
3 WAY MOTORISED VALVE (DIVERTING) .
CONDENSATE DRAIN PORT AB LPHW IN
DH75/110
CONNECTIONS FOR REMOTE 12V AIR THERMOSTAT & OPTIONAL HYGROSTAT. FIG.4
FIG.5 L/L1
L2
L3
FUSED MAINS ELECTRICAL SUPPLY
N
SIGNALERING OP VERZOEK BIJ LPHW KETEL (INDIEN VOORZIEN)
REMOTE 12V AIR TEMP THERMOSTAT FOR LPHW AVAILABLE FROM MACHINE CALOREX AVAILABLE FROM CALOREX
9
REMOTE 12V HYGROSTAT
8
7
6
5
DE AANSLUITINGEN 5 TOT 9 ZIJDE ELEKTRISCHE KAST (AAN DE ZIJKANT)
Page 2
9. Connect remote Hygrostat as shown, ensure that knob on MACHINE HYGROSTAT is set FULLY ANTICLOCKWISE. 10. When LPHW coil & valve are fitted, a remote air temperature thermostat must be connected as shown.
USER CHECK LIST OPERATION A normal hygrostat setting (50-60%) is marked on the console. Minimum air temperature 5°C. Note :- The fan stops during defrost. The fan will start automatically, as required, on machines fitted with LPHW and or remote Hygrostat (fan control switch set to cycle). OPERATING a. Ensure air inlets/outlets and filters are kept clear and clean. Filters are located behind inlet grille. b. Wipe clean with damp cloth or cleaning fluid suitable for painted surfaces. Note. The Reply Paid Warranty Registration Card must be returned to ensure the correct warranty is given. If you do not find a Registration Card with your machine, please contact Calorex Service Department or your dealer giving your name, address and serial number of your machine, a card will then be sent to you. FILTER CLEANING The filter can be washed in warm, soapy water, rinsed and shaken dry before replacement. Frequency of cleaning depends on user although no more than two months should elapse between cleaning. The dehumidifier must not be run without a filter fitted. MACHINE NOT RUNNING AT ALL. CHECK THE FOLLOWING. 1. Is supply switched on? 2. Is supply fuse healthy?. 3. Turn Hygrostat knob fully clockwise. 4. Check air inlet and outlet for obstructions and that the filter is not blocked. 5. Check fault lamp - if illuminated reset the HP and LP switches (see control panel layout on page 4). 6. If, after carrying out the above and waiting 30 mins, the machine does not start, telephone for service. MACHINE FAN ONLY RUNNING 7. Turn Hygrostat knob fully clockwise. 8. Check air inlet and outlet for obstructions and that filter is not blocked. 9. Check that HP and LP switch are reset,(see control panel layout on page 4) if after 30 mins the machine has not restarted, telephone for service. WATER LEAKING FROM BASE OF UNIT 10. Check connection from machine to drain for blockages and clear accordingly. Check fall is adequate. 11. Check that machine is level both vertically and horizontally. 12. Check that “tun dish”, if fitted, is not blocked (see below). The user check list should be carried out before initiating a service call. Do not attempt to interfere with any internal control settings as these have been factory calibrated and sealed. If in doubt or if advice is required, contact Calorex Service Department. Telephone (01621)857171 or 856611.
DH75/110 (COPPER STUB)
CUSTOMERS "TUN DISH"
DH75/110 UNIT
DRAIN TO WASTE
'U' TRAP
Page 3
SECTION 2.0 CONTROL LAYOUT & LPHW OPERATION. SECTION 2.1 CONTROL LAYOUT
LP SWITCH RESET MAINS LAMP
30%
20%
60%
80%
HYGROSTAT CONTROL
HP SWITCH FAULT LAMP RESET
LOW SPEED
FAN SPEED SWITCH
HIGH SPEED
DEFROST LAMP
SECTION 2.2 LPHW OPERATION The 3 way, motorised, diverting valve fitted to machines with the LPHW option is operated by a remote 12V AC air temperature thermostat (available from Calorex). When the valve is energised the flow is through the LPHW coil. When the valve is unenergised the flow is diverted. NOTE :- When the fan switch is set to cycle and the fan is not running, a demand on the LPHW valve will cause the fan to automatically start.
