1. Section "Cable Trays for Communications Systems" for cable trays and accessories serving communications systems

County Admin. Offices Remodel, 250 5th Street, Colusa, CA SECTION 260536 - CABLE TRAYS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Secti...
Author: Myra Neal
51 downloads 0 Views 116KB Size
County Admin. Offices Remodel, 250 5th Street, Colusa, CA

SECTION 260536 - CABLE TRAYS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1

SUMMARY A.

Section Includes: 1. 2. 3. 4.

B.

Related Requirements: 1.

1.2

Ladder cable trays. Single-rail cable trays. Trough cable trays. Fiberglass cable trays.

Section 270536 "Cable Trays for Communications Systems" for cable trays and accessories serving communications systems.

ACTION SUBMITTALS A.

Product Data: For each type of product.

B.

Shop Drawings: For each type of cable tray.

C.

Delegated-Design Submittal: For seismic restraints. 1. 2. 3.

1.3

Seismic-Restraint Details: Signed and sealed by a qualified professional engineer, licensed in the state where Project is located, who is responsible for their preparation. Design Calculations: Calculate requirements for selecting seismic restraints. Detail fabrication, including anchorages and attachments to structure and to supported cable trays.

INFORMATIONAL SUBMITTALS A.

Seismic Qualification Certificates: For cable trays, accessories, and components, from manufacturer.

B.

Field quality-control reports.

PART 2 - PRODUCTS 2.1

PERFORMANCE REQUIREMENTS A.

Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design cable tray supports and seismic bracing.

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 1

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

B.

2.2

Seismic Performance: Cable trays and supports shall withstand the effects of earthquake motions. GENERAL REQUIREMENTS FOR CABLE TRAYS

A.

Cable Trays and Accessories: Identified as defined in NFPA 70 and marked for intended location, application, and grounding.

B.

Sizes and Configurations: See the Cable Tray Schedule on Drawings for specific requirements for types, materials, sizes, and configurations.

C.

Structural Performance: See articles on individual cable tray types for specific values for uniform load distribution, concentrated load, and load and safety factor parameters.

2.3

LADDER CABLE TRAYS A.

Description: 1. 2. 3. 4. 5. 6.

7. 8. 9. 10. 11. 12. 13. 14.

2.4

Configuration: Two I-beam side rails with transverse rungs welded to side rails. Rung Spacing: 6 inches o.c. Radius-Fitting Rung Spacing: 9 inches (225 mm) at center of tray's width. Minimum Cable-Bearing Surface for Rungs: 7/8-inch (22-mm) width with radius edges. No portion of the rungs shall protrude below the bottom plane of side rails. Structural Performance of Each Rung: Capable of supporting a maximum cable load, with a safety factor of 1.5, plus a 200-lb (90-kg) concentrated load, when tested according to NEMA VE 1. Minimum Usable Load Depth: 3 inches (75 mm). Straight Section Lengths: 10 feet (3 m) except where shorter lengths are required to facilitate tray assembly. Width: 6 inches (150 mm) unless otherwise indicated on Drawings. Fitting Minimum Radius: 12 inches (300 mm). Class Designation: Comply with NEMA VE 1. Splicing Assemblies: Bolted type using serrated flange locknuts. Hardware and Fasteners: ASTM F 593 and ASTM F 594 stainless steel, Type 316, Steel, zinc plated according to ASTM B 633. Splice Plate Capacity: Splices located within support span shall not diminish rated loading capacity of cable tray.

SINGLE-RAIL CABLE TRAYS A.

Description: 1. 2. 3. 4.

Configuration: Center rail with extruded-aluminum rungs arranged symmetrically about the center rail. Construction: Aluminum rungs mechanically connected to aluminum center rail in at least two places, with ends finished to protect installers and cables. Rung Spacing: 6 inches (150 mm) o.c. Radius-Fitting Rung Spacing: 9 inches (225 mm) at center of tray's width.

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 2

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15.