Page 4
SECTION 3.0 MACHINE DIMENSIONS STANDARD MACHINE WITH COVER 1532.00
385.00
1520.00
675.00 (MAINS IN PG16)
69.00 (DRAIN 15mm)
402.00 (LPHW IN 22 DIA)
AIR
502,00 (LPHW OUT 22 DIA)
796.00
AIR
30.00
THROUGH THE WALL MODEL 1512.00 1474.00 980.00 350.00
AIR
1167.00
988.00
AIR
342.00
AIR SAMPLE TUBES DO NOT OBSTRUCT
260.00
AIR
138.00
888.00
780.00
62.00
VIEW FROM POOL HALL SERVICE REQUIREMENTS
FILTER
1500.00*
1500.00 800.00*
RECOMMENDED TO PREVENT RECIRCULATION
* DIMENSIONS MARKED THUS ARE RECOMMENDED FOR SERVICE ACCESS
30.00 DRAIN TTW ONLY MACHINE AND DUCT MUST BE SEALED TO WALL AND ALL CAVITIES BRIDGED TO PREVENT RECIRCULATION
800.00*
STANDARD MACHINE WITH COVER
800.00*
THROUGH THE WALL MODEL Page 5
SECTION 4.0 DATA SHEET. MODEL
DH75AX DH110AX DH110BX TTW75AX TTW110AX TTW110BX
DUTY DEHUMIDIFICATION AIR HEATING (SENSIBLE) DEHUMIDIFIER ONLY
L/hr kW
3,6 4,7
4,5 6,4
4,5 6,4
3,6 4,7
4,5 6,4
4,5 6,4
AIR HEATING (SENSIBLE) DEHUMIDIFIER & LPHW
kW
11,3
12,2
12,2
11,3
12,2
12,2
AIR HEATING (SENSIBLE) LPHW ONLY
kW
8,9
8,9
8,9
8,9
8,9
8,9
kW kW
0,16 1,46
0,16 2,12
0,16 1,94
0,16 1,46
0,16 2,12
0,16 1,94
230V ~1N
230V ~1N
400V ~3N
230V ~1N
230V ~1N
400V ~3N
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
AMP
13
20
10
13
20
10
FULL LOAD AMPS (MIN SUPPLY CAPACITY)
AMP AMP
6,4 9,5
9,3 12
4,2 5,5
6,4 9,5
9,3 12
4,2 5,5
COMPRESSOR LRA
AMP
55
66
30
55
66
30
AIR DATA AIR FLOW (NOMINAL)
m³/h
1180
1180
1180
1180
1180
1180
NOMINAL POWER CONSUMED FAN ONLY COMPRESSOR AND FAN ELECTRICAL DATA ELECTRICAL SUPPLY MAX FUSE RATING NOMINAL RUNNING
WATER DATA LPHW FLOW RATE
L/min
9,6
9,6
9,6
9,6
9,6
9,6
LPHW PRESSURE
m hd
2,80
2,80
2,80
2,80
2,80
2,80
L
0,63
0,63
0,63
0,63
0,63
0,63
LPHW COIL VOLUME GENERAL DATA HERMETIC SYSTEM REFRIGERANT SOUND PRESSURE LEVEL @ 1m
kg R407c
2
2
2
2
2
2
dB(A)
53
53
53
53
53
53
1474
DIMENSIONS WIDTH
(UNPACKED
mm
1520
1520
1520
1474
1474
DEPTH
(UNPACKED
mm
385
385
385
350
350
350
HEIGHT
(UNPACKED
mm
796
796
796
1167
1167
1167
WEIGHT WIDTH
(UNPACKED STD/LPHW (PACKED)
kg
143/147
144/148
144/148
143/147
144/148
143/147
mm
1575
1575
1575
1575
1575
1575
DEPTH
(PACKED)
mm
420
420
420
420
420
420
HEIGHT
(PACKED)
mm
932
932
932
932
932
932
WEIGHT
(PACKED)
kg
163/167
164/168
164/168
163/167
164/168
163/167
STD/LPHW
NOTES:a) These performance figures are based on air @ 30º C and 60% RH & pool water @ 28º C, boiler water at 80º C. b) Hygrostat adjustable from 20% to 80%RH. c) Minimum air temperature on standard models 5º C, Maximum air temperature on standard models 40º C. d) R407c Global warming potential (GWP) 1700.
Page 6
HP
CAPACITOR FAN
CAPACITOR SLOW
CAPACITOR FAST
DELAY TIMER
FUSE
DEFROST THERMOSTAT
C3
C4
C5
D
F
FT
LPHW THERMOSTAT
SOLENOID VALVE
SH
Y
DEHUMIDISTAT
S2
TH
SWITCH FAN SPEED
S1
TRANSFORMER
SWITCH FAN MODE
R
THERMAL CUTOUT
RELAY/ CONTACTOR
MV
TC
FAN MOTOR
MC
T
LOW PRESSURE SWITCH
COMPRESSOR MOTOR
LP
HIGH PRESSURE SWITCH
HP
LAMP
CAPACITOR RUN
C2
H1-3
DEFROST THERMOSTAT/TIMER
CAPACITOR START
C1
F
SH HYGROSTAT BREAKS ON FALL
A
L
H3
A1
A2
D
6
5
R3
4
LP
3
CONT
R2
3
1
3 4
6
2
A
7
9
MV 1~
C5
C4
T
REMOTE HYGROSTAT
12V
VOLT FREE
LPHW BOILER GO SIGNAL
CONDENSATEUR DU COMPRESSEUR
SELECTEUR DE MODE DU VENTILATEUR
RELAIS/ KONTAKTGEBER
MOTEUR DU VENTILATEUR
COMPRESSEUR
REINITIALISATION DEFAUT BASSE PRESSION
REINITIALISATION DEFAUT HAUTE PRESSION
LAMPE
THERMOSTAT DE DEGIVRAGE
SICHERUNG
TEMPORISATEUR
CONDENSATEUR DU RAPIDE
CONDENSATEUR DU LENT
CONDENSATEUR DU VENTILATEUR
ONTDOOIKLEP MET SPOEL
PVWV-STAT
UBERHITZUNGSSCHUTZ
TRANSFORMATOR
HYGROSTAAT
VANNE ELECTROMAGNETIQUE
THERMOSTAT LPHW
PROTECTION THERMIQUE
TRANSFORMATEUR
HYGROSTAT
SCHALTERANHANGERGESCHWINDIGKEIT LE MOUVEMENT DE VENTILATEUR DE COMMUTATEUR
GEBLASESCHALLTER
RELAIS
VENTILATORMOTOR
COMPRESSOR
LAGEDRUKPRESSOSTAT
HOGEDRUKPRESSOSTAT
LAMPE
ONTDOOI THERMOSTAAT
FUSIBLE
TIJDVERTRAGING
CONDENSATOR SCHNELL
CONDENSATOR VERLANGSAMEN
CONDENSATOR VENTILATOR
CONDENSATOR COMPRESSOR
THERMOSTAT DE DEGIVRAGE TEMPORISE
9
6
12V
CONDENSATEUR DU COMPRESSEUR
230V
12V
R1
3
(OPTIONAL)
LPHW VALVE
7
REMOTE STAT
Y
H2
C3
1 R4
3 4
COMPRESSOR RELAIS
HIGH
ONTDOOIKLOK
H1
S1
C2
LOW
VALVE ENERGISED - FLOW THROUGH COIL VALVE UNENERGISED - FLOW DIVERTED
1
4
S2
MC
CYCLE
9
N
BROWN
GRN/YEL
VIO
S1
CONT
GROEN / GEEL
PAARS
WIT
ROOD
ROZE
ORANJE
GRIJS
BRUIN
BLAUW
ZWART
RED/ORN 0,5 PNK 1,5
BLK 1,5
BRN 0,5
BLU 1,0
RED/ORN 0,5
RED 0,5
BRN 0,5
HARD START CAP
C1
C2 RUN CAP
GREEN/YELLOW
VIOLET
WHITE
RED
RED WHT
PINK
ORANGE
PNK
ORN
GREY
BLUE
BLACK
BRN GRY
BLU 0,5
GRN/YEL 1,0
BRN 1,50
ROCKER SWITCH
BLU
BLK
CYCLE
BRN 0,5
BLU 0,50 BLU 0,5
C3 FAN CAP
EARTH
CONSOLE
H1 MAINS
GRY 0,5
BLU 1,50
HYGROSTAT
SH
H2 DEFROST
BRN 0,5