2.5

Straight Section Lengths: 10 feet (3 m) except where shorter lengths are required to facilitate tray assembly. Width: 6 inches (150 mm) unless otherwise indicated on Drawings. Support Point: Splice fittings shall be hanger support point. Support Spacing: Support each section at midpoint. Support wall-mounted sections a maximum of one-sixth of the section length from each end. Loading Depth: 3 inches (75 mm). Maximum Loads: 25 lb/ft. (37 kg/m). Unbalanced Loads: Maintain cable tray rungs within six degrees of horizontal under all loading conditions. Splicing Assemblies: Bolted type using serrated flange locknuts. Splicing Assembly Capacity: Splices located within support span shall not diminish rated loading capacity of cable tray. Hardware and Fasteners: ASTM F 593 and ASTM F 594 stainless steel, Type 316, Steel, zinc plated according to ASTM B 633. Splices and Connectors: Protect cables from edges of center rail and do not intrude into cable fill area.

TROUGH CABLE TRAYS A.

Description: 1.

2. 3. 4.

5. 6. 7. 8. 9. 10. 11. 12.

2.6

Configuration: Two longitudinal members (side rails) with a solid sheet over rungs exposed on the interior of the trough, or corrugated sheet with both edges welded to the side rails. Rung Spacing: Rungs or corrugations shall be spaced a maximum of 6 inches (150 mm) o.c. and have a minimum flat bearing surface of 2 inches (50 mm). Radius-Fitting Rung Spacing: 9 inches (225 mm) at center of tray's width. Structural Performance: Capable of supporting a maximum cable load, with a safety factor of 1.5, plus a 200-lb (90-kg) concentrated load, when tested according to NEMA VE 1. Minimum Usable Load Depth: 3 inches (75 mm). Straight Section Lengths: 10 feet (3 m) except where shorter lengths are required to facilitate tray assembly. Width: 6 inches (150 mm) unless otherwise indicated on Drawings. Fitting Minimum Radius: 12 inches (300 mm). Class Designation: Comply with NEMA VE 1. Splicing Assemblies: Bolted type using serrated flange locknuts. Splicing Assembly Capacity: Splices located within support span shall not diminish rated loading capacity of cable tray. Hardware and Fasteners: ASTM F 593 and ASTM F 594 stainless steel, Type 316, Steel, zinc plated according to ASTM B 633.

FIBERGLASS CABLE TRAYS A.

Description: 1.

Configuration: Two longitudinal members with rounded edges and smooth surfaces, complying with NEMA FG 1.

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 3

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

2.

3.

4. 5. 6. 7. 8. 9. 10. 11.

2.7

Materials: Straight section structural elements; side rails, rungs and splice plates shall be pultruded from glass-fiber-reinforced [polyester] [vinyl ester] resin, complying with NEMA FG 1 and UL 568. Fasteners: Fiberglass-encapsulated, ASTM F 593 and ASTM F 594 stainless steel, Type 316. Design fasteners so that no metal is visible when fully assembled and tightened. Fastener encapsulation shall not be damaged when torqued to manufacturer's recommended value. Minimum Usable Load Depth: 1 inch (25 mm) according to NEMA FG 1. Straight Section Lengths: 10 feet (3 m). Width: 6 inches (150 mm) unless otherwise indicated on Drawings. Class Designation: Comply with NEMA VE 1. Temperature Rating: Reduce the load rating of tray exposed to temperatures above 75 deg F (24 deg C) according to Table 4-3, "Working Loads," in NEMA FG 1. Fitting Minimum Radius: 12 inches (300 mm). Splicing Assemblies: Minimum four nuts and bolts per plate. Splice plates shall be furnished with straight sections and fittings. Splicing Assembly Capacity: Splices located within support span shall not diminish rated loading capacity of cable tray.

MATERIALS AND FINISHES A.

Steel: 1.

2. 3. 4.

Straight Section and Fitting Side Rails and Rungs: Steel complies with the minimum mechanical properties of ASTM A 1011/A 1011M, SS, Grade 33, ASTM A 1008/A 1008M, Grade 33, Type 2. Steel Tray Splice Plates: ASTM A 1011/A 1011M, HSLAS, Grade 50, Class 1. Fasteners: Steel complies with the minimum mechanical properties of ASTM A 510/A 510M, Grade 1008. Finish: Mill galvanized before fabrication. a.