BRN 0,5
BLK
6 LP SWITCH L
H
9
8
GO SIGNAL
LPHW BOILER
7
GRN/YEL 1,0
L
6
VIO 0,5
BRN 0,5
RED/BLK 0,5
LP
5
M LPHW VALVE (OPTIONAL)
FLYING LEAD
BLU 0,5
N
HP
BLU 1,0
BLU 1,50
BRN 1,50 BRN 1,50
L
H
C
2
1
3
DH110
MV FAN
1
21
22
BLU 0,5
4
A2
A1
D DELAY TIMER
BLK
DH75
MV FAN
1
2
PNK 0,5
BLU 0,5
3
BLU 0,5
GRY 0,5
6
VIO 0,5 VIO 0,5
2
STAT
PNK 0,5
REMOTE
4
4
GRN/RED 0,5
REMOTE
R3
5
BRN 0,5
CONTACTOR
3
BLU 1,0
BRN 0,5
RED/BLK 0,5 RED/BLK 0,5
HP SW ITCH
HYGROSTAT
VIO 0,5 PNK 0,5
H3 FAULT
BLU 1,50
C1
F BRN 1,50
BLU 1,0
2
BLU 1,50
ORN 0,5 BLK
BLK
ORN 0,5
GRN/YEL 1,0
Y
DEFROST VALVE
C4 SLOW CAP
HIGH SPEED
S2
COM
T
ORN 0,5 RED/ORN 0,5
BRN 0,5
TRANSFORMER
GRN/YEL 1,0
BASE PLATE
ROCKER SWITCH LOW SPEED
CAP OFF FOR SAFETY
BLU RED
BLU 0,5 PNK 0,5
ORN/BLK 0.5
C
RED/ORN 0,5 WHT 0.5
ORN 0,5
VIO 0,5
VIO 0,5
PNK 1,5
B
A
B
R
9
WHT 0,5
6
GRY 0,5
GRY 0,5
BLU 0,5 BLU 0,5
BRN 0,5
9
7
C5 FAST CAP
W HT 0.5
R2
R1
4
1
3
6
R4
IF FITTED
FLYING LEADS
HEATER
1
4
RED/BLU 0,5
DH/TTW 5.1 DH/TTW 75/11075/110 AX (240V AX (230V ~ 1N 50Hz) ~ 1N 50 Hz)
DRG No D402950
C
3
2
3
1
3
1
A DEFROST STAT/TIMER
ORN/BLK 0.5
S COMPRESSOR
MC
4
6
9
7
4
7
RED 1,5
A
B
A
BRN 0,5
RED/ORN 0,5
BLK 1,5
BLU 0,5
RED/BRN 0,5
1
GRY
N
GRN/YEL 1,0 GRN/YEL 1,0
GRN/YEL 1,0 GRN/YEL 1,0 GRN/YEL 1,0 GRN/YEL 1,0 ORN
RED 1,5
BRN 1,50 BRN 0,5 RED/BRN 0,5 BRN
RED 0,5
COMPRESSOR HEATER (IF FITTED)
BRN 0,5 BRN
GRN/YEL GRN/YEL
BRN 1,50 GRN/YEL
BLK 1,5 BLU
BLU 0,5 BLU
BLK 1,5 BLK
W HT 0.5 W HT 0.5
ORN 0,5 GRN/RED 0,5 VIO 0,5
RED/WHT 0,5 BRN
BRN 0,5
22
BLK
21
GRN/YEL
RED/W HT 0,5
WHT
BLU 0,5 BLU 0.5 BLU 0.5
WHT/RED 0,5 BLK
VIO 0,5
ORN 0,5
Page 7
BLK
L
SECTION 5.0 WIRING DIAGRAMS
A1
A2
R2
3
LPHW VALVE
T
VEREISUNGSSCHUTZTHERMOSTAT
CAPACITOR SLOW
CAPACITOR FAST
DELAY TIMER
FUSE
DEFROST THERMOSTAT
C4
C5
D
F
LOW PRESSURE SWITCH
COMPRESSOR MOTOR
FAN MOTOR
RELAY/ CONTACTOR
SWITCH FAN MODE
SWITCH FAN SPEED
DEHUMIDISTAT
TRANSFORMER
THERMAL CUTOUT
LPHW THERMOSTAT
SOLENOID VALVE
LP
MC
MV
K
S1
S2
SH
T
TC
TH
Y
HIGH PRESSURE SWITCH
HP
LAMP
CAPACITOR FAN
FT
FUSIBLE
CAPACITOR RUN
C3
7
9
VOLT FREE
CONDENSATEUR DU VENTILATEUR
CONDENSATEUR DU COMPRESSEUR
CONDENSATEUR DU COMPRESSEUR
SELECTEUR DE MODE DU VENTILATEUR
MOTEUR DU VENTILATEUR RELAIS/ KONTAKTGEBER
COMPRESSEUR
REINITIALISATION DEFAUT BASSE PRESSION
REINITIALISATION DEFAUT HAUTE PRESSION
LAMPE
THERMOSTAT DE DEGIVRAGE
SICHERUNG
TEMPORISATEUR
CONDENSATEUR DU RAPIDE
CONDENSATEUR DU LENT
C3
LPHW BOILER GO SIGNAL
REMOTE HYGROSTAT
12V
12V
7
THERMOSTAT DE DEGIVRAGE TEMPORISE
9
6
Y
H2
REMOTE STAT
1 MV ~
1 R4
3 4
MAGNETVENTIL
PVWV-STAT
UBERHITZUNGSSCHUTZ
TRANSFORMATOR
HYGROSTAT
VANNE ELECTROMAGNETIQUE
THERMOSTAT LPHW
PROTECTION THERMIQUE
TRANSFORMATEUR
HYGROSTAT
SCHALTERANHANGERGESCHWINDIGKEIT LE MOUVEMENT DE VENTILATEUR DE COMMUTATEUR
GEBLASESCHALLTER
RELAIS/ CONTACT
VENTILATORMOTOR
KOMPRESSORMOTOR
NIEDERDRUCKSCHALTER
HOCHDRUCKSCHALTER
LAMPE
VERZOGERUNGSRELAIS
KONDENSATOR SCHNELL
KONDENSATOR VERLANGSAMEN
KONDENSATOR VENTILATOR
KONDENSATOR KOMPRESSOR
KONDENSATOR KOMPRESSOR
ABTAUTHERMOSTAT/-UHR
230V
12V
R1
3
(OPTIONAL)
C2
H1-3
1
3 4
6
2
VALVE UNENERGISED - FLOW DIVERTED
DEFROST THERMOSTAT/TIMER
H3
CAPACITOR START
H1
S1
1
4
A
C5
VALVE ENERGISED - FLOW THROUGH COIL
S2
HIGH
C1
F
R3
2
CONT
1
LOW
A
L3 L2 L1
D
LP
MC
N
GREY
WHT
GRN/YEL
GREEN/YELLOW
VIOLET
WHITE
RED
VIO
PINK RED
PNK
ORANGE
BROWN
GRY ORN
BRN
BLACK BLUE
ZWART
BRN 0,5
GROEN/GEEL
PAARS
WIT
ROOD
ROZE
ORANJE
GRIJS
BRUIN
BLAUW
RED/ORN 0,5 BRN 0,5
RED/ORN 0,5
RED 0,5
ORN 0,5 BLK 1,0
RED 1.5
BRN 0,5
S1 ROCKER SWITCH
CONT
BLU
BLK
CYCLE
BRN 0,5
BLK 0,5
GRN/YEL 1,0
RED 1,50
C1 FAN CAP
CONSOLE EARTH
H1 MAINS
BLK 0,50 BLK 0,50
GRY 0,5
BLK 1,50
HYGROSTAT
H2 DEFROST
BRN 0,5
BRN 0,5
F
4
LP SWITCH
L
H
L1
8
7
GRN/YEL 1,0
LPHW BOILER GO SIGNAL 9
RED/BLK 0,5
LP
PNK 1,50
VIO 0,5
N
BRN 0,5 FLYING LEAD
BLK 0,5
L3
M LPHW VALVE (OPTIONAL)
5
6
L2
PNK 1,50
SH
BLK 1,50 BLK 1,5
9
BRN 0,5
HP
SH HYGROSTAT BREAKS ON FALL
RED 1.5 RED 1.5
3
CYCLE
4
3
REMOTE HYGROSTAT
BLK 1.0 VIO 0,5 PNK 0,5
HP SWITCH
2
1
RED 1.5
4
1
2
REMOTE STAT
6
21
VIO 0,5
D DELAY TIMER
BLK
DEFROST VALVE Y
PNK
RED/WHT 0,5 BLK 0.5
GRY 0,5 PNK 1.5
A2
A1
BLK 0.5
22
VIO 0,5
BLK 0,5