5. 6.

Finish: Electrogalvanized before fabrication. Finish: Hot-dip galvanized after fabrication. a.

7.

9. B.

Hardware: Chromium-zinc plated, ASTM F 1136 or Stainless steel, Type 316, ASTM F 593 and ASTM F 594.

Finish: Epoxy-resin or Powder-coat enamel paint. a.

8.

Hardware: Galvanized, ASTM B 633 or Chromium-zinc plated, ASTM F 1136.

Hardware: Chromium-zinc plated. ASTM F 1136 or Stainless steel, Type 316, ASTM F 593 and ASTM F 594.

Finish: Factory-standard primer, ready for field painting, with chromium-zinc-plated hardware according to ASTM F 1136. Finish: Black oxide finish for support accessories and miscellaneous hardware according to ASTM D 769.

Aluminum:

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 4

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

1.

2. 3. C.

Stainless Steel: 1. 2.

2.8

Materials: Alloy 6063-T6 according to ANSI H35.1/H 35.1M for extruded components, and Alloy 5052-H32 or Alloy 6061-T6 according to ANSI H35.1/H 35.1M for fabricated parts. Hardware: Chromium-zinc-plated steel, ASTM F 1136, Stainless steel, Type 316, ASTM F 593 and ASTM F 594. Hardware for Aluminum Cable Tray Used Outdoors: Stainless steel, Type 316, ASTM F 593 and ASTM F 594.

Materials: Low-carbon, passivated, stainless steel, Type 304L or Type 316L, ASTM F 593 and ASTM F 594. Hardware for Stainless-Steel Cable Tray Used Outdoors: Stainless steel, Type 316, ASTM F 593 and ASTM F 594.

CABLE TRAY ACCESSORIES A.

Fittings: Tees, crosses, risers, elbows, and other fittings as indicated, of same materials and finishes as cable tray.

B.

Covers: Solid or louvered type made of same materials and with same finishes as cable tray.

C.

Barrier Strips: Same materials and finishes as for cable tray.

D.

Cable tray supports and connectors, including bonding jumpers, as recommended by cable tray manufacturer.

2.9

WARNING SIGNS A.

Lettering: 12 inches (300 mm) high, black letters on yellow background with legend "Warning! Not To Be Used as Walkway, Ladder, or Support for Ladders or Personnel."

B.

Comply with requirements for fasteners in Section 260553 "Identification for Electrical Systems."

2.10 A.

SOURCE QUALITY CONTROL Testing: Test and inspect cable trays according to NEMA.

PART 3 - EXECUTION 3.1

CABLE TRAY INSTALLATION A.

Install cable trays according to NEMA.

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 5

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

B.

Install cable trays as a complete system, including fasteners, hold-down clips, support systems, barrier strips, adjustable horizontal and vertical splice plates, elbows, reducers, tees, crosses, cable dropouts, adapters, covers, and bonding.

C.

Fasten cable tray supports to building structure and install seismic restraints.

D.

Design fasteners and supports to carry cable tray, the cables, and a concentrated load of 200 lb (90 kg). Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems." Comply with seismic-restraint details according to Section 260548.16 "Seismic Controls for Electrical Systems."

E.

Install center-hung supports for single-rail trays designed for 60 versus 40 percent eccentric loading condition, with a safety factor of 3.

F.

Make connections to equipment with flanged fittings fastened to cable trays and to equipment. Support cable trays independent of fittings. Do not carry weight of cable trays on equipment enclosure.

G.

Install expansion connectors where cable trays cross building expansion joints and in cable tray runs that exceed dimensions recommended in NEMA. Space connectors and set gaps according to applicable standard.

H.

Seal penetrations through fire and smoke barriers. Comply with requirements in Section 078413 "Penetration Firestopping."

I.

Install capped metal sleeves for future cables through firestop-sealed cable tray penetrations of fire and smoke barriers.

J.

Install barriers to separate cables of different systems, such as power, communications, and data processing; or of different insulation levels, such as 600, 5000, and 15 000 V.

K.

Install permanent covers, if used, after installing cable. Install cover clamps according to NEMA VE 2.