PNK 0,5
GRN/RED 0,5
MV FAN DH110
5
BRN 0,5
R3 CONTACTOR
3
BLK 1,5
BRN 0,5
RED/BLK 0,5 RED/BLK 0,5
BLU 1,5
L
PNK 1,50
RED 1.5
BLK 1,0
HP
H
BLU 1.5
6
BLK
BLK 1,5 BLK 1,0 BLU 0.5
C4
BLU 0.5
RED/WHT 0,5 WHT/RED 0,5
C
RED 0,5
BASE PLATE
BLU
C4 SLOW CAP
S2 HIGH SPEED
COM
ROCKER SWITCH LOW SPEED
PNK
PNK 1.5
ORN 0,5
RED/BLU 0,5 RED 1,5
C
WHT 0.5
RED/ORN 0,5
WHT 0.5
ORN 0,5
BRN 0,5
T TRANSFORMER
RED 1.5
B
R
BLU 1.5
A
6
BRN 0,5 9
GRY 0,5
BLK 0,5 BLK 0,5
WHT 0,5
4
6
9
7
4
7
9
7
R2
4
1
3
6
R4
IF FITTED
HEATER FLYING LEADS
1
RED/BLU 0,5
4
C5 FAST CAP
WHT 0.5
C
3
2
3
1
3
1 R1
A DEFROST STAT/TIMER
GRY 0,5 ORN/BLK 0.5
MC S COMPRESSOR
PNK 1,5
BLK 0,5 BLK 0,5
B
A
BRN 0,5
RED/ORN 0,5
B
A
DRG No D402952
BRN 0,5
GRN/YEL 1,0
ORN/BLK 0.5
ORN 0,5
VIO 0,5
H3 FAULT
RED/BRN 0,5
VIO 0,5
RED/ORN 0,5 WHT 0.5 GRY 0,5
6
GRY
BRN 0,5
5
GRN/YEL 1,0 GRN/YEL 1,0
GRN/YEL 1,0 GRN/YEL 1,0 GRN/YEL 1,0 GRN/YEL 1,0 ORN
RED 1,50 GRN/YEL
RED/BRN 0,5
BLU 1,5
BRN
BLK 0,5 BLU
N
BLU 1.5
ORN 0,5 GRN/RED 0,5 VIO 0,5
COMPRESSOR HEATER (IF FITTED)
BRN 0,5 BRN
GRN/YEL GRN/YEL
WHT 0.5 WHT 0.5
RED 1.5 BLU
BLU GRN/YEL 1,0
RED 0,5
22
BLK
21
ORN 0,5
PNK 1.5 BLK
VIO 0,5
Page 8
BLK
L3 L2 L1
DH/TTW 110 BX (400V ~ 3N 50Hz)
PORT
Page 9
TEV PHIAL TO BE POSITIONED IN 1O O'CLOCK POSITION AND COVERED IN INSULATION
TEV PHIAL
1/2
1/2 X 1/2 X 3/8
1/2
SCHRADER
VIBRATION ELIMINATOR 1/8 OD PIPE 3 COILS OF 40mm DIA
LP SERVICE
LP
1/8
DRIER
3/8
HP
3/8 X 3/8 X 1/4
SCHRADER
HP SERVICE
RECEIVER/DRIER ASSY
PROBE
EVAPORATOR
1/4
3/8
DEFROST
INSULATION
PROCESS
TEV
AIR ON
1/2
RECEIVER
3/8
DEFROST VALVE
LIQUID INDICATOR
3/8
AIR CONDENSER
3/8
SECTION 6.0 REFRIGERATION CIRCUIT
COMP
SECTION 7.0 PERFORMANCE GRAPHS 80%RH
70%RH
(FANS AT FULL SPEED) 60%RH
50%RH
40%RH
7
DH110 6
Litres/hr
5 4
Def rost Zone
3 2 1 0 6
DH75 5
Litres/hr
4 3
Def rost Zone
2 1 0
kW Output @60%RH
5°C
10°C
15°C
20°C
25°C
30°C
35°C
40°C
7 DH110
5 3
DH75
1
kW Input @60%RH
3 2.5 DH110
2 1.5
DH75 1 5°C
10°C
15°C
20°C
Page 10
25°C
30°C
35°C
40°C
SECTION 9.0 OPTIONAL ITEMS, REMOTE CONTROLS. REMOTE HYGROSTAT INSTALLATION INSTRUCTIONS.