L.

Install warning signs in visible locations on or near cable trays after cable tray installation.

3.2

CABLE TRAY GROUNDING A.

Ground cable trays according to NFPA 70 unless additional grounding is specified. Comply with requirements in Section 260526 "Grounding and Bonding for Electrical Systems."

B.

Cable trays with electrical power conductors shall be bonded together with splice plates listed for grounding purposes or with listed bonding jumpers.

C.

Cable trays with single-conductor power conductors shall be bonded together with a grounding conductor run in the tray along with the power conductors and bonded to the tray at 72-inch (1800-mm) intervals. The grounding conductor shall be sized according to NFPA 70, Article 250.122, "Size of Equipment Grounding Conductors," and Article 392, "Cable Trays."

D.

Bond cable trays to power source for cables contained within with bonding conductors sized according to NFPA 70, Article 250.122, "Size of Equipment Grounding Conductors."

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 6

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

3.3

CABLE INSTALLATION A.

Install cables only when each cable tray run has been completed and inspected.

B.

Fasten cables on horizontal runs with cable clamps or cable ties according to NEMA VE 2. Tighten clamps only enough to secure the cable, without indenting the cable jacket.

C.

Fasten cables on vertical runs to cable trays every 18 inches (450 mm).

D.

Fasten and support cables that pass from one cable tray to another or drop from cable trays to equipment enclosures. Fasten cables to the cable tray at the point of exit and support cables independent of the enclosure. The cable length between cable trays or between cable tray and enclosure shall be no more than 72 inches (1800 mm).

E.

Tie MI cables down every 36 inches (900 mm) where required to provide a 2-hour fire rating and every 72 inches (1800 mm) elsewhere.

F.

In existing construction, remove inactive or dead cables from cable trays.

3.4

CONNECTIONS A.

3.5

Connect raceways to cable trays according to requirements in NEMA VE 2 and NEMA FG 1. FIELD QUALITY CONTROL

A.

Perform the following tests and inspections: 1. 2.

3.

4. 5. 6.

7. 8.

B.

After installing cable trays and after electrical circuitry has been energized, survey for compliance with requirements. Visually inspect cable insulation for damage. Correct sharp corners, protuberances in cable trays, vibrations, and thermal expansion and contraction conditions, which may cause or have caused damage. Verify that the number, size, and voltage of cables in cable trays do not exceed that permitted by NFPA 70. Verify that communications or data-processing circuits are separated from power circuits by barriers or are installed in separate cable trays. Verify that there are no intruding items such as pipes, hangers, or other equipment in the cable tray. Remove dust deposits, industrial process materials, trash of any description, and any blockage of tray ventilation. Visually inspect each cable tray joint and each ground connection for mechanical continuity. Check bolted connections between sections for corrosion. Clean and retorque in suspect areas. Check for missing, incorrect, or damaged bolts, bolt heads, or nuts. When found, replace with specified hardware. Perform visual and mechanical checks for adequacy of cable tray grounding; verify that all takeoff raceways are bonded to cable trays. Test entire cable tray system for continuity. Maximum allowable resistance is 1 ohm.

Prepare test and inspection reports.

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 7

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

3.6

PROTECTION A.

Protect installed cable trays and cables.

END OF SECTION 260536

CABLE TRAYS FOR ELECTRICAL SYSTEMS

260536 - 8

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

SECTION 265119 - LED INTERIOR LIGHTING PART 1 - GENERAL 1.1

SUMMARY A.

Section Includes: 1. 2.

B.

Related Requirements: 1.

2. 3.

4.

1.2

Interior solid-state luminaires that use LED technology. Lighting fixture supports.

Section 260923 "Lighting Control Devices" for automatic control of lighting, including time switches, photoelectric relays, occupancy sensors, and multipole lighting relays and contactors. Section 260926 "Lighting Control Panelboards" for panelboards used for lighting control. Section 260933 "Central Dimming Controls" or Section 260936.19 "Standalone Multipreset Modular Dimming Controls" for architectural dimming systems and for fluorescent dimming controls with dimming ballasts specified in interior lighting Sections. Section 260943.16 "Addressable-Fixture Lighting Controls" and Section 260943.23 "Relay-Based Lighting Controls" for manual or programmable control systems with lowvoltage control wiring or data communication circuits.

DEFINITIONS A.

CCT: Correlated color temperature.

B.

CRI: Color Rendering Index.

C.

Fixture: See "Luminaire."

D.

IP: International Protection or Ingress Protection Rating.

E.

LED: Light-emitting diode.

F.

Lumen: Measured output of lamp and luminaire, or both.

G.

Luminaire: Complete lighting unit, including lamp, reflector, and housing.

1.3

ACTION SUBMITTALS A.

Product Data: For each type of product, arranged by designation.

B.

Shop Drawings: For nonstandard or custom luminaires.

LED INTERIOR LIGHTING

265119 - 1

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

1. 2.

3. C.

LEED Submittals: 1. 2.

D. 1.4

Include plans, elevations, sections, and mounting and attachment details. Include details of luminaire assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. Include diagrams for power, signal, and control wiring.

Product Data for Credit IEQ 4.2: For paints and coatings, documentation including printed statement of VOC content. Laboratory Test Reports for Credit IEQ 4.2: For paints and coatings, documentation indicating that products comply with the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."

Product Schedule: For luminaires and lamps. Use same designations indicated on Drawings. INFORMATIONAL SUBMITTALS

A.

Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale and coordinated with each other, using input from installers of the items involved:

B.

Seismic Qualification Certificates: For luminaires, accessories, and components, from manufacturer.

C.

Product Certificates: For each type of luminaire.

D.

Sample warranty.

1.5

CLOSEOUT SUBMITTALS A.

1.6

Operation and maintenance data. WARRANTY

A.

Warranty: Manufacturer and Installer agree to repair or replace components of luminaires that fail in materials or workmanship within specified warranty period.

B.

Warranty Period: 5 year(s) from date of Substantial Completion.

PART 2 - PRODUCTS 2.1

PERFORMANCE REQUIREMENTS A.

Seismic Performance: Luminaires shall withstand the effects of earthquake motions.

LED INTERIOR LIGHTING

265119 - 2

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

B.

Seismic Performance: Luminaires and lamps shall be labeled vibration and shock resistant. 1.

2.2

The term "withstand" means "the luminaire will remain in place without separation of any parts when subjected to the seismic forces specified and the luminaire will be fully operational during and after the seismic event."

LUMINAIRE REQUIREMENTS A.

Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B.

NRTL Compliance: Luminaires for hazardous locations shall be listed and labeled for indicated class and division of hazard by an NRTL.

C.

FM Global Compliance: Luminaires for hazardous locations shall be listed and labeled for indicated class and division of hazard by FM Global.

D.

Recessed Fixtures: Comply with NEMA LE 4.

E.

Rated lamp life of 50,000 hours.

F.

Lamps dimmable from 100 percent to 0 percent of maximum light output.

G.

Internal driver.

H.

Nominal Operating Voltage: 120 V ac. 1.

I.

Housings: 1. 2.

2.3

Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless otherwise indicated.

Housing and heat sink. Anodized, powder-coat or painted finish.

CYLINDER A.

2.4

With integral mounting provisions. DOWNLIGHT

A.

Universal mounting bracket.

B.

Integral junction box with conduit fittings.

2.5

LOWBAY A.

Universal mounting bracket.

LED INTERIOR LIGHTING

265119 - 3

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

2.6

RECESSED LINEAR A.

2.7

Integral junction box with conduit fittings. STRIP LIGHT

A. 2.8

Integral junction box with conduit fittings. SURFACE MOUNT, LINEAR

A. 2.9

Integral junction box with conduit fittings. SURFACE MOUNT, NONLINEAR

A. 2.10 A. 2.11 A. 2.12 A.

Integral junction box with conduit fittings. SUSPENDED, LINEAR Integral junction box with conduit fittings. SUSPENDED, NONLINEAR Integral junction box with conduit fittings. MATERIALS Metal Parts: 1. 2. 3.

Free of burrs and sharp corners and edges. Sheet metal components shall be steel unless otherwise indicated. Form and support to prevent warping and sagging

B.

Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under operating conditions, and designed to permit relamping without use of tools. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position.

C.

Diffusers, and Globes: 1. Acrylic: One hundred percent virgin acrylic plastic, with high resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation. 2. Glass: Annealed crystal glass unless otherwise indicated. 3. Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless otherwise indicated.

D.

Housings: 1.

Housing and heat sink.

LED INTERIOR LIGHTING

265119 - 4

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

2. 2.13 A.

2.14

Anodized, powder-coat or painted finish.

METAL FINISHES Variations in finishes are unacceptable in the same piece. Variations in finishes of adjoining components are acceptable if they are within the range of approved Samples and if they can be and are assembled or installed to minimize contrast. LUMINAIRE SUPPORT COMPONENTS

A.

Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for channel and angle iron supports and nonmetallic channel and angle supports.

B.

Single-Stem Hangers: 1/2-inch (13-mm) steel tubing with swivel ball fittings and ceiling canopy. Finish same as luminaire.

C.

Wires: ASTM A 641/A 641 M, Class 3, soft temper, zinc-coated steel, 12 gage (2.68 mm).

D.

Rod Hangers: 3/16-inch (5-mm) minimum diameter, cadmium-plated, threaded steel rod.

E.

Hook Hangers: Integrated assembly matched to luminaire, line voltage, and equipment with threaded attachment, cord, and locking-type plug.

PART 3 - EXECUTION 3.1

INSTALLATION A.

Comply with NECA 1.

B.

Install luminaires level, plumb, and square with ceilings and walls unless otherwise indicated.

C.

Install lamps in each luminaire.

D.

Supports: Sized and rated for luminaire weight.

E.

Flush-Mounted Luminaire Support: Secured to outlet box.

F.

Wall-Mounted Luminaire Support: 1.

2. G.

Attached to structural members in walls or attached to a minimum 20 gauge backing plate attached to wall structural members, or attached using through bolts and backing plates on either side of wall. Do not attach luminaires directly to gypsum board.

Ceiling-Mounted Luminaire Support: 1.

Ceiling mount with two 5/32-inch- (4-mm-) diameter aircraft cable supports.

LED INTERIOR LIGHTING

265119 - 5

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

2. 3. H.

Suspended Luminaire Support: 1. 2.

3.

4. I.

Ceiling mount with pendant mount with 5/32-inch- (4-mm-) diameter aircraft cable supports. Ceiling mount with hook mount.

Pendants and Rods: Where longer than 48 inches (1200 mm), brace to limit swinging. Stem-Mounted, Single-Unit Luminaires: Suspend with twin-stem hangers. Support with approved outlet box and accessories that hold stem and provide damping of luminaire oscillations. Support outlet box vertically to building structure using approved devices. Continuous Rows of Luminaires: Use tubing or stem for wiring at one point and wire support for suspension for each unit length of luminaire chassis, including one at each end. Do not use ceiling grid as support for pendant luminaires. Connect support wires or rods to building structure.

Ceiling-Grid-Mounted Luminaires: 1. 2.

Secure to any required outlet box. Secure luminaire using approved fasteners in a minimum of four locations, spaced near corners of luminaire.

J.

Comply with requirements in Section 260519 "Low-Voltage Electrical Power Conductors and Cables" for wiring connections.

K.

Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."

3.2

FIELD QUALITY CONTROL A.

Perform the following tests and inspections: 1. 2.

Operational Test: After installing luminaires, switches, and accessories, and after electrical circuitry has been energized, test units to confirm proper operation. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify transfer from normal power to battery power and retransfer to normal.

B.

Luminaire will be considered defective if it does not pass operation tests and inspections.

C.

Prepare test and inspection reports.

END OF SECTION 265119

LED INTERIOR LIGHTING

265119 - 6

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

SECTION 265219 - EMERGENCY AND EXIT LIGHTING PART 1 - GENERAL 1.1

SUMMARY A.

Section Includes: 1. 2. 3.

1.2

Emergency lighting units. Exit signs. Luminaire supports.

DEFINITIONS A.

CCT: Correlated color temperature.

B.

CRI: Color Rendering Index.