PINK
PINK
GREEN/RED
VIOLET
Isolate machine from mains supply before commencing with installation. Remove cover of unit for access to electric box mains supply terminal block. Terminate remote Hygrostat to unit with minimum 0.5mm² cable as shown below.
L/L1 L2 L3 N
TERMINAL BLOCK IN MACHINE
REMOTE HYGROSTAT 1 %
HYGROSTAT (NOT SUPPLIED, WE RECOMMEND CALOREX PART No SD385250. SIEBE PART No 119 1701 91100).
2 REMOVE CONTROL KNOB AND UNDO SCREW TO REMOVE COVER FOR TERMINAL ACCESS
REMOTE THERMOSTAT INSTALLATION MUST BE FITTED TO LPHW VERSIONS
L/L1
L2
L3
N
PINK
GREEN/RED
PINK
VIOLET
Isolate machine from mains supply before commencing with installation. Remove cover of unit for access to electric box mains supply terminal block. Terminate remote Thermostat to unit with minimum 0.5mm² cable as shown below.
TERMINAL BLOCK IN MACHINE
PIN NUMBERS DIFFER
1
JAEGAR
1
(1)
3
(2)
AIR STAT (NOT SUPPLIED, WE RECOMMEND CALOREX PART No SD385251. JAEGER TA630.01, INTERCONTROL Q302.07 (5-60ºC).
Page 19
REMOTE THERMOSTAAT
(1)INTERCONTROLS
REMOTE HYGRO/THERMOSTAT INSTALLATION INSTRUCTIONS. Isolate machine from mains supply before commencing with installation. Remove cover of unit for access to electric box mains supply terminal block. Terminate remote Hygro/Thermostat to unit with minimum 0.5mm² cable as shown below. IMPORTANT NOTE :- Set existing Hygrostat in machine to fully anti-clockwise ie 80% Dehumidification.
L/L1 L2 L3
THERMOSTAT
PINK
GREEN/RED
PINK
VIOLET
HYGROSTAT
TERMINAL BLOCK IN MACHINE
N
SWITCH ON (|) ADJUST CONTROLS TO DESIRED TEMP/ % RH
7 HYGRO/THERMOSTAT (NOT SUPPLIED, WE RECOMMEND CALOREX PART No SD385252. SIEBE PART No 119 7901 100).
5
2 %
|
O ºC
REMOTE HYGRO/THERMOSTAT REMOVE CONTROL KNOB AND UNDO SCREW TO REMOVE COVER FOR TERMINAL ACCESS
Page 20
SECTION 10.0 WARRANTY CONDITIONS The following exclusions apply to the Warranty given by Calorex Heat Pumps Ltd. No claims will be accepted if :1. The dehumidifier is incorrectly sized for the application. 2. The dehumidifier is installed in any way that is not in accordance with the current procedures as defined by Calorex Heat Pumps Ltd. 3. The dehumidifier has been worked upon or is adjusted by anyone other than a person authorised to do so by Calorex Heat Pumps Ltd. 4. The air flow through the machine is outside the specified limits. 5. The water flow through the machine is outside the specified limits. (LPHW units). 6. The electrical supply is insufficient or in any way incorrect. 7. The dehumidifier has suffered frost damage.
IF IN DOUBT PLEASE ASK.
Note:- The Reply Paid Warranty Registration Card must be returned, to ensure that the correct warranty is given.If you do not find a Registration Card with your Dehumidifier please contact the Calorex Service Department giving your name, address and serial number of your Dehumidifier. A card will be sent to you for completion.
Web Site http://www.calorex.com
Email
[email protected]
PHONE 01621 857171
FAX 01621 850871
Please give MODEL NUMBER and SERIAL NUMBER of your Dehumidifier when making technical or service enquiries. This will assist in correct diagnosis and ensure service can provide with a minimum delay.
Page 21