C.

Emergency Lighting Unit: A lighting unit with integral or remote emergency battery powered supply and the means for controlling and charging the battery and unit operation.

D.

Fixture: See "Luminaire" Paragraph.

E.

Lumen: Measured output of lamp and luminaire, or both.

F.

Luminaire: Complete lighting unit, including lamp, reflector, and housing.

1.3

ACTION SUBMITTALS A.

Product Data: For each type of emergency lighting unit, exit sign, and emergency lighting support, arranged by designation.

B.

Shop Drawings: For nonstandard or custom luminaires. 1. 2.

3. 1.4

Include plans, elevations, sections, and mounting and attachment details. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. Include diagrams for power, signal, and control wiring.

INFORMATIONAL SUBMITTALS A.

Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, coordinated with each other, using input from installers of the items involved:

B.

Product Certificates: For each type of luminaire.

EMERGENCY AND EXIT LIGHTING

265219 - 1

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

C.

Seismic Qualification Certificates: For luminaires, accessories, and components, from manufacturer.

D.

Sample Warranty.

1.5

CLOSEOUT SUBMITTALS A.

1.6

Operation and maintenance data. WARRANTY

A.

Warranty: Manufacturer and Installer agree to repair or replace components of luminaires that fail in materials or workmanship within specified warranty period. 1.

B.

Warranty Period: Two year(s) from date of Substantial Completion.

Special Warranty for Emergency Lighting Batteries: Manufacturer's standard form in which manufacturer of battery-powered emergency lighting unit agrees to repair or replace components of rechargeable batteries that fail in materials or workmanship within specified warranty period.

PART 2 - PRODUCTS 2.1

PERFORMANCE REQUIREMENTS A.

Seismic Performance: Luminaires shall withstand the effects of earthquake motions. 1.

2.2

The term "withstand" means "the luminaire will remain in place without separation of any parts when subjected to the seismic forces specified and the luminaire will be fully operational during and after the seismic event."

GENERAL REQUIREMENTS FOR EMERGENCY LIGHTING A.

Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B.

NRTL Compliance: Fabricate and label emergency lighting units, exit signs, and batteries to comply with UL 924.

C.

Comply with NFPA 70 and NFPA 101.

D.

Comply with NEMA LE 4 for recessed luminaires.

E.

Comply with UL 1598 for recessed luminaires.

F.

Internal Type Emergency Power Unit: Self-contained, modular, battery-inverter unit, factory mounted within luminaire body.

EMERGENCY AND EXIT LIGHTING

265219 - 2

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

1. 2.

3.

Emergency Connection: Operate lamp(s) continuously upon loss of normal power. Connect unswitched circuit to battery-inverter unit and switched circuit to fixture ballast. Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. Environmental Limitations: Rate equipment for continuous operation under the following conditions unless otherwise indicated: a.

b. c. d. 4.

Test Push-Button and Indicator Light: Visible and accessible without opening fixture or entering ceiling space. a. b.

5. 6. 7.

G.

Ambient Temperature: Less than 0 deg F (minus 18 deg C) or exceeding 104 deg F (40 deg C), with an average value exceeding 95 deg F (35 deg C) over a 24-hour period. Ambient Storage Temperature: Not less than minus 4 deg F (minus 20 deg C) and not exceeding 140 deg F (60 deg C). Humidity: More than 95 percent (condensing). Altitude: Exceeding 3300 feet (1000 m).

Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. Indicator Light: LED indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

Battery: Sealed, maintenance-free type. Charger: Fully automatic, solid-state, constant-current type with sealed power transfer relay. Integral Self-Test: Factory-installed electronic device automatically initiates coderequired test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

External Type: Self-contained, modular, battery-inverter unit, suitable for powering one or more lamps, remote mounted from luminaire. 1. 2.

3. 4. 5. 6.

7.

Emergency Connection: Operate lamp(s) continuously. Connect unswitched circuit to battery-inverter unit and switched circuit to luminaire. Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger. Nightlight Connection: Operate lamp in a remote fixture continuously. Battery: Sealed, maintenance-free type. Charger: Fully automatic, solid-state, constant-current type. Housing: NEMA 250, Type 1 enclosure listed for installation inside, on top of, or remote from luminaire. Remote assembly shall be located no less than half the distance recommended by the manufacturer, whichever is less. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

EMERGENCY AND EXIT LIGHTING

265219 - 3

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

8. 9.

2.3

LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. Integral Self-Test: Factory-installed electronic device automatically initiates coderequired test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

EMERGENCY LIGHTING A.

General Requirements for Emergency Lighting Units: Self-contained units.

B.

Emergency Luminaires: 1.

Emergency Luminaires as indicated on drawings, with the following additional features: a. b. c.

2.4

Operating at nominal voltage of 120 V ac. Internal emergency power unit. Rated for installation in damp locations, and for sealed and gasketed fixtures in wet locations.

EXIT SIGNS A.

2.5

Internally Lighted Signs: 1. Operating at nominal voltage of 120 V ac. 2. Lamps for AC Operation: LEDs; 50,000 hours minimum rated lamp life. 3. Self-Powered Exit Signs (Battery Type): Internal emergency power unit. MATERIALS

A.

Metal Parts: 1. 2. 3.

B.

Free of burrs and sharp corners and edges. Sheet metal components shall be steel unless otherwise indicated. Form and support to prevent warping and sagging.

Doors, Frames, and Other Internal Access: 1. 2. 3.

Smooth operating, free of light leakage under operating conditions. Designed to permit relamping without use of tools. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position.

C.

Diffusers and Globes: 1. Acrylic: 100 percent virgin acrylic plastic, with high resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation. 2. Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless otherwise indicated.

D.

Housings: 1. Anodized, powder-coat or painted finish.

EMERGENCY AND EXIT LIGHTING

265219 - 4

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

E. 2.6

Conduit: Minimum 3/4 inch (21 mm) in diameter. METAL FINISHES

A.

2.7

Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast. LUMINAIRE SUPPORT COMPONENTS

A.

Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for channel and angle iron supports and nonmetallic channel and angle supports.

PART 3 - EXECUTION 3.1

INSTALLATION A.

Comply with NECA 1.

B.

Install luminaires level, plumb, and square with ceilings and walls unless otherwise indicated.

C.

Install lamps in each luminaire.

D.

Supports: 1. 2. 3. 4.

E.

Wall-Mounted Luminaire Support: 1.

2. F.

Sized and rated for luminaire and emergency power unit weight. Able to maintain luminaire position when testing emergency power unit. Provide support for luminaire and emergency power unit without causing deflection of ceiling or wall. Luminaire-mounting devices shall be capable of supporting a horizontal force of 100 percent of luminaire and emergency power unit weight and vertical force of 400 percent of fixture weight.

Attached to structural members in walls, or attached to a minimum 20-gage backing plate attached to wall structural members, or attached using through bolts and backing plates on either side of wall. Do not attach fixtures directly to gypsum board.

Suspended Luminaire Support: 1. 2.

3.

Pendants and Rods: Where longer than 48 inches (1200 mm), brace to limit swinging. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers. Support with approved outlet box and accessories that hold stem and provide damping of fixture oscillations. Support outlet box vertically to building structure using approved devices. Continuous Rows of Luminaires: Use tubing or stem for wiring at one point and wire support for suspension for each unit length of fixture chassis, including one at each end.

EMERGENCY AND EXIT LIGHTING

265219 - 5

County Admin. Offices Remodel, 250 5th Street, Colusa, CA

4. G.

Ceiling Grid Mounted Luminaires: 1. 2.

H.

3.2

Do not use ceiling grid as support for pendant luminaires. Connect support wires or rods to building structure.

Secure to any required outlet box. Secure emergency power unit using approved fasteners in a minimum of four locations, spaced near corners of emergency power unit.

Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems." FIELD QUALITY CONTROL

A.

Perform the following tests and inspections: 1.

Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify transfer from normal power to battery power and retransfer to normal.

B.

Luminaire will be considered defective if it does not pass operation tests and inspections.

C.

Prepare test and inspection reports.

END OF SECTION 265219

EMERGENCY AND EXIT LIGHTING

265219 - 